background image

Wattstopper

 

®

Digital Lighting Management Low Voltage Scene Switch (v3)
Interrupteur d’ambiance à basse tension (v3)
Interruptor de escena de bajo voltaje de control de iluminación digital (v3)

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 23272 – 05/21  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMSW-105

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMSW-105-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltage .............................................................................. 24VDC
Current Consumption .............................................................5mA
Power Supply ................Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network .................... 2 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx 

room controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ................................................. For Indoor Use Only
 

Operating Temperature .................32° to 131°F (0° to 55°C)

 

Storage Temperature ...................23° to 176°F (-5° to 80°C)

 

Relative Humidity .......................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, 

adjustment is optional.

For full operational details, adjustment and more features 

of the product, see the DLM System Installation Guide 

provided with Wattstopper room controllers, and also 

available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable 

regulations, local and NEC codes. 

Wire connections shall 

be rated suitable for the wire size (lead and building wiring) 

employed. 

For Class 2 DLM devices and device wiring: To be 

connected to a Class 2 power source only. Do not reclassify 

and install as Class 1, or Power and Lighting Wiring.

Do not apply cleaning solvent directly onto unit. Apply 

cleaning solvent onto a cloth, then wipe the unit to clean it..

MOUNTING THE SWITCH

WARNING:

 Do not install to cover a junction box having Class 1, 3 or 

Power and Lighting Circuits.

Red LED

Blue Status LEDs

Scene Button (4)

Configuration Button 

(behind switch plate)

Tap when load OFF: 

 Turn ON to last level

Tap when load ON: 

 

Go to full bright

Press & Hold: 

 

Ramp Up

Tap when load ON: 

 Turn OFF

Press & Hold: 

 

Ramp Down

BUTTONS AND INDICATORS

When all loads bound to the dimmer paddle are OFF, it’s 

Blue status LED is dim. When any load bound to the dimmer 

paddle is ON it’s Blue status LED is bright. 
When a scene is active the LED on the scene button is bright.

CONNECTIVITY

The illustrations show examples of free-topology wiring. The LMSW-105 communicates with all other Digital Lighting Management 

devices connected to the low voltage DLM Local Network. 

Line Voltage

Line Voltage

J-Box

Occupancy Sensor

LMRC-212

Dimming

Room

Controller

LMDM-101

Dimming Switch

LMDM-101

Dimming Switch

LMSW-105

Scene Switch

Class 2  0-10 Volt Control Wiring

0-10 Volt

Ballast

0-10 Volt

Ballast

LMRJ Cables

Corner Mount

Occupancy

Sensor

Switch/

Dimmer

Ceiling Mount

Occupancy

Sensor

J Box

To

Load

DLM Local Network

(low voltage, Class 2)

LMRJ cables

LMRC-21x

Room

Controller

To 0-10V 

Dimming Ballast

Daylighting

Sensor

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 –  

IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Summary of Contents for Wattstopper LMSW-105

Page 1: ...the wire size lead and building wiring employed For Class 2 DLM devices and device wiring To be connected to a Class 2 power source only Do not reclassify and install as Class 1 or Power and Lighting...

Page 2: ...rt of the Plug n Go factory default setting The Blue LED will be ON bright for all switch buttons dimmers scene buttons and sensors that are bound to this load Step 2 Load selection 1 Press and releas...

Page 3: ...le solvant de nettoyage sur un chiffon et frotter l appareil pour le nettoyer MONTAGE DE L INTERRUPTEUR MISE EN GARDE Ne pas installer avec une bo te de jonction dot e de circuits de classe 1 3 d ali...

Page 4: ...le maintenir enfonc pendant trois secondes jusqu ce que la DEL rouge de l interrupteur commence clignoter 2 Lorsque l on rel che le bouton de configuration la DEL rouge sur les autres dispositifs com...

Page 5: ...Solo para uso en interiores Temperatura de funcionamiento 0 a 55 C 32 a 131 F Temperatura de almacenamiento 5 a 80 C 23 a 176 F Humedad relativa 5 a 95 sin condensaci n Patente en tr mite Esta unidad...

Page 6: ...do registre la escena Si hay luces en la habitaci n que desea que no est n afectadas por la escena debe desvincular dichas luces del bot n de escena mediante Push n Learn Personalizaci n del usuario S...

Page 7: ...e el interruptor est conectado a la red local DLM 2 Compruebe la entrada de 24 V CC al interruptor Conecte un dispositivo DLM diferente en la ubicaci n del interruptor Si el dispositivo no se enciende...

Page 8: ...s de d fauts de mat riaux et de fabrication pour une p riode de cinq 5 ans Wattstopper ne peut tre tenu responsable de tout dommage cons cutif caus par ou li l utilisation ou la performance de ce prod...