WHAD HE 3-4-5-6 kVA
EN
31
Main features
3 101 66
3 101 67
3 101 68
3 101 69
Rated power
3000 VA
4000 VA
5000 VA
6000 VA
Active power
3000 W
4000 W
5000 W
6000 W
Technology
on-line double conversion
Classification according to EN62040-3: VFI-SS-111
IN/OUT Configuration
Single-phase / Single-phase
Neutral system
Neutral passing straight from input to output (not isolated)
Bypass
Automatic (static)
Manual (for maintenance - optional)
Overvoltage category
OVC II
Input electrical characteristics
3 101 66
3 101 67
3 101 68
3 101 69
Rated input voltage
230 V
Range of input voltages
184 V – 264 V with rated load
Input frequency
50 / 60 Hz ± 2% (autosensing)
50 / 60 Hz ± 14% (by software configuration)
Max input current (with minimum input
voltage and battery charger active)
18 A
24 A
30 A
35 A
Power factor on input
PF > 0,99
Total harmonic distortion of the input current
THDi < 3% (full load)
Inrush current
100% of the rated current
Icp Presumed short circuit current
10 kA
Electrical output characteristics (normal mode)
3 101 66
3 101 67
3 101 68
3 101 69
Rated output voltage
230 V ± 1%
Rated output frequency
50 / 60 Hz
Tolerance on the output frequency
synchronised with the input (with a range of ± 2% to ± 14%,
selected through the software)
± 1% when not synchronised
Max output current
13 A
17,3 A
21,7 A
26 A
Crest factor admitted on the output current
3:1
Total harmonic distortion of output voltage
on linear rated load
< 0,5%
Total harmonic distortion of output voltage
on non-linear rated load
< 3%
Network efficiency (online mode)
up to 96%
Efficiency in ECO MODE
99% max (by software configuration)
Overload admitted
125% for 10 minutes without automatic bypass activation
150% for 60 seconds without automatic bypass activation
8. Technical data