32
8. Technical data
Electrical output characteristics (battery mode)
3 101 66
3 101 67
3 101 68
3 101 69
Rated output voltage
230 V ± 1%
Rated output frequency
50 / 60 Hz ± 1%
Max output current
13 A
17,3 A
21,7 A
26 A
Total harmonic distortion of output voltage
on linear rated load
< 0,5%
Total harmonic distortion of output voltage
on non-linear rated load
< 3%
Overload admitted
115% for 2 minutes
135% 30 second
Batteries and Battery Charger Characteristics
3 101 66
3 101 67
3 101 68
3 101 69
Rated battery voltage
108 Vdc
144 Vdc
180 Vdc
216 Vdc
No. of batteries
9
12
15
18
Battery type
Maintenance-free sealed lead-acid (VRLA) 12Vdc – 9Ah
Type of battery charger
High performance PWM
Recharge curve
Smart Charge, advanced three-stage cycle
Battery charger rated recharge current
2,5 A max
Recharge time up to 90% of the total charge
8 h
Average battery life
3-6 years depending on use and operating temperature
Features
3 101 66
3 101 67
3 101 68
3 101 69
Signals and alarms
Multicolour status indicator, acoustic notification
Communication ports
1 RS232 port, 1 logic contact port, 1 SNMP slot for optional
interfaces
Software
Free “UPS Communicator” software available
for the following functions:
- display of all operating and diagnostic data in case of problems;
- special function setup;
- automatic shutdown of all computers powered by the UPS
(if connected to the TCP/IP network).
A free copy of the free software can be downloaded from
http://www.ups.legrand.com
Protective devices
Electronics against overloads, short-circuit and excessive
battery discharge
Block of functions due to the end of autonomy
In-rush limiter on start up
EPO contact
Integrated backfeed protection