E-Flex CapT2
Installation G
uide F684
F684 R1.00 Lehigh Electric Products Co. 6265 Hamilton Blvd., Allentown, Pa. 18106 Tel: 610-395-3386 www.lehighdim.com
CAT5 Connection Schedule
Wire
Color
Description
1
White/Orange
+24V DC
2
Orange
+24V DC
3
White/Green
CAP1 Signal
4
Blue
CAP2 Signal
5
White/Blue
CAP3 Signal
6
Green
CAP4 Signal
7
White/Brown
COM
8
Brown
COM
Station Configuration
SW1 – CAPx Signal Selection
Each E-Flex relay panel (EFRP) has four discrete CapT signal inputs (CAP1-4) while the E-Flex room controller (EFRC) supports three
signal inputs (CAP1-3) which are then assigned to control selected zones. These input connections are made over a single Cat5 cable;
wires 3 thru 6 carry the CAPx signals (See CAT5 schedule above). The selection of which CAPx input a station will be connected to will
be made at the station using a rotary switch, SW1.
Note: Multiple stations can be set to connect to the same CAPx signal and stations can be connected to more than one E-Flex panel or
room controller.
SW1
CAPx Signal
0
CAP1
1
CAP2
2
CAP3
3
CAP4
SW2 – Preset Bank Select, LED Tracking
SW2 dip switch is used to select preset banks on select stations. The standard CapT2-7 (shown above) provides four preset banks 1-
4, 5-8, 9-12, and 13-16. This dip switch is also used to enable /disable LED tracking on the station. When enabled, the button LED
indicators track the last button pressed. When disabled the button LED indicators are lit only while pressed.
*CapT2-5 Button 1 Function.
Function
SW2-1
SW2-2
SW2-3
CapT2-2
CapT2-5
CapT2-7
Preset Bank 1
ON
ON
N/A
Full/Off
Full*
Preset 1-4
Preset Bank 2
OFF
ON
N/A
Preset 1/OFF
Preset 1*
Preset 5-8
Preset Bank 3
ON
OFF
N/A
Start/Stop Panic
Preset 16*
Preset 9-12
Preset Bank 4
OFF
OFF
N/A
ButtonX
ButtonX
Preset 13-16
Track Last
N/A
N/A
OFF
N/A
N/A
N/A
Lit on Press
N/A
N/A
ON
N/A
N/A
N/A
CapT2 wall stations for the E-Flex Lighting and Energy control system provide a
capacitive touch button interface in a Decora frame. CapT2 wall stations include button
layouts with up to 7-buttons for simple ON/OFF to a 4-preset recall with OFF, and
raise/lower control. The standard 4-preset recall layout is bank selectable via a dip
switch on the rear of the station and can be configured to recall presets 1-4, 5-8, 9-12,
or 13-16 from an E-Flex relay panel or E-Flex room controller. Station interconnects
using standard CAT5 cable.
Power
:
+24V DC
Unit Load
:
.25 (UL=50mA)
Cable Length
:
300 Ft. maximum station to controller