Each model of 5FCC series item is devised with 3 fitting methods: semi-recessed compelte external
mounting or boltless with fast clip(ending Q) on request.
4
.
Safety and caution
Safety warning
:
cooling unit is a kind of precise electrical device, thus please put in down
gently, do not bottom it up or recline it in transportation and storage.
Cautions
:
Clean the filter mesh regularly in the dusty, oily or plush environment; otherwise the
performance may be impacted.
The inlet opening of cooling unit should be located on the top of enclosure.
The temperature surrounding the enclosure shall not exceed 55 degree Celsius and transient
high temperature will not affect the function of cooling unit.
The packaging shows no signs of damage. Oil stains or damaged packaging is an indication
of refrigerant loss and of leakage in the unit system. Any damage to the packaging may be
the cause of subsequent malfunctions.
The protection grade of enclosure must be up to IP54; the condensate may form in case of
any gaps or openings at the enclosure walls.
The distance between 2 units or that away from the wall should not be less than 200 mm.
Air inlet and outlet are not obstructed inside enclosure.Units should only be fitted horizontally
in the specified position. Max. deviation from true Horizontal: 2°
Maintenance and power transmission must be operated by the professional person
To avoid an increase on condensation
,
a door operated switch should be used which will
switch off the cooling unit when the enclosure door is opened.
The heat loss load from inside components should not exceed the rated cooling capacity of
the unit.
The customer must not modify the design or configuration of cooling unit in any way
◆
◆
◆
◆
◆
◆
◆
◆
◆
◆
◆
5. Electrical connection
The
voltage
and
frequent
in
use
must
match
the
data
stated
in
the
rating
plate
of cooling
unit;
Motor
protector
is
suggested
for
the
3
-
phase
cooling
unit
;
for
special
voltage
,
refer
to the
assembly
instruction
for
details
.。
3
.
Assembly
HTTP://WWW.LEIZIG.COM
14