background image

11. Common faults and troubleshooting

Faults

Probable cause

Diagnosis method

Troubleshooting

abnormal voltage

check if the power matches the
stated standard

Adjust the capacity of mains power supply,
voltage and output

contacter fault

check the coils of contacter
if they are burnt out

Replace the contacter

thermostat
malfunction

adjust the thermostat to the
lowest and check if contact can
be connected

replace it in case of disconnection; or
adjust its accuracy in case of connection

overheat protector
burnout

check if it can be connected

replace it in case of disconnection

capacitor aging

check if capacitor has electro
-discharging ability

replace the capacitor

Program error
on control panel

observe the display panel for
the error codes

replace it after cause clarification

condenser dirts

check the dirts in the inner copper
tube of condenser

clean the condenser

incondensable air
in system

check if outlet temperature and
pressure is normal

refill the refrigerant after
vacuumization

condenser fan' filter

mesh dirt blockage

check if the filter mesh is
clogged

clean the filter mesh

condenser fan
no startup

check if the fan(capacitor)
is burnt out

replace the capacitor

Refrigerant leakage system leakage inspection

test and mend the leakage, pressurize and
vacuumize it and contact manufacturer for
commissioning it after refrigerant refilling.

dirt blockage

check if the filter dryer is iced up

replace filter dryer, pressurize and 
vacuumize it and contact manufacturer for 
commissioning it after refrigerant refilling.

breaker malfunction
(wrong use)

check if the breaker is too small
in fuse capacity

The capacity of breaker selected should
be 1.5 of AC working current

compressor
malfunction

check if the insulation of
compressor coils and earthing
are damaged

compressor fan
malfunction

 

evaporator fan
malfunction

check if the insulation of fan
and earthing are damaged

condenser fan filter
mesh dirt blockage

check if the filter mesh is clogged

clean the filter mesh

system leakage

1

.

test

 

the

 

leakage

2

.

measure

 

the

 

current

Contact the manufacturer

system dirt
blockage

check if the filter dryer is iced up

replace filter dryer, pressurize and
vacuumize it and contact manufacturer for
commissioning it after refrigerant refilling.

Contact the manufactuer

Weak cooling

air switch
tripping
after AC
startup

Compressor

not working

System
high pressure
alarm

Compressor
+2 fans working
but not cooling

HTTP://WWW.LEIZIG.COM   

20 

Summary of Contents for 30200001

Page 1: ...Enclosure Climate Control Unit Assembly Instructions FCC FCC225 FCC320 FCC680 FCC825 FCC1100 FCC1500...

Page 2: ...1 2 3 4 5 6 7 8 9 10 11...

Page 3: ...55 230 278 1 264 530 FCC225Q 320Q FCC225 320 FCC225 FCC225P FCC225Q 30200001 30200049 30200547 FCC320 FCC320P FCC320Q 30200002 30200050 30200548 19 20 19 18 19 18 FCC225 FCC320 225 180 R134a 60g 20 5...

Page 4: ...39 30200543 30200549 FCC825 FCC825P FCC825Q 30200540 30200544 30200550 39 40 39 37 38 37 FCC680 FCC825 680 540 R134a 300g 20 55 230 331 50Hz 220 240 414 330x860x173 825 620 R134a 360g 20 55 230 368 50...

Page 5: ...1206 FCC1100 1500 FCC1100Q 1500Q FCC1100 FCC1100P FCC1100Q 30200541 30200545 30200551 FCC1500 FCC1500P FCC1500Q 30200542 30200546 30200552 55 56 55 53 54 53 FCC1100 FCC1500 1100 850 R134a 430g 20 55...

Page 6: ...FCC P Q 4 55 IP54 200mm 2 5 HTTP WWW LEIZIG COM 04 3 6...

Page 7: ...6 1 HTTP WWW LEIZIG COM 05 SET UP DOWN SET UP DOWN SET UP 1 1 2 UP COM ALM UP SET UP UP SET SET UP DOWN 30 DOWN 1 SET DOWN...

Page 8: ...6 2 20 99 9 999 000 10 OFF 6 3 1 SET 35 SET 28 40 SET HTTP WWW LEIZIG COM 06 6 4 DCOM 2 SET 3 SET 1 9 SET 10 0 2 0 2 1 0 2 0 2...

Page 9: ...HTTP WWW LEIZIG COM 07 6 5 5 15 10 6 6 30 1 UP DOWN SET 2 30 3 30 4 30 5 30 7 8...

Page 10: ...2V B A J3 J11 RS485 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 L N PE 1 2 3 4 5 NO NC COM E04 12V NO NC COM 9 10 11 12 13 14 15 16 17 AC12V B A RS485 35 34 33 32 31 30 29 28 27 26 25 24 23...

Page 11: ...HTTP WWW LEIZIG COM 09 11 1 5 1 2...

Page 12: ...ing 3 Assembly 4 Safety and caution 5 Electrical connection 6 Regular operations 7 Working principle 8 Maintenance care 9 Quality warranty 10 Electrical schematic diagram 11 Common faults and troubles...

Page 13: ...eat dissipation items such as air air heat exchanger and filter fan unit 230 278 1 Application 264 530 FCC225Q 320Qcutout drawing FCC225 320cutout drawing FCC225 FCC225P FCC225Q 30200001 30200049 3020...

Page 14: ...CC680 FCC825 680 540 R134a 300g 20 55 230 331 50Hz 220 240 414 330x860x173 825 620 R134a 360g 20 55 230 368 50Hz 220 240 460 IP54 55dB A IP54 55dB A 330x860x173 164 860 265 394 154 82 230 290 230 183...

Page 15: ...1500P FCC1500Q 30200542 30200546 30200552 55 56 55 53 54 53 Model col FCC1100 FCC1500 1100 850 R134a 430g 20 55 230 515 50Hz 220 240 644 450x1250x185 1500 1200 R134a 550g 20 55 230 589 50Hz 220 240 73...

Page 16: ...ent malfunctions The protection grade of enclosure must be up to IP54 the condensate may form in case of any gaps or openings at the enclosure walls The distance between 2 units or that away from the...

Page 17: ...WN to increase or decrease the value then validate it and return to lookup status by a short press of SET again UP Incr 1 2 In setting interface a short press makes the value increased progressively 1...

Page 18: ...binet inside temperature if the remote control points are short circuited it will show the unit is closing down Setting In the setting interface the 1st Nixie tube displays the setting codes the next...

Page 19: ...rger than the shortest halt time In case of communication malfunction he display will keep in memory the interface before the fault The compressor will restart in 1 min delay after the reset of compre...

Page 20: ...ational certification The fan of ball bearing has a lifespan up to 30 000 hour The filter mesh is recommended to use in case of dense dusts and clean at twice every month Turn off the power if the coo...

Page 21: ...13 14 15 16 17 E04 AC12V B A J3 J11 RS485 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 L N PE 1 2 3 4 5 NO NC COM E04 12V NO NC COM 9 10 11 12 13 14 15 16 17 AC12V B A RS485 35 34 33 32 31 30...

Page 22: ...p check if the fan capacitor is burnt out replace the capacitor Refrigerant leakage system leakage inspection test and mend the leakage pressurize and vacuumize it and contact manufacturer for commiss...

Page 23: ......

Page 24: ...1609 Fax 023 67852033 75 15F1212 350000 Tel 0591 83324546 Fax 0591 83325725 4 1816 545000 Tel 0771 2022453 Fax 0771 2022453 167 829 510610 Tel 020 61135589 Fax 020 86450775 1 E 1603 518052 Tel 0755 61...

Reviews: