LEMA Off-Grid User Manual (DM-003-A)
© 2021 LEMA - lema.io
Saint Paul, Minnesota, USA
Page |
78
WARNING –
Before installing or uninstalling batteries, make sure all 5 circuit
breakers are in the OFF (Disconnected) position. The OFF position is when the
switch it toggled down to the ground. The five circuit breakers are: 4A, 15A, 30A,
80A, 20A AC.
Upon opening the LEMA Off-Grid Electrical Enclosure for the first time, inspect the unit for any loose or damaged wires
or components. (The Battery Cables and Upper Battery Mounts should be the only floating/loose cables).
The batteries are labeled BAT 101, BAT 102, BAT 103 and BAT 104. The cables and battery terminals are also labeled.
For example, a Battery Cable labeled “117 [+] [4]” connects to the battery terminal labeled “117 [+] [4]”.
Here is an example where you can see a Battery Cable end labeled “115 [-] [3]” which lands on a battery terminal
labeled “115 [-] [3]”.
Figure 5-60 - Battery “BAT 102” Terminal Labels
The following is a sequence of images which illustrates the order to install the batteries.
Note the two battery harness arms need to be held up while batteries physically moved into position.
Cut the zip ties and unwind the Battery Cables that are around the Upper Battery Mounts.