INITIAL START UP
INITIAL START UP
1.Open all valves in the water inlet and/or water outlet
to allow water to flow into the pump.
2.Fill the pool and spa with water following the
manufacturers instructions.
3.Check all plumbing connections for leaks.
ONCE THE POOL AND SPA ARE FILLED WITH
WATER (BETWEEN 40 AND 104
E
F) COMMENCE
START UP PROCEDURES
You must successfully complete all of the steps in this
procedure. If you encounter a problem, check and
repair your installation immediately and begin the
procedure again.
4.Turn power OFF.
5.Turn timer(s) OFF.
6.Verify water temperature is between 40 and 104
E
F
7.Turn power ON.
SPA WATER TEMPERATURE SETTING
#
The spa water temperature is controlled by the
maintenance control or the wireless remote control.
To set the spa water temperature, refer to the
temperature setting instructions.
#
Do not expect to feel hot water coming from the jets.
#
The length of time it takes for the spa water to reach
the desired temperature depends on several factors:
Water temperature at start
Ambient air temperature
Quantity of water in spa
Insulating qualities of the spa cover and enclosure
#
An insulating cover should be kept on the spa at all
times when not in use. Also, remember that
prolonged use of the air system and hydrotherapy jets
when using the spa will have a significant cooling
effect on the spa water.
LCD WARNING DISPLAYS
High Temperature Warning
Digital temperature displays will flash when water
temperatures range between 109
E
F and 120
E
F
Hi Limit Reached
System will automatically lock out the heater in spa
mode whenever the water temperature reaches 120
E
F.
In the event that the water reaches this preset hi limit,
the warning message “OH” (Over Heat) will replace the
digital temperature display. As the water cools to
below 120
E
F, the OH warning will be replaced by an
alternating display that shows the actual spa water
temperature and “HL”(Heater Lockout). Flashing
temperature and “HL” display continues until the hi limit
is manually reset. Manual reset is accomplished by
depressing the temperature up and down buttons
simultaneously.
SPA SHOULD NOT BE USED UNTIL THE SYSTEM
HAS BEEN INSPECTED AND REPAIRED
Inoperative Temperature Control
In the event that the temperature control system fails,
one of two warning messages will appear on the LCD
display:
OP - Temperature sensor has failed in the open
position.
SH - Temperature sensor has failed due to electrical
short circuit.
SPA SHOULD NOT BE USED UNTIL THE SYSTEM
HAS BEEN INSPECTED AND REPAIRED