Overview of Elevator Control

External (Cabinet) Tamper

An external cabinet tamper is configured by connecting a tamper device 
across pins 3 & 4 of J18 on the SDC. If not used, a jumper must be installed 
across pins 3 & 4 of J18.

Note:

Power fail is not supported on the SDC; therefore no jumper is 
required. This is labeled in the diagram as “NOT USED.”

External tamper wiring

Note:

Input status LEDs will be off when the tamper device is in closed 
position or the jumper is installed.

Power and Communications

For its power input, the SDC requires a 12 to 24 VDC ± 10% power source 
for it input power.
Wire the power input with 18 AWG (minimum) twisted pair cable.

Power source wiring

Notes:

Be sure to observe polarity.

Do not use an AC transformer to directly power the Single Door 
SDC Interface Module.

Intelligent System Controller

Output 

Control 
Module

Elevator 

Reader

(inside cab)

Input Control 

Module

Access 
Control 
System

Elevator Control Room

Up to 128 Outputs - 

eight Output Control 

Modules

Up to 128 Inputs - 

eight Input Control 

Modules

Single Reader Interface

Single 

Reader 

Interface 

Module

Single 

Reader 

Interface

Maximum: 

4000 feet

(1219.2 meters)

5 conductors

Power Source

Requirements

Current

DC power source

Isolated, non-switching, 
regulated DC power

700mA for 12VDC
350mA for 24VDC

Summary of Contents for LNL-1300-U

Page 1: ...es a 12 to 24 VDC power source SDC board Dimensions are in inches mm Package Contents LNL 1300 U board 1000 ohm resistors Installation To install the SDC perform the installation procedures described...

Page 2: ...bps off ON off ON 38400 bps ON ON ON ON SW1 Switch 5 State ON LEDs behave as the Access LNL series module off LED behavior is in Normal Mode Address SW2 switch 5 4 3 2 1 0 off off off off off 1 off o...

Page 3: ...Ds LED Table for Series 2 LNL 1300 Mode When switch 5 is in the ON position the LEDs behave like the series 2 LNL 1300 LED Table for Normal Mode When SW1 switch 5 is in the off position the LEDs opera...

Page 4: ...modem packet and terminated the firmware download operation Invalid Application firmware for module CPU 3 Red 0 Green The module is not operational Application firmware loaded on the module will not r...

Page 5: ...hms maximum Belden 9841 West Penn or equivalent The drop cables to downstream devices should be kept as short as possible no longer than 10 feet The RS 485 communication is asynchronous half duplex us...

Page 6: ...ing LCD reader display control Wiring for OSDP readers Elevator Control OnGuard hardware is capable of supporting elevator control for up to 128 floors An elevator reader has an input output module th...

Page 7: ...uires a 12 to 24 VDC 10 power source for it input power Wire the power input with 18 AWG minimum twisted pair cable Power source wiring Notes Be sure to observe polarity Do not use an AC transformer t...

Page 8: ...o 95 at 85 C 185 F non condensing storage Certifications FCC Part 15 FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15...

Reviews: