UL Listed Systems: Notes and Requirements
46 —
revision 1.007
12. A mechanical ringer shall give an indication automatically to the user when only 5 minutes operating
power remains in the sounding device.
13. There shall be provision for testing or automatic meter supervision over all sources of electrical energy.
If testing is used, it is to be made under load with the sounding device operating.
14. To be installed with UL Listed high security cable such as Beldon model 9512, 8444.
11.3
Burglar Alarm (Bank Safe and Vault)
1. Same as local burglar alarm above except installed with Listed, Rothenbuhler Engineering, Model 5110
Electronic Sounding Device.
2. One 17 Ah battery shall be used to provide the 72 hours standby time followed by 15 minutes of alarm
and extended power loss of 72 h.
11.4
Burglar Alarm (Police Connect)
Grade A - Dact+Bell, High Line Security (AA) - Packet Switched Data Network
Same as local burglar alarm above. System supplies standard line security (DACT) when used with IP
Module 650-9060 as defined in UL 365.
11.5
Burglar Alarm (Central Station)
Grade C - Dact, Grade AA - Packet Switched Data Network, Grade B - Dact+, Grade A -
Bell+Bell Housing
Same as local burglar alarm above. The system shall be programmed to transmit the required opening and
closing signals. The system shall be programmed to transmit the required opening and closing signals.
11.6
Burglar Alarm (Proprietary)
Grade A-Dact, Grade A - Packet Switched Data Network
Same as Central Station.
11.7
Household Fire Alarm
1. If any fire alarm circuits are present on the zone expansion devices, the Amseco Model PAL 328N
trouble annunciating device shall be connected to an open collector output programmed to activate if
the bus fails. The device provides supervision of the remote fire alarm initiating circuits.
2. A Listed audible signaling device suitable for fire, rated to operate over the range of 11.0 to 12.3 V shall
be used.
3. The maximum total current draw from auxiliary, SNAPP, and outputs 1, 2, combined shall not exceed
1.0 A.
Summary of Contents for OnGuard 2013
Page 1: ...PERPETUAL INNOVATION 2013 NGP Keypad Installation Guide...
Page 5: ...COMPLIANCE STATEMENTS...
Page 6: ......
Page 10: ...Compliance Statements 10 revision 1 007...
Page 11: ...HARDWARE COMPONENTS...
Page 12: ......
Page 28: ...Hardware Components 28 revision 1 007...
Page 29: ...PROGRAMMING THE SYSTEM...
Page 30: ......
Page 36: ...Programming the System 36 revision 1 007...
Page 37: ...DIAGNOSTICS...
Page 38: ......
Page 40: ...Diagnostics 40 revision 1 007...
Page 41: ...UL LISTED SYSTEMS...
Page 42: ......
Page 48: ...UL Listed Systems Notes and Requirements 48 revision 1 007...
Page 50: ...Index 50 revision 1 007...