background image

Tamper 

GPO1

GPO2

GND 

B/RX

A/TX

GND

DC+ 

CP 

D1 Clock 

D0 Data 

GND 

G-LED

R-LED

BZ CTRL

K-LED

Tamper output 

General purpose I/O

 

General purpose I/O

 

Ground

RS485 - / OSDP

 

RS485 + / OSDP

 

Power supply

Power supply 9 

to

 30 VDC 

Card Present 

Wiegand Data1/Clock/Data 

Wiegand Data0/Clock/Data

Ground 

External Green LED control 

External Red LED control 

External Buzzer control 

External keypad LED control

PIN

Description

Description

Wiegand

Wiegand

x

-

-

-

-

-

x

x

-

x

x

-

x

x

x

x

Terminal description

RS485/

OSDP

RS485/

OSDP

Clock/

Data

Clock/

Data

-

-

-

-

x

x

x

x

-

-

-

-

-

-

-

-

-

-

-

-

x

x

x

x

x

-

-

-

-

-

-

-

P2

P1

PIN

K-LED

BZ CTRL

R-LED

G-LED

GND

D0 Data

D1 Clock

CP

Tamper

GPO1

GPO2

GND

B/RX

A/TX

GND

DC+

P1

P2

Tamper 

GPO1

GPO2

GND 

B/RX

A/TX

P1

P2

CP 

D1 Clock 

D0 Data 

GND 

G-LED

R-LED

BZ CTRL

K-LED

Quick Installation Guide

LenelS2 Readers - 5000 Series Standard 13.56 MHz 

LenelS2 Readers - 5000 Series Standard 13.56 MHz/125 kHz

GND

DC+ 

Quick Installation Guide

LenelS2 Readers - 5000 

Series Slimline 13.56 MHz

Please note that this is only a quick installation guide.  

Information regarding recommendations, measurements and accessories are 

available in the full version of the Lenel

S2

 Readers - 5000 Series installation 

guide.

1   Current draw does not include heater consumption.

2   LED settings; LED Bar = Low, Back Light = Low

Please consult table in full installation manual for more information on heater 

consumption settings and how the LED-settings will affect current draw.

Power consumption:

Notes

1.

Maximum 

W

iegand cable length is 150 meters and requires a high quality

shielded cable with minimum AWG18 dimension (=0.8231

 

mm

2

) in an environment

free from electrical noise. A cable with smaller dimension or an installation
environment with electrical disturbances will reduce the maximum cable length.

2.

 Wiegand & Clock/Data requires dedicated wires for external control of Green

LED, Red LED, Buzzer and Keypad backlight.

3.

When utilizing the GPI/O’s, each respective GPO1 or GPO2 must be connected

to each respective pin and also to GND. The general purpose input/output will only
be activated if so applied in the reader configuration.

4.

RS485/OSDP requires twisted pair cable.

Model

Current draw (idle

1

Current draw (peak

1,2

)

12

 

V

24

 

V

12

 

V

24

 

V

Standard 13.56

 

MHz

50 mA

40 mA

147 mA

99 mA

Standard 

13.56 MHz/125 kHz

90 mA

60 mA

187 mA

119 mA

Slimline 13.56

 

MHz

50 mA

40 mA

164 mA

108 mA

Please note that this is only a quick installation guide. 

Information regarding recommendations, measurements and QR code modules and other 

accessories are available in the full version of the LenelS2 Readers - 5000 Series installation 

guide.

Please consult table in the full installation manual for more information on heater

consumption settings and how the LED-settings will affect current draw.

12 VDC

12 VDC

24 VDC

24 VDC

Reviews: