background image

10

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Chimney Connector Systems and Clearances from Combustible 

Walls for Residential Heating Appliances (NFPA 211)

Refer to 

Figure 8

System  A.

  Minimum  3.5  in.  (90  mm)  thick  brick  masonry  wall 

framed into combustible wall with a minimum of 12 in. (305 mm) 

brick separation from clay liner to combustibles. Fireclay liner (ASTM 

C 315, Standard Specification for Clay Flue Linings, or equivalent), 

minimum 5/8 in. (16 mm) wall thickness, shall run from outer surface 

of brick wall to, but not beyond, the inner surface of chimney flue 

liner and shall be firmly cemented in place.
Clearance: 12 in. (305 mm)

System B

. Solid-insulated, listed factory-built chimney length of the 

same inside diameter as the chimney connector and having 1 in. 

(25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air 

space between the outer wall of the chimney length and combustibles.
The inner end of the chimney length shall be flush with the inside of 

the masonry chimney flue and shall be sealed to the flue and to the 

brick masonry penetration with non-water-soluble refractory cement. 

Supports shall be securely fastened to wall surfaces on all sides.
Fasteners between supports and the chimney length shall not pen-

etrate the chimney liner.
Clearance: 9 in. (229 mm)

System C.

 Sheet steel chimney connector, minimum 24 gauge [0.024 

in. (0.61 mm)] in thickness, with a ventilated thimble, minimum 24 

gauge [0.024 in. (0.61 mm)] in thickness, having two 1 in. (25.4 

mm) air channels, separated from combustibles by a minimum of 6 

in. (152 mm) of glass fiber insulation. Opening shall be covered, and 

thimble supported with a sheet steel support, minimum 24 gauge 

[0.024 in. (0.61 mm)] in thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 6 in. (152 mm)  

System D.

 Solid-insulated, listed factory-built chimney length with 

an inside diameter 2 in. (51 mm) larger than the chimney connector 

and having 1 in. (25.4 mm) or more of insulation, serving as a pass-

through for a single wall sheet steel chimney connector of minimum 

24 gauge [0.024 in. (0.61 mm)] thickness, with a minimum 2 in. 

(51 mm) air space between the  outer wall of chimney section and 

combustibles. Minimum length of chimney section shall be 12 in. 

(305 mm). Chimney section concentric with and spaced 1 in. (25.4 

mm) away from connector by means of sheet steel support plates 

on both ends of chimney section. Opening shall be covered, and 

chimney section supported on both sides with sheet steel supports 

of minimum 24 gauge [0.024 in. (0.61 mm)] thickness.
Supports shall be securely fastened to wall surfaces on all sides and 

shall be sized to fit and hold chimney section. Fasteners used to secure 

chimney section shall not penetrate chimney flue liner.
Clearance: 2 in. (51 mm)

Additional requirements:

1. Insulation material used as part of wall pass-through system shall be 

of noncombustible material and shall have a thermal conductivity of 

1.0 Btu-in./hr-ft

2

 - ºF (4.88 kg-cal/hr-m

2

 - ºC) or less.

2. All clearances and thicknesses are minimums; larger clearances and 

thicknesses shall be permitted.

3. Any material used to close up an opening for the connector shall be of 

noncombustible material.

4. A connector to a masonry chimney, except for System B, shall extend 

in one continuous piece through the wall pass-through system and the 

chimney wall to the inner face of the flue liner, but not beyond.

Factory Built 

Chimney Length 

Air Space – 9 in. 

(228.6mm) Min. 

Chimney Length 

Flush with 

Inside of Flue 

Min. Clearance 

9 in. (229mm) 

Chimney 

Connector 

Use Chimney 

Mfrs. Parts to 

Attach 

Connector 

Solid-Insulated 

Listed Factory-

Built Chimney 

Length

Sheet Steel Supports

Sheet Steel Supports

Sheet Steel Supports

Minimum Chimney Clearance from Masonry to Sheet Steel 

Supports & Combustibles – 2 in. (51mm) 

Nonsoluble 

Refractory  

Cement

Minimum chimney clearance to sheet

steel supportrs and combustibles

2 in. (51mm)

Chimney 

Connector 

2 Air Channels, Each 1 

in. (25.4 mm) 

2 Ventilated Air 

Channels, Each 

1 in. (25.4 mm) 

Construction of 

Sheet Steel 

Minimum chimney clearance to sheet steel 

supports and combustibles 2 in. (51mm) 

Sheet Steel 

Supports 

Chimney 

Connector 

Chimney 

Section

Air Space – 2 in. 

(51mm) Min. 

Chimney connector  

Chimney length

1 in. (25.4 mm) 

air space to 

        chimney length

Min. Clearance  

2 in. (51 mm) 

Minimum

12 in. (305mm)

to combustibles

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Masonry chimney

constructed to NFPA 211

Minimum chimney clearance to brick

and combustibles 2 in. (51mm)

Minimum clearance

12 in. (305mm)

of brick

Chimney

Chimney

flue

Chimney

flue

Chimney

flue

connector

Fire clay

liner

Figure 8 - 

Chimney Connector Systems and Clearances from Combustible Walls

System A

System B

System C

System D

Summary of Contents for CANYON ST310

Page 1: ... A French manual is available upon request Order P N 775217CF Ce manuel d installation est disponible en francais simplement en faire la demande Numéro de la pièce 775217CF This appliance must be properly installed and operated in order to prevent the possibilityofahousefire Pleasereadthisentireinstallationandoperation manual before installing and using your wood stove Failure to follow theseinstr...

Page 2: ...cting the Proper Venting System 4 Negative Pressure Warning 5 Creosote 5 Disposal of Ashes 5 Fuel 5 Paint Curing 5 Burn In Period 5 Clearances to Combustibles 6 7 Floor Protection 6 7 Alcove Clearances 6 Chimney and Connector 6 Components Required for Installation 6 Installation Clearances Figures 7 Typical Installation Figures 8 Chimney Installation 9 Manufactured mobile Home Installations 9 Chim...

Page 3: ...h during the burn ing season to check for soot and creosote accumulations Any accumulations over 1 8 thick should be removed by a professionalchimneysweep Donotattempttoburnoutheavy creosoteaccumulationswithahotfire Iflargeaccumulations are occurring review your burning procedures 14 If a creosote fire should develop the fire department should be called immediately and then attempts should be made...

Page 4: ...the connected appliance in accordance with the manufacturer s instructions Chimney Guidelines This appliance requires approximately 12 feet minimum of effective draw provided by the venting system As a rule of thumb every 90 degree total direction change in the venting will result in a loss of approximately 5 feet of effective draw Example If two 45 degree offsets are used subtract 5 feet from the...

Page 5: ...ioned sources Outside air connected to the appliance probably will not resolve such a problem as the stove or fireplace insert is not the source of negative pressure Lennox Hearth Products accepts no liability for damages resulting from negative pressures described here Ventilation Requirements Provide adequate air for combustion The fresh air requirements of this appliance must be met within the ...

Page 6: ...ent length above the flue outlet exceeds 14 feet it is recommended that the 8 to 6 pipe reducer is used and a 6 venting system be installed This appliance may be vented into a code approved masonry chimney with flue liner Warning Chimney connector must be in good condition and kept clean Do not install damaged parts Residential chimney systems must be from the same brands of double wall pipe as li...

Page 7: ...l distances should be measured from the stove s flue collar 2 Minimum noncombustible hearth pad dimensions 3 Not applicable to alcove installations 4 In corner applications when installed at minimum back wall clearances the required floor protection is dimensioned off the back plane of the stove therefore the floor protection required off the back corners at a 45 degree angle only needs to extend ...

Page 8: ...R Using 6 or 8 Diameter Rigid Stainless Steel Liner Figure 5 Typical Installation Figure 6 Connected to a Masonry Chimney Floor Protector Floor Protector Fasten each stove pipe connection with at least 3 sheet metal screws Single wall stove pipe must not pass through attics closets walls or ceilings It is used to connect this appliance to a factory built or masonry chimney INSTALL VENTING SYSTEM P...

Page 9: ... chimney termination All mobile home installa tions require an outside air kit see Page 27 for ordering information and the stove must be secured to the floor and grounded to the mobile home chassis Install Outside Air Kits per instructions on Page 11 INSTALL VENTING SYSTEM PER VENT MANUFACTURERS INSTRUCTIONS Fasten stove pipe to flue collar using 3 sheet metal screws SecureStove to floor Grounded...

Page 10: ...ll be 12 in 305 mm Chimney section concentric with and spaced 1 in 25 4 mm away from connector by means of sheet steel support plates on both ends of chimney section Opening shall be covered and chimney section supported on both sides with sheet steel supports of minimum 24 gauge 0 024 in 0 61 mm thickness Supports shall be securely fastened to wall surfaces on all sides and shallbesizedtofitandho...

Page 11: ... the contents upon receipt and check for any damaged or missing parts If there is hidden damage notify your freight company or Lennox Hearth Products dealer im mediately CAUTION Wear gloves during installation in case of sharp edges on the stove Leg Installation 1 Carefully place stove on its back Be careful not to scratch the stove use a piece of cardboard or carpet to protect the back of the sto...

Page 12: ...washer and screw in that leg as well 9 Install bricks and baffle as per instructions on Pages 14 and 15 It is highly recommended that the baffle be assembled before the chimney is installed so that the baffle blankets can be adjusted into place through the flue collar 10 If installed into a mobile home the stove shall be grounded to the mobile home chassis with a 8 AGW copper wire or equivalent 11...

Page 13: ...ole s center should be 3 76 mm directly forward from the center of the flue outlet or locate as per the instructions below 6 Position the stove on your floor protection in the exact location where it is to be located making sure all minimum clearances are met Mark the floor protection where the pedestal will be located then remove the stove 7 Make four 1 1 2 38 mm cuts in one end of the corrugated...

Page 14: ...unit Once you have the first two boards installed slide the board to the left side of the baffle support all the way to the left and rear of the unit You will slide the board to the right side of the secondary support to the right and rear of the unit Next you will install the two remaining boards where you originally installed the first two boards on each side of the baffle support and pushed aga...

Page 15: ... X 8 3 4 B 6 1 2 X 4 1 2 C 3 1 2 X 9 D 1 1 2 X 4 1 2 E 3 7 8 X 9 F 4 1 2 X 9 H 3 1 2 X 4 1 2 K 3 X 7 M 4 1 2 X 4 1 2 Figure 14 26 B 27 B 28 M 29 B 30 B 1 F 2 F 3 F 4 F 5 F 6 F 7 F 8 F 9 E 31 A 32 A 34 A 33 A 10 F 11 F 12 F 13 E 14 F 15 F 16 F 17 F 18 F 19 C 20 H 21 C 24 D 22 F 23 F 25 D Side View M Brick These bricks go up against the stoves back wall 1 2 2 1 2 M 4 1 2 Firebox Brick Side Cut A Way...

Page 16: ... produce extreme temperatures within the appliance Damage caused from over firing is not covered under the manufacturers limited warranty 5 For best results use smaller pieces of wood to get the insert tem perature very high before loading larger wood for sustained burns If necessary crack the door to allow ignition of the fuel charge Do not leave the unit unattended while the front door is slight...

Page 17: ...ac cordingly to ensure un interrupted blower operation For example a small fire may require a slower blower speed to keep the heat output by the blower consistent If the blower is operated in manual mode it may be necessary to adjust the blower speed as the fire begins to burn down and the appliance is no longer hot enough to effectively heat the air moved by the blower If the air coming from the ...

Page 18: ...Elites locate thermometer on the face of the insert just above the door Now load the firebox and set the draft control At this point you may need to burn the stove with the draft open for a few minutes to ignite the wood All Country Collection stoves are EPA tested for emissions at low burn with the air control completely closed Whether or not you should burn your stove with the air control comple...

Page 19: ...inge pin by pulling up while holding the op posite side of the door Lift door out of the lower hinge pin and place face down on a soft surface Step 2 Remove Door Back Screws 6 ea Using a 5 32 allen wrench remove the 6 retainer screws from the faceplate To locate screws peel back the door gasket as necessary Step 3 Disassemble Door Assembly Flip door assembly over to be face up Separate faceplate f...

Page 20: ...ES WHEN 1 If smoke is entering the room check to make sure your baffle boards are properly installed DOOR IS OPEN and that the baffle blankets are pushed back flush with the front of the baffle boards 2 Check the chimney for blockage due to creosote see Chimney and Creosote sections on Pages 5 and 6 3 Check draft See POOR DRAFT section above WOOD BURNS 1 The draft control must be closed further TO...

Page 21: ...T Close the door tightly during Burn In Period DO Be sure to clean any fingerprints from optional accessories that have plated surfaces before burning the appliance Clean the plated surfaces only with household type glass cleaner and a very soft cloth DO Consult local building department if other than recommended clearances are desired DO Read instructions for the baffle boards and baffle blankets...

Page 22: ...71117 Bottom Heatshield 24 H5662 Cascade Olympic Leg Kit Outside Air Plenum Box ContactanLennoxHearthProductsdealertoobtainanyofthese parts Neverusesubstitutematerials Useofnon approvedparts can result in poor performance and safety hazards FSB BLOWER PARTS 25 H8062 FSB700 Blower Only Assembly w blower wiring har ness 26 H5658 Fan Blade FSB700 27 H5657 Fan Cage FSB700 28 H8063 FSB700 Blower Only W...

Page 23: ... NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 34 47 48 49 33 35 41 41 39 39 39 42 39 39 39 39 39 39 39 39 39 39 38 37 41 41 39 39 39 42 36 43 45 43 44 39 39 44 40 40 46 40 40 ...

Page 24: ...24 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 Door Parts Blower Parts 25 29 31 28 27 26 32 30 7 11 10 6 9 5 4 4 1 8 2 3 ...

Page 25: ...25 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 22 24 18 20 21 23 Leg and Leg Parts ...

Page 26: ...26 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE Replacement Parts Model ST310 15 18 15 18 19 16 17 19 Ash Drawer Pedestal and Pedestal ...

Page 27: ...oz Aerosol 71134 Reducer 6 8 Pipe Reducer from 8 to 6 Stainless H5308 W LEGF LBRKT Leg Fasetening L Brackets 4 per pkg Tie down kit to be used in mobile or modular homes ref form 506033 18 Accessories Model ST310 VENTING COMPONENTS Model ST310 Product Reference Information Cat No Description Ship Weight Ship Volume H7888 ST310T B Stove Step Top Tradi tional Black Door Nickel Nameplate 520 lb 19 5 ...

Page 28: ...ENGTH 6 8 4 6DLK 6DLK DAMPER UNIT DL 6 4 6DQDH 6DQDH DECORATIVE COLLAR 25 6DQ 6DQ TRIM COLLAR 10 Secure Temp Factory Built Chimney 6 Secure Temp ASHT and Secure Temp G ASHT Cat No Model Description Pc Container Lengths and Fittings 6L8 6L8 LENGTH 6 X 8 1 6L12 6L12 LENGTH 6 X 12 1 6L18 6L18 LENGTH 6 X 18 1 6L24 6L24 LENGTH 6 X 24 1 6L36 6L36 LENGTH 6 X 36 1 6L48 6L48 LENGTH 6 X 48 1 6LA 6LA ADJUSTA...

Page 29: ...2 12 3 6FC 6FC STORM COLLAR 10 Chimney Termination 6CC 6CC RAIN CAP 1 PE PE UNIVERSAL SPARK ARRESTER BAND 10 Chimney Accessories 6PF 6PF DECORATIVE TRIM 5 6PB 6PB DECORATIVE COLLAR 25 6PA 6PA BLACK PIPE ADAPTOR 1 6PD 6PD FINISHING CONE 1 Fireplace Components 6EK 1 6EK 1 EXTERIOR KIT INCLUDES 1 TI 1 TCI 1 SME 1 RSM 1 CC 1 PB 1 BM 1 6IK 6IK INTERIOR KIT INCLUDES 1 SFC 1 RSA2 1CC 1 Security Chimneys ...

Page 30: ...TH 8 X 18 1 8L24 8L24 LENGTH 8 X 24 1 8L36 8L36 LENGTH 8 X 38 1 8L48 8L48 LENGTH 8 X 48 1 8LA 8LA ADJUSTABLE LENGTH 12 1 8TI 8TI INSULATED TEE TCS INCLUDED 1 8TCS 8TCS INSULATED SS TEE CAP INCLUDED WITH TI 10 8TB 8TB BASE TEE GALVANIZED TC INCLUDED 1 8TBS 8TBS BASE TEE STAINLESS TCS IN CLUDED 1 8TBD 8TBD BASE TEE GALVANIZED DOUBLE TCI INCLUDED 1 8TC 8TC BASE TEE CAP GALVANIZED 10 8TCI 8TCI INSULAT...

Page 31: ...8BH GUY WIRE BAND WIRE NOT INCLUDED 10 8FR 8FR FLAT ROOF FLASHING 3 8FAR 8FAR ADJUSTABLE ROOF FLASHING 1 12 7 12 3 8FARA 8FARA ADJUSTABLE MALLEABLE ALUMI NUM ROOF FLASHING 1 12 7 12 3 8FBR 8FBR ADJUSTABLE ROOF FLASHING 8 12 12 12 3 8FBRA 8FBRA ADJUSTABLE MALLEABLE ALUMI NUM ROOF FLASHING 8 12 12 12 3 8FBBR 8FBBR ADJUSTABLE ROOF FLASHING 12 12 21 12 3 8FPR 8FPR PEAK ROOF FLASHING 1 12 7 12 3 8FPBR ...

Page 32: ...32 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE SAFETY LISTING LABEL eNGLISH 2012 2013 2014 ...

Page 33: ...33 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE SAFETY LISTING LABEL FRENCH ...

Page 34: ...ages 22 through 26 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 ...

Reviews: