background image

4

Troubleshooting

NOTE:  When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas sup-

ply inlet is in the “ON” position.
IMPORTANT:  Call your gas supplier or plumber for additional help with any gas control problem.  Valve system 

troubleshooting should only be accomplished by a qualified service technician.

SYMPTOM

PROBABLE CAUSE

CORRECTIVE ACTION

Thin black coating 

(soot) forms on the 

viewing glass, logs, or 

firebox.

Improper log or ember 

placement.

Blocked flue.

Improper air shutter 

setting.

See 

Brick Panel, Log Set, & Ember Installation

.

Check for obstructions in vent pipe, check for proper restrictor setting. See 

Flue Restric-

tors

.

See 

Air Shutter Adjustment

.

Humming or whistling 

coming from fireplace.

Normal operating noise.

Dirt in burner orifice.

See 

Quiet Operation

. The noise may be reduced by slightly turning the flame down. Turning 

the flame down will reduce the heat output of the fireplace.

Clean orifice.

A change in flame 

appearance or burner 

operation.

A change in gas pres-

sure.

Improper ember or log 

placement.

Have your gas supplier check for correct gas pressure (7” W.C. natural gas; 11” W.C. LP 

gas). 

See 

Brick Panel, Log Set, & Ember Installation

.

Pilot will not light.

No gas supplied to unit.    

 

Air in line.

Defective igniter (no 

spark at electrode).

The valve control knob 

is not turned to “pilot” 

and pushed in.

Turn on gas. 

To purge, hold in control knob in pilot position for 1-2 minutes and light.

Check for spark at electrode and pilot, if no spark and electrode wire is properly connected, 

replace igniter.

See 

Lighting Instructions

.

Pilot will not stay lit 

after carefully following 

lighting instructions.

Pilot flame is not sur-

rounding thermocouple.

Thermocouple not 

generating sufficient 

voltage.

Air in gas supply line.

Check pilot flame adjustment (see 

Maintenance & Servicing

 section).

Check the connection between the thermocouple lead and the valve. Turn control knob to 

“pilot” and push in and light pilot. While lit, take millivolt reading at lead going into valve’s 

CPU. Minimum reading should be 17 millivolts. If less, replace thermocouple.

Purge air in pilot gas line by holding in control knob at “pilot” and sparking igniter. The air 

in the line may take up to several minutes to purge.

Main burner will not 

burn.

Pilot has gone out.

Rocker switch or 

thermostat wires are 

defective.

Thermopile may not be 

generating sufficient 

millivolts.

See 

Lighting Instructions

.

Disconnect rocker switch and thermostat wires at terminals 1 and 3 on valve. Jumper 

across from 1 to 3 with pilot lit. If burner comes on either rocker switch or thermostat wir-

ing is not functioning.

Make sure thermopile is fully engulfed by the pilot flame. Check thermopile with millivolt 

meter. With pilot lit and the rocker switch and thermostat off, the millivolt reading with the 

meter connected to valve terminals 1 and 2 should be after 2 minutes at least 325. If the 

thermopile lead connections are good at terminals 1 and 2 and readings are less than 325, 

replace faulty thermopile.

Summary of Contents for Gas Stove

Page 1: ...ppelez le service des incendies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life AVERTISSEMENT Assurez vousdebiensuivrelesinstruc tionsdonnées danscettenoticepou...

Page 2: ... Vertical Vent Installation 13 Flue Restrictors 13 Horizontal Terminations 14 Vertical Terminations 14 Vent Termination Locations 15 Gas Line Installation 16 Gas Pressure Requirements 16 LP Natural Gas Supplies 16 Operating Instructions 17 20 Pre Lighting Checklist 17 Lighting Instructions 17 Flame Color Behavior 18 Air Shutter Adjustment 19 Quiet Operation 19 Paint Curing 19 Operating Options 20 ...

Page 3: ...ations ANSI A225 1 latest edition The appliance when installed must be electrically grounded in accordance with local codes or in the ab sence of local codes with the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code latest edition Your Lennox gas stove must be equipped for the proper fuel type altitude at which it will be operated Any op...

Page 4: ...e are any questions or if you need further substantiation either write to or call your Lennox Hearth Products dealer If you have further questions please contact Lennox Hearth Products The Vision Stove Mustconformwithalllocal state andnationalinstallation codes In the absence of local codes the installation must conform with National Fuel Gas Code ANSI Z223 1 latest edition also known as NFPA 54 I...

Page 5: ...h The individual manual shut off must be a T handle type valve Commonwealth Of Massachusetts Requirements Note The following requirements reference various Massachusetts and national codes not contained in this document Forallsidewallhorizontallyventedgasfueledequipmentinstalledinevery dwelling building or structure used in whole or in part for residential purposes including those owned or operate...

Page 6: ...ore burns even during a power outage Fuel This stove comes from the factory equipped to burn natural gas at a specified elevation The stove can be converted to burnLPgas liquidpropane bychangingthecassette valve and pilot assembly or installing a conversion kit Only Len nox Hearth Products conversion kits can be used to convert from NG to LP or LP to NG Contact your Lennox Hearth Products dealer f...

Page 7: ...r other safety hazard The Lennox Hearth Products warranty will be voided if one of the following occurs Installation of any damaged stove or vent system component Unauthorized modification of the direct vent system Installation other than as instructed by Lennox Hearth Products Security Chimneys or Simpson Dura Vent Installationofanystoveorventsystemcomponentnot manufacturedorapprovedbyLennoxHeart...

Page 8: ...ls in inches millimeters Parallel Installation Corner Installation Alcove dimensions The minimum width between the alcove side walls is 51 1295mm Theminimumheightofthealcoveis46 1168mm and the maximum depth is 35 889mm Floor Protection A non combustible hearth pad is not required This stove may be installed on a combustible surface as long as the combustible material such as carpeting does not ext...

Page 9: ...ingcan create visible dimples on the plated surface To install the trim on the door first see Opening and Remov ing Door on page 22 Slide the threaded studs on the trim through the holes in the door Install the nuts on the studs to secure the trim to the door Do not over tighten the nuts or they will snap the studs off To install the spring handle first close the door and screw the handle into the...

Page 10: ...the brick retainer bracket from the upper left corner inside the stove Log Inserts 5 Place rockwool over ports Rockwool can be placed to obscure air holes but do not cover the air holes Fifty percent or less of rockwool supplied should be used in LP installations Too much rockwool will result in tall sooty flames 6 The right front log positioned with the black charred surface toward the front shou...

Page 11: ...em Installationofanyventcomponentpartnotapproved or manufactured by the approved vent manufac turer InstallationotherthanasinstructedbyLennoxHearth Products and vent manufacturers instructions Residential and Mobile Home Installations These are the minimum pieces required Other parts may be required for your particular installation Minimum Components for Horizontal Installation Horizontal Terminat...

Page 12: ... Vent Installation Venting terminals may not be recessed into a wall or siding 1 Set the unit in the desired location Check whether or not wall studs are in the way when the venting system is attached If wall studs are in the way you may want to adjust the location of the unit 2 Assemble the desired combination of pipe and elbow to the appliance adaptor with pipe seams facing down Off setting the ...

Page 13: ...s in the top of the firebox Restrictor positions are based on tests run in a laboratory StormCollar VerticalTermination Cap CeilingFirestop Framing 10 x 10 Roof Maintain 1 Clearance to Combustibles Pipe Length Flashing Handbreaktoremove unwantedrestrictor LightObstructor onlyusedforVision25w short horizontalrun nofluerestrictor Position1 FlueRestrictor Position3 Position2 A Vertical Vent Installat...

Page 14: ...Required No Light Obstructor Vision 35 NG 0 3 horizontal 14 Snorkel Required No Light Obstructor Offsets must remain within maximum and minimum lines To install the stove with pipe directly out the back a snorkel is not required for the Vision 25 gas stove A snorkel is required for the Vision 35 gas stove See pages 12 13 for snorkel installation instructions Vertical Terminations The diagram below...

Page 15: ...bove meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 6 in 15 2 cm for appliances 10 000 BTU ...

Page 16: ...heck manifold pressure with the stove burning at the high burn setting insert a small flat bladed screwdriver into the tap and turn a half turn counter clockwise Cover the tap with the line from the manometer and check the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution retighten if necessary Ifthepressureisnots...

Page 17: ...t push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D DONOTusethisapplianceifanyparthasbeenunderwater Immediately call a qualified service technician to inspect theapplianceandtoreplaceanypartofthecontrolsystem and any gas control which has been under water OPERATING INSTRUCTIONS CAUTION Your Lennox gas AP...

Page 18: ... if installed to a setting below room temperature The pilot will remain lit for future burner igni tion For complete shutdown see TO TURN OFF GAS TO APPLIANCE above Flame Color Behavior Your Vision gas stove is designed for maximum heating efficiency Therefore upon lighting of the main burner the flames will be semi transparent or bluish After 10 20 minutes of operation the logs will heat up and t...

Page 19: ...teristics of the stove Quiet Operation As the Vision gas stove is burning a number of normal op erational sounds may be heard The flow of gas through the gas valve and orifice may make a rushing or whistling noise If this noise is objectionable it can be reduced by turning down the flame Turning down the flame can reduce total heat output by more than 30 When the blower turns on the sound of rushi...

Page 20: ...er on and off indepen dently Be sure to set the rocker switch to the Off position when using the thermostat or remote control and set the thermostatorremotecontroltothelowesttemperaturewhen you wish to use the rocker switch only otherwise one may override the other Millivolt Control System This stove operates on a millivolt control system As such no additional power supply is needed for the stove ...

Page 21: ...rthegaspressurehasbeenchecked and supply lines have been completely bled this may take an hour or more when bleeding through the pilot All pilots are checked and burned at the factory prior to shipment The pilot adjustment screw is located to the lower left of the flame height control knob 2 Adjust the pilot screw to properly size the flames The flames should completely surround the thermopile and...

Page 22: ...inserted in the slot at the bot tom of the firebox Glass Door Cleaning and Maintenance Cleaning Whencool theglassmaybecleanedwithaclean softclothandglasscleaner Forcleaningwhitecondensation from the interior glass use KEL KEM gas stove glass cleaner available from your stove dealer Use of caustic or abrasive cleaners may damage glass Gold or nickel plated trim must be cleaned with glass cleaner or...

Page 23: ...the two phillips head screws from the back of the burner 4 Lift the right end of the burner and slide if off the orifice and shutter tube Remove the burner from the firebox 5 Removethelabeledcoverthroughwhichthevalvecontrol knobs protrude by removing the two screws securing it and slide it off the valve knobs 6 Mark and disconnect wires on valve terminals 1 and 3 connected to the burner on off swi...

Page 24: ... pilot position for 1 2 minutes and light Check for spark at electrode and pilot if no spark and electrode wire is properly connected replace igniter See Lighting Instructions Pilot will not stay lit after carefully following lighting instructions Pilot flame is not sur rounding thermocouple Thermocouple not generating sufficient voltage Air in gas supply line Check pilot flame adjustment see Main...

Page 25: ...H5951 Orifice High Altitude Main Burner LP 25 000 BTU H5959 Orifice High Altitude Main Burner LP 35 000 BTU 75265 Conversion Kit NG to LP 75266 Conversion Kit LP to NG H3071 Blower H5875 Blower Snap Switch H5877 Blower Speed Control rheostat H5744 On Off Switch 46246 On Off Switch Wires H5745 Piezo Igniter 70006 Thermostat 70005 AC Remote Control Thermostat 71155 DC Remote Control Thermostat H5660...

Page 26: ...ors can cause improper and dangerous operation Verify proper operation after servicing POWER CORD SNAP SWITCH GRN 6 SPEED CONTROL SWITCH BLOWER BLK 6 RED 12 RED 7 RED 8 BLK 16 8 MALE SPADE 1 4 FEMALE SPADE 1 4 RING LUG CRIMP FEMALE SPADE 1 4 STRIP OUTER JACKET 6 W H T 6 2 PL FEMALE SPADE 1 4 FEMALE SPADE 1 4 MALE SPADE 1 4 FEMALE SPADE 1 4 Figure 31 ...

Page 27: ... service ou un fournisseur de gaz Si vous opérez cet appareil sans qu il ne soit correctement raccordé à un conduit d évacuation vous pourriez risquer d être empoisonné au monoxyde de carbone CO ce qui pourrait entraîner des conséquences grave ou la mort POUR COUPER L ALIMENTATION EN GAZ DE L APPAREIL 1 Pour arrêter le brûleur mettre l interrupteur à la position OFF ou ajustez le thermostat à une ...

Page 28: ...2 000 FT 0 610 M 35 000 23 000 35 000 23 500 25 000 17 500 25 000 18 000 MANIFOLD PRESSURE IN WC 3 5 10 0 3 5 10 0 MIN INLET PRESSURE IN WC 5 0 11 5 0 11 ORIFICE DMS 0 2 000 FT 0 610 M 34 111 IN 50 070 IN 42 093 IN 53 059 IN UNIT FACTORY EQUIPPED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS DATE OF MANUFACTURE DATE DE FABRICATION 2007 2009 201...

Page 29: ...out your fireplace Please contact your Lennox Hearth Products dealer for any questions or concerns For the number of your nearest Lennox Hearth Products dealer please call 877 247 3673 Replacement parts See Page 25 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox Hearth Products distributor or dealer Parts...

Page 30: ... 2007 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1110 West Taft Avenue Orange CA 92865 ...

Reviews: