41
Table 2. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
446
Service
Soon/Service
Urgent
OD Low Suction
Pressure Fault
Suction pressure < 40 psig in operation.
Error code initially will be a service soon and will escalate to service urgent and stop system
operation after five-strikes during a single thermostat demand. Recommend replacement of low
pressure switch.
Recommend replacement of low pressure
switch.
500
Service Soon
PA Differential
Pressure Sensor
Fault
•
Pressure sensor reports a fault for more than 5 minutes, or does not respond for more than 5
minutes.
•
Device will not perform any pressure reading calculations until fault is recovered. Remaining filter
life display will indicate “-“ while fault exists.
Automatically clears 30 seconds after fault
is recovered.
501
Service Soon
PA UV Sensor
Fault
•
Ultra-violet (UV) sensor reports a fault for more than five minutes or UV sensor does not respond
for more than 5 minutes.
•
Device will not perform any UV lamp life remaining calculations until fault has recovered. Life
remaining display shall indicate “-“ while fault exists.
Automatically clears 30 seconds after fault
is recovered.
502
Service Soon
PA UV Lamp Off
The light is determined to be off when the last three last light intensities measurements are below
the set threshold.
Light is determined on after 1 set of five
samples are above the set threshold.
503
Service Soon
PA Filter Life At
10%
Filter life remaining determined to be <=10%, but greater than 0%.
None. Replace and reset filter.
504
Service Soon
PA Filter Life
At 0%
Filter life remaining determined to be 0%.
None. Replace and reset filter.
505
Service Soon
PA Model
Selection
Changed
Model Selection jumper has changed positions.
Jumper repositioned back to original jumper
position or system rebooted.
506
Service Soon
PA Lamp At 0%
life
Ultra violet lamp life is at 0%.
None. Replace and reset filter.
507
Service Soon
PA Filter
Calibration
Failure
•
Filter calibration determined failed due to all test cfm static pressures reading <= 7 Pa.
• Send alert code immediately.
•
No filter tests or life calculation occur while this alert code is active.
None. Replace and reset filter.
530
Service Soon
ZS Low Damper
24VAC Voltage
•
Check 24VAC voltage to all dampers.
•
Check 24VAC damper transformer.
•
Check connections.
Replace transformer if applicable.