INSTALLATION INSTRUCTIONS FOR WALL−MOUNT SENSOR (59M04) IS USED WITH

BUILDING CONTROLLERS (BC) ON THE L CONNECTION

®

 NETWORK

504,764M
4/2003

INDOOR

TEMPERATURE

SENSOR

MISCELLANEOUS

E

2003

Litho U.S.A.

Shipping and Packing List

Package 1 of 1 contains:

 1− Sensor

 2− Screws

WARNING

Improper installation, adjustment, alteration, ser
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser
vice must be performed by a qualified installer, ser
vice agency or the gas supplier

Application

This sensor provides a temperature input to the Building
Controller. The BC can use the indoor temperature to
override NCP scheduled outputs and to set alarms based

on over or under temperature conditions.

The BC Building Controller, used with the L Connection
Network, controls lights, vent hoods, exhaust fans,
sprinklers, security and fire systems, and other building

equipment.

The sensor is 

NOT

 compatible with IMC or NTC rooftop

controllers.

Installation

Locate sensor in conditioned space approximately 5 feet
(1−1/2m) above the floor in an area with good air
circulation at average temperature. Avoid locating the
room thermostat where it might be affected by:

−drafts or dead spots behind doors and in corners

−hot or cold air from ducts

−radiant heat from sun or appliances

−concealed pipes and chimneys

 1− Route shielded cable between sensor location and

Building Controller.

Cable type: Lennox P/N 94L63, Belden type 88761 or
equivalent. (22AWG stranded or twisted pair, 100%
aluminum shield with drain wire, Teflon jacket).

 

2− Remove sensor cover and center opening in

baseplate over opening in wall. See figure 1.

 3− Mark holes for screws. Remove baseplate and drill

holes.

 4− Insert  wall anchors (field provided) and align baseplate

over opening in wall. Pull wiring through opening in
baseplate. Secure baseplate to wall with screws.

FIGURE 2

WIRING

CONNECTOR

SENSOR

BASEPLATE

 5− Connect the shielded cable to sensor terminal block.

 6− Replace  sensor  cover  and  tighten  side  screws  to

secure in place.