INSTALLATION INSTRUCTIONS LD4120 SMOKE DETECTOR REPLACEMENT KIT (73W51

& 73W52; LB−90945R & S) USED WITH SGA/SCA/LGB/LCB/LGE/LCE036−240 UNITS

Litho U.S.A.

506748−01
2/2011
Supersedes 506592−01

E

2011

LD4120 REPLACEMENT

SMOKE DETECTOR KIT

PACKAGED UNITS KITS
AND ACCESSORIES

Shipping and Packing List

Package 1 of 1 contains:

 1− Smoke detector

 3− Sampling tubes (two tubes on 73W52)

 1− Smoke detector bracket

 1− Sampling tube bracket (73W52 only)

 1− Bag assembly containing:

1−Magnet
6−#10−16 X 5/8" screws
2−#8−32 X 1" screws

Application

The smoke detector replacement kit is used on

SGA/SCA/LGB/LCB/LGE/LCE036, 060, 120, 240, & 288

units. LD4120 replaces DH400 and DH100 smoke detectors.

73W51 is used in return air installations and 73W52 is used

in supply air installations.

Smoke detector will send a 24vac signal to the unit A55
IMC when smoke is sensed. IMC default mode will
de−energize unit. Some units will interrupt the main power
signal to the unit to de−energize the unit when smoke is
detected.

Installation

Refer to manufacturer’s instructions provided with smoke
detector.

Install Sampling Tubes

 1− Install sampling and exhaust tubes in smoke detector

before installing smoke detector or bracket in unit.
The exhaust tube is packaged with the smoke
detector. See figure 1. Also refer to figure 2 and 3 for
supply air installations and figure 5 for return air
installations. Discard unused tubes.

Unit

Tube Length (in.)

Supply Air

Return Air

036/060

18

18

120

30

30

240

30

36

WARNING

Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser-
vice must be performed by a qualified installer, ser-
vice agency or the gas supplier

SMOKE DETECTOR

FIGURE 1

SENSOR MODULE

COVER

POWER BOARD MODULE COVER

SENSOR HEAD

METAL

SAMPLING TUBE

POWER BOARD

EXHAUST TUBE

MAGNET TEST LOCATION