background image

Page 10

5- Furnace Control (A3) 80UHG-1 Model

80UHG units are equipped with an integrated ignition/blower

control  (EGCĆ2)  which  controls  ignition,  safety  circuits,

blower operation, fan off timing, and allows for thermostat

connection and troubleshooting. The EGCĆ2 is a printed

circuit board which is divided into two sections, 120 and

24VAC. Line voltage comes into the board on the 120VAC

side. See figure 10. Terminal designations are listed in

tables 6 and 7.

Ignition  Control

80UHG units use the EGC-2 direct spark integrated

ignition control. The EGC-2 controls and monitors the

entire sequence of operation. On a call for heat from the

thermostat the control monitors the combustion air inĆ

ducer prove switch. The control will not begin the heatĆ

ing cycle if the prove switch is closed (byĆpassed). Once

the prove switch is determined to be open, the combustion

air inducer is energized. When the differential in pressure

across the prove switch is great enough, the prove switch

closes and a 15 second preĆpurge period begins. If the

prove switch does not close within 2 1/2 minutes, the conĆ

trol goes into 5 minute watchguard. After the preĆpurge peĆ

riod, the gas valve will open and ignition (spark) will be atĆ

tempted for 10 seconds. After ignition, the control initiates a

ten second flame stabilization period. The flame stabiĆ

lization period allows the burners to heat up and the

flame to stabilize. Once flame is established, the control will

constantly monitor the burner flame using flame rectification.

Flame failure response time is 0.8 seconds.
If the initial attempt for ignition fails, the sequence is reĆ

peated up to five times. After the fifth trial, the control goes into
Watchguard"*. During watchguard mode, the entire unit will

be deĆenergized for one hour. After one hour the control will

repeat the ignition sequence.  Watchguard may be manually
reset by breaking and remaking thermostat demand.

*NOTE-If flame is established beyond the 10 second flame

stabilization period then lost, the control resets for five more

ignition trials. The control can be reset five times during one

unsatisfied thermostat demand, providing a maximum

of 25 trials for ignition.

Safety Circuits

During the entire heating demand the control monitors the

safety circuits. If the primary or secondary heating limits

open, the control deĆenergizes the main gas valve and

combustion air blower while the indoor blower remains enĆ

ergized. When the limit automatically resets, the ignition seĆ

quence also resets. If either of the limits trip five consecuĆ

tive times during one unsatisfied thermostat demand, the

control will go into watchguard for one hour.
The control monitors main valve voltage. If voltage is sensed

when no voltage should be present, the control deĆenergizes

the combustion air inducer  which terminates voltage to the

valve. The system goes into hard lockĆout which is reset only

by removing power to the unit.
If flame is sensed when no flame should be present, the conĆ

trol will energize the combustion and indoor blowers. The

unit will remain locked in this sequence until the flame is no

longer sensed or the main power is turned off to reset the

control.
The rollĆout circuit is also monitored by the EGCĆ2 control. If

the switch opens, the control will deĆenergize the gas

valve, combustion air inducer, and indoor blower. The

unit will remain deĆenergized until the switch is manualĆ

ly reset.

DANGER

Shock hazard. Avoid personal injury. Make sure to

disconnect power before changing fan off" timing.

Blower Operation / Fan Off Timings

Fan off" timing (time that the blower operates after the heat

demand has been satisfied) can be adjusted by moving the

jumper on the EGCĆ2 blower control board. Figure 9 shows

the various fan off" timings and how jumper should be posiĆ

tioned. To adjust fan off " timing, gently disconnect jumper

and reposition across pins corresponding with new timing.

Unit is shipped with a factory fan off" setting of 180  seconds.

Fan  on"  time  is  factory  set  at  45  seconds  following  the

opening of the main gas valve and is not adjustable.
Fan off" time will affect comfort and efficiency and is adĆ

justable to satisfy individual applications. The fan off" timĆ

ing is initiated after a heating demand but not after a coolĆ

ing demand.

NOTEĊIf fan off" time is set too low, residual heat in

heat exchanger may cause primary limit S10 to trip, reĆ

sulting in frequent cycling of blower. If this occurs, adjust

blower to longer fan off" time setting.

FIGURE 9

FANĆOFF TIME ADJUSTMENT

180

60

120

90

To adjust fanĆoff timing:

Remove jumper from EGCĆ2 and select

one of the other pin combinations to

achieve the desired time.

TIMING

JUMPER

TIMING PINS

(seconds)

Leave jumper off for

240 second fanĆoff timing.

Summary of Contents for 80UHG Series

Page 1: ...itrogen Oxides NOx Standards and California Sea8 sonal Efficiency requirements All units use a redundant gas valve to assure safety shut off as required by A G A or C G A Units may be installed in upf...

Page 2: ...46J66 15 lbs 8 kg SPECIFICATIONS Model No 80UHG3 4 X 100 80UHG4 5 X 100 80UHG3 4 X 120 80UHG4 5 X 120 Input Btuh kW 100 000 29 3 120 000 35 2 Output Btuh kW 82 000 24 0 98 400 28 8 A F U E 80 1 80 0...

Page 3: ...375 20 50 1370 645 1180 555 980 460 790 375 25 62 1350 635 1160 545 970 460 780 370 30 75 1330 630 1140 540 955 450 770 365 40 100 1280 605 1095 515 925 435 750 355 50 125 1210 570 1040 490 900 425 72...

Page 4: ...lace Also see Filter Air Resistance table FILTER AIR RESISTANCE cfm L s in w g Pa 0 0 0 00 0 200 95 0 01 2 400 185 0 03 7 600 280 0 04 10 800 375 0 06 15 1000 470 0 09 22 1200 560 0 12 30 1400 655 0 1...

Page 5: ...BOX SECONDARY LIMITS FRONT ACCESS PANEL DOOR INTERLOCK SWITCH CONTROL BOARD TRANSFORMER PROVE SWITCH 80UHG PARTS IDENTIFICATION FIGURE 2 HEAT EXCHANGER COMBUSTION AIR INDUCER MANIFOLD ROLLOUT SWITCH...

Page 6: ...protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic dis charge by putting the furnace the control and the technician at the same electrostatic po...

Page 7: ...be open the combustion air inducer is energized When the differ8 ential in the prove switch is great enough the prove switch closes and a 15 second pre purge begins If the prove switch is not proven...

Page 8: ...ed OR Pressure switch closed prior to activation of combustion air blower ALTERNATING SLOW FLASH ALTERNATING SLOW FLASH Watchguard burners fail to ignite SLOW FLASH OFF Flame sensed without gas valve...

Page 9: ...nal is sensed NOTE The 80UHG furnace contains electronic components that are polarity sensitive Make sure that the furnace is wired correctly and is properly grounded PARK TERMINAL DESIGNATIONS COOL H...

Page 10: ...ts If the primary or secondary heating limits open the control de energizes the main gas valve and combustion air blower while the indoor blower remains en ergized When the limit automatically resets...

Page 11: ...is a heating demand On Flash Primary or Secondary Limit Switch Open Auto Reset Switch Flash Off Pressure Switch Watchguard pressure switch opened during operation Alternate Flash Alternate Flash Watch...

Page 12: ...P 1 2 1 3 1 4 5MFD 370V 5MFD 370V 7 5MFD 370V 80UHG5 6 80UHG4 80UHG4 5 1 2 7 5MFD 370V 3 4 40MFD 370V 3 4 40MFD 370V FIGURE 11 SUPPLY AIR BLOWER AND SECONDARY LIMITS Front Bottom Right Left Top Back B...

Page 13: ...t point will be printed on the limit Two limits are supplied in each furnace 80UHG3 80UHG4 and 80UHG4 5 model units built prior to Apri 1999 will have one each of style shown in figures 13 and 14 If s...

Page 14: ...ODEL SHOWN FIGURE 18 SPARK ELECTRODE SPARK ELECTRODE TO BURNER GAP 80UHG 1 MODEL SHOWN BURNER FLAME SENSOR TO BURNER GAP BURNER FLAME SENSOR SPARK ELECTRODE 5 16 in 7 mm 5 16 in 7 mm 13 Combustion Air...

Page 15: ...ard 80UHG 1 units are equipped with a direct spark igni tion system Do not attempt to light manually 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest sett...

Page 16: ...to check for gas leaks D Testing Gas Supply Pressure When testing supply gas pressure connect test gauge to inlet pressure tap field provided See figure 20 Check gas line pressure with unit firing at...

Page 17: ...roamp DC meter is needed to check the flame signal on the ignition control Flame microamp signal is an electrical current which passes from the furnace control through the sensor during unit opera tio...

Page 18: ...mperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable in crease blower speed to reduce temperature To change blower s...

Page 19: ...in the heat exchanger clean ing is not recommended Removal is for inspection only NOTE Use papers or protective covering in front of fur nace while cleaning furnace To clean burners 1 Remove screws ho...

Page 20: ...ting in gas leaks fire or explosion C Supply Air Blower 1 Check and clean blower wheel 2 Motors used on the Lennox 80UHG series units are permanently lubricated and need no further lu brication D Flue...

Page 21: ...n control energizes the combustion air inducer B6 When the combustion air inducer nears full speed combustion air prove switch S18 closes Switch must close within 2 1 2 minutes or control goes into 5...

Page 22: ...OR BLOWER WITH DELAY OFF DIAG CODE 1 OFF 2 FLASHING C A B PRESSURE SWITCH OPEN IS 5 MINUTE RESET PERIOD COMPLETE INDOOR AIR BLOWER ON Fixed 45 second delay PRIMARY SECONDARY LIMITS MONITORED IN HEAT C...

Page 23: ...RMOSTAT CONTROL ENERGIZES SYSTEM FAN AT HEATING SPEED ACC TERMINAL ENERGIZED THERMOSTAT CALLS FOR HEAT LED Slow flash rate REMAINS UNCHANGED THROUGHOUT SEQUENCE THERMOSTAT CALLS FOR COOLING SYSTEM FAN...

Page 24: ...hguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 second trial for ignition i...

Page 25: ...AS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequen...

Page 26: ...CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILU...

Page 27: ...D SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY COOLING SPEED EAC H TERM ENERGIZED COMPRESSO...

Page 28: ...THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL H SPEED EAC H TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G...

Page 29: ...he roll out switch by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code 1 2 2 Roll out switch failure ACTION 1 Check continuity across r...

Page 30: ...WER DOES NOT ENERGIZE Condition Possible Cause Corrective Action Comments 2 1 Unit operates with a cooling or con tinuous fan demand Combustion air inducer will not start with a Heating demand Diagnos...

Page 31: ...e pressure switch failure code 2 5 minutes after heating demand 3 1 2 Pressure switch does not close due to obstructions in the pressure lines ACTION 1 Remove any obstructions from the the pressure li...

Page 32: ...ch code LED 1 Off LED 2 Slow Flash 5 1 1 Low pressure differential at the pres sure switch ACTION 1 Check for restricted exhaust vent Remove all blockage ACTION 2 Check for proper vent sizing See inst...

Page 33: ...3 4 Burners are not properly located in the burner box ACTION 1 Check that the burners are firing into the center of the heat exchanger openings Cor rect the location of the burners if necessary 5 4...

Page 34: ...Action Comments 7 0 Indoor blower fails to operate in continuous fan cooling or heating mode 7 1 1 Miswiring of furnace or improper con nections at control or indoor blower motor ACTION 1 Correct wir...

Reviews: