507281-06
Page 28 of 58
Issue 1724
Figure 37. Flush-Mount Side Wall Termination
51W11
2” EXTENSION FOR 2” PVC
PIPE1” EXTENSION FOR 3”
PVC PIPE
1-1/2” ACCELERATOR
(
all -45, -070 and -090 units)
FURNACE
EXHAUST
PIPE
FURNACE
INTAKE
PIPE
4''
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT
SIDE
Figure 38. Direct Vent Concentric Wall Termination
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
Figure 39. Direct Vent Concentric Rooftop
Termination
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
Figure 40. Optional Vent Termination For Multiple Unit
Installation of Direct Vent Wall Termination
EXHAUST
VENT
INTAKE
AIR
5-1/2”
(140mm)
Front View
12”
(305MM)
5”
(127MM)
18” MAX.
(457MM)
EXHAUST VENT
INTAKE
AIR
Inches (MM)
Side View
12” (305MM) Min.
above grade or
average snow
accumulation.
optional intake elbow
Figure 41. Direct Vent Application Using Existing
Chimney
3” - 8”
(76MM-
203MM)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
8” - 12”
(203MM - 305MM)
3”-8”
(76MM-203MM)
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
ALTERNATE
INTAKE PIPE
NOTE:
Do not discharge exhaust gases directly into any chimney
or vent stack. If vertical discharge through an existing unused
chimney or stack is required, insert piping inside chimney until
the pipe open end is above top of chimney and terminates as
illustrated. In any exterior portion of chimney, the exhaust vent
must be insulated.