background image

507281-06

Page 52  of 58

Issue 1724

Unit

Gas

Manifold Pressure in. w.g.

Supply Line 

Pressure in. 

w.g. 0 - 10000 ft.

0 - 4500 ft.

4501 - 5500 ft.

5501 - 6500 ft.

6501 - 7500 ft.

7501 - 10000 ft.

Low 

Fire

High 

Fire

Low 

Fire

High 

Fire

Low 

Fire

High 

Fire

Low 

Fire

High 

Fire

Low 

Fire

High 

Fire

Min

Max

All 

Sizes

Natural

1.7

3.5

1.6

3.3

1.5

3.2

1.5

3.1

1.7

3.5

4.5

13.0

LP / 

Propane

4.9

10.0

4.6

9.4

4.4

9.1

4.3

8.9

4.9

10.0

11.0

13.0

NOTE

A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation 

instruction for the conversion procedure.

Table 16. Manifold and Supply Line Pressure 0 - 10,000 ft.

For  proper  furnace  operation,  the  minimum  gas  supply 

pressure is 4.5” w.c and the maximum gas supply pressure 

is  10.5”  w.c  for  natural  gas.  The  minimum  gas  supply 

pressure is 10” w.c. and the maximum gas supply pressure 

is 13” w.c. for LP/propane gas.

Manifold Pressure Measurement

1.  A  manifold  pressure  post  located  on  the  gas  valve 

provides access to the manifold pressure. See Figure 

67. Back out the 3/32 Hex screw one turn, connect a 

piece of 5/16” tubing and connect to a manometer to 

measure supply pressure.

2.  Start unit and allow 5 minutes for unit to reach steady 

state.

3.  While  waiting  for  the  unit  to  stabilize,  observe  the 

flame. Flame should be stable and should not lift from 

burner. Natural gas should burn blue.

4.  After  allowing  unit  to  stabilize  for  5  minutes,  record 

manifold  pressure  and  compare  to  value  given  in 

Table 16.

5.  Shut unit off and remove manometer as soon as an 

accurate reading has been obtained. Take care to re-

tighten the 3/32 Hex screw.

Proper Combustion

Furnace should operate minimum 15 minutes with correct 

manifold  pressure  and  gas  flow  rate  before  checking 

combustion.  Take  combustion  sample  beyond  the  flue 

outlet  and  compare  to  the  tables  below.  The  maximum 

carbon monoxide reading should not exceed 100 ppm.

High Altitude Information

NOTE

In  Canada,  certification  for  installations  at 

elevations  over  4500  feet  (1371  m)  is  the  jurisdiction  of 

local authorities.

Units may be installed at altitudes up to 10,000 ft. above 

sea level. See Table 16 for de-rate manifold values. Units 

installed at altitude of 7501 - 10,000 feet require an orifice 

change.  Units  installed  at  altitude  of  4501  -  10,000  feet 

(1371 to 3048 m) may require a pressure switch change 

which can be ordered separately. Table 15 lists conversion 

Other Unit Adjustments

Primary Limit

The primary limit is located on the heating compartment 

vestibule  panel.  This  limit  is  factory  set  and  requires  no 

adjustment.

Flame Rollout Switches (Two)

These manually reset switches are located on the front of 

the burner box.

Pressure Switch

The pressure switch is located in the heating compartment 

on the cold end header box. This switch checks for proper 

combustion air inducer operation before allowing ignition 

trial. The switch is factory set and must not be adjusted.

Temperature Rise

After the furnace has been started and supply and return 

air temperatures have been allowed to stabilize, check the 

temperature rise. If necessary, adjust the blower speed to 

maintain the temperature rise within the range shown on 

the unit nameplate. Increase the blower speed to decrease 

the temperature. Decrease the blower speed to increase 

the temperature rise. Failure to adjust the temperature rise 

may cause erratic limit operation.

Fan Control

The fan ON time of 30 seconds is not adjustable. The fan 

OFF delay (amount of time that the blower operates after 

the heat demand has been satisfied) is 120 seconds and 

is not adjustable.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to 

the amp draw listed on the wiring diagram that is attached 

to the unit.

kit and pressure switch requirements at varying altitudes. 

The  combustion  air  pressure  switch  is  factory-set  and 

requires no adjustment.

Summary of Contents for 95G2UHE

Page 1: ...hanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equipment CAUTION Improper installation adjustment alteration service or maintena...

Page 2: ...9 3 4 19 1 Bottom Return Air Opening GAS PIPING INLET Either Side Side Return Air Opening Either Side 1Bottom Return Air Opening EXHAUST AIR OUTLET ELECTRICAL INLET Either Side SUPPLY AIR OPENING W E...

Page 3: ...507281 06 Page 3 of 58 Issue 1724 Figure 1 Parts Arrangement...

Page 4: ...pane LP gas applications NOTE In Direct Vent installations combustion air is taken from outdoors and flue gases are discharged outdoors Non Direct Vent installations combustion air is taken from indoo...

Page 5: ...nces must take precedence over fire protection clearances NOTE For installation on combustible floors the furnace shall not be installed directly on carpeting tile or other combustible material other...

Page 6: ...lling one of these furnaces Place the furnace as close to the center of the air distribution system as possible The furnace should also be located close to the chimney or vent termination point When t...

Page 7: ...es to ensure efficient and safe operation You must consider combustion air needs and requirements for exhaust vents and gas piping A portion of this information has been reprinted with permission from...

Page 8: ...he building or from outside Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined air can be brought in by providing two permanent openings between th...

Page 9: ...penings shall each have a free area of at least one square inch per 4 000 Btu 645mm2per 1 17kW per hour of the total input rating of all equipment in the enclosure Ventilation Louvers Inlet Air Minimu...

Page 10: ...ck to front to aid in the draining of the heat exchanger Unit must be level side to side in all applications When ducts are used they shall be of the same cross sectional area as the free area of the...

Page 11: ...or either side of the furnace installed in an upflow application If the furnace is installed on a platform with bottom return make an airtight seal between the bottom of the furnace and the platform t...

Page 12: ...ottom panel has been removed reinstall the bottom cap See Figure 16 Figure 16 Removing the Bottom Panel Horizontal Applications Do not install the furnace on its front or its back See Figure 13 WARNIN...

Page 13: ...a crawl space a proper support platform may be created using cement blocks 4 Route auxiliary drain line so that water draining from this outlet will be easily noticed by the homeowner 5 If necessary r...

Page 14: ...lowing and contain no lumps undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement The cement shall show no gelation stratification...

Page 15: ...2855 DANGER OF EXPLOSION Fumes from PVC glue may ignite during system check Allow fumes to dissipate for at least 5 minutes before placing unit into operation DANGER 1 Measure and cut vent pipe to des...

Page 16: ...t will show a bead around its entire perimeter Any gaps may indicate an improper defective assembly due to insufficient solvent 9 Handle joints carefully until completely set Venting Practices Figure...

Page 17: ...any other gas burning appliances to their previous mode of operation 7 If a venting problem is found during any of the preceding tests the common venting system must be modified to correct the problem...

Page 18: ...stems which include multiple pipe sizes NOTE All horizontal runs of exhaust pipe must slope back toward unit A minimum of 1 4 6 mm drop for each 12 305 mm of horizontal run is mandatory for drainage N...

Page 19: ...78 74 9 36 21 70 70 48 13 93 92 73 73 69 10 31 16 65 65 43 8 89 87 68 68 64 Standard Termination at Elevation 4 501 10 000 ft Number of 90 Elbows Used 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model 45 70...

Page 20: ...65 9 28 13 60 60 44 9 76 76 69 69 60 10 23 8 55 55 39 n a 71 71 64 64 55 Concentric Termination at Elevation 4 501 10 000 ft Number of 90 Elbows Used 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model 45 70 9...

Page 21: ...73 72 53 53 49 10 16 6 50 50 28 68 67 48 48 44 Standard Termination at Elevation 4 501 10 000 ft Number of 90 Elbows Used 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model 45 70 90 110 135 45 70 90 110 135...

Page 22: ...he shortest length of 2 PVC pipe possible NOTE Exhaust pipe and intake pipe must be the same diameter Figure 25 Typical Exhaust Pipe Connections in Horizontal Direct or Non Direct Vent Applications Ri...

Page 23: ...on direct vent applications when intake air will be drawn into the furnace from the surrounding space the indoor air quality must be considered and guidelines listed in the Combustion Dilution Ventila...

Page 24: ...ill not be obstructed by loose insulation or other items that may clog the debris screen 4 If intake air is drawn from a ventilated attic Figure 30 or ventilated crawlspace Figure 31 the exhaust vent...

Page 25: ...als prolonged exposure to exhaust condensate can destroy protective coatings It is recommended that the exhaust outlet not be located within 6 feet 1 8 m of a condensing unit because the condensate ca...

Page 26: ...nt installations combustion air is taken from outdoors and flue gases are discharged to outdoors NOTE Flue gas may be slightly acidic and may adversely affect some building materials If any vent termi...

Page 27: ...ulation of exhaust back into intake pipe 5 On field supplied terminations for sidewall exit exhaust piping may extend a maximum of 12 inches 305 mm for 2 PVC and 20 inches 508 mm for 3 76 mm PVC beyon...

Page 28: ...VENT INTAKE AIR Inches MM Side View 12 305MM Min above grade or average snow accumulation optional intake elbow Figure 41 Direct Vent Application Using Existing Chimney 3 8 76MM 203MM STRAIGHT CUT OR...

Page 29: ...within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 pliances 10 000 Btuh 3kw and 50 000 pliances 50 000 Btuh 15kw 6 inches 152mm for applianc...

Page 30: ...3 76MM Vent Pipe A Clearance above grade or average snow accumulation B Horizontal separation between intake and exhaust C Minimum from end of exhaust to inlet of intake D Exhaust pipe length E Wall s...

Page 31: ...inlet Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda porch deck or balcony 12 Equal to or greater than soffit depth 3 feet 9m 12 3 feet 9m within a...

Page 32: ...igure 47 When exhaust piping must be run up an outside wall any reduction in exhaust pipe size must be done after the final elbow Figure 45 Non Direct Vent Roof Termination Kit 15F75 or 44J41 Figure 4...

Page 33: ...ermination Drain Trap assembled Figure 49 Kit 51W18 USA 15Z70 Canada Parts Identification and Assembly Exhaust from Furnace To Termination Exhaust from Furnace To Termination Kit 51W18 is shown Figure...

Page 34: ...ate line must maintain a 1 4 downward slope from the furnace to the drain Do not use copper tubing or existing copper condensate lines for drain line CAUTION 5 Figure 54 and Figure 55 show the furnace...

Page 35: ...sition with remote trap Piping from furnace must slope down a minimum of 1 4 per ft toward trap Figure 54 Unit With Evaporator Coil Figure 55 Condensate Trap Locations Unit shown in horizontal right h...

Page 36: ...must be vented to relieve pressure in order for the furnace pressure switch to operate properly IMPORTANT Figure 56 Condensate Trap with Optional Overflow Switch Figure 57 Evaporator Coil using a Com...

Page 37: ...nished Drain Assembly for 3 4 inch Drain Pipe Condensate Drain Connection In Unit Condensate Drain Connection In Unit Vent To Drain Condensate Drain Connection In Unit Optional Condensate Drain Connec...

Page 38: ...using suitable hangers or straps Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate 5 A 1 8 N P T plugged tap or pressure post is located on the gas valve to facil...

Page 39: ...ications a 4 BIP nipple must be installed to allow clearance for the low inlet pressure switch AUTOMATIC GAS VALVE with manual shut off valve Figure 62 Horizontal Applications Possible Gas Piping Conf...

Page 40: ...16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 50...

Page 41: ...fuse or circuit breaker select circuit protection and wire size according to unit nameplate NOTE Unit nameplate states maximum current draw Maximum over current protection allowed is shown in Table 9...

Page 42: ...and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power Generator should have a wave form distortion of less than 5 THD total harmonic di...

Page 43: ...TR CHASSIS GROUND GRD Y1 THERMOSTAT 1ST STAGE COOL SIGNAL Y2 THERMOSTAT 2ND STAGE COOL SIGNAL O THERMOSTAT SIGNAL TO HEAT PUMP REVERSING VALVE L NOT USED DH NOT USED 3 16 QUICK CONNECT TERMINALS FLAM...

Page 44: ...the ON position it will provide a 12 minute delay before second stage heat is initiated This switch is only activated when the thermostat selector jumper is positioned for single stage thermostat use...

Page 45: ...507281 06 Page 45 of 58 Issue 1724 Table 13A Field Wiring Applications With Conventional Thermostat...

Page 46: ...507281 06 Page 46 of 58 Issue 1724 Table 13B Field Wiring Applications With Conventional Thermostat Continued...

Page 47: ...Field Wiring Applications With Conventional Thermostat Continued Connect W1 to W1 ONLY if using defrost tempering kit 67M41 NOTE DO NOT make a wire connection between the room thermostat L terminal a...

Page 48: ...Field Wiring Applications With Conventional Thermostat Continued Connect W1 to W1 ONLY if using defrost tempering kit 67M41 NOTE DO NOT make a wire connection between the room thermostat L terminal a...

Page 49: ...507281 06 Page 49 of 58 Issue 1724 Figure 66...

Page 50: ...ically light The ignitor does not get hot when there is no call for heat on these units Gas Valve Operation 1 STOP Read the safety information at the beginning of this section 2 Set the thermostat to...

Page 51: ...f flame is not detected after first ignition trial the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve The ignition control will then automatically repeat s...

Page 52: ...ximum carbon monoxide reading should not exceed 100 ppm High Altitude Information NOTE In Canada certification for installations at elevations over 4500 feet 1371 m is the jurisdiction of local author...

Page 53: ...tts cfm Watts cfm Watts 0 00 1380 315 1305 250 1190 200 965 105 920 100 0 10 1360 325 1270 255 1180 205 915 115 865 100 0 20 1310 335 1250 265 1130 215 880 120 815 110 0 30 1275 340 1205 275 1100 225...

Page 54: ...Sides or Return Air from Bottom and One Side Single Side Return Air Air volumes in bold require field fabricated transition to accommodate 20 x 25 x 1 in air filter in order to maintain proper air ve...

Page 55: ...condensate water 3 Remove the clean out cap from the condensate trap and empty water Inspect the trap then reinstall the clean out cap Cleaning Heat Exchanger If cleaning the heat exchanger becomes ne...

Page 56: ...lexible no hub connector Reconnect the 2 pin plug to the wire harness 38 Reconnect drain tubes between flue collar and cold end header box 39 Secure burner assembly to vestibule panel using four exist...

Page 57: ...ons Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their fur...

Page 58: ...imum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less...

Reviews: