507281-06
Page 53 of 58
Issue 1724
A95UH0452E12 / 95G2UH045E12 Performance (Less Filter)
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1345
340
1255
245
1150
185
895
105
845
95
0.10
1305
345
1225
250
1105
200
855
110
810
95
0.20
1290
360
1190
260
1080
205
825
120
780
105
0.30
1275
370
1150
270
1045
215
785
125
720
110
0.40
1220
385
1120
280
1015
220
735
135
690
120
0.50
1215
390
1090
290
980
230
705
140
635
125
0.60
1190
395
1060
300
950
240
650
150
600
135
0.70
N/A
N/A
1015
300
900
250
620
155
555
140
0.80
N/A
N/A
1000
310
870
260
580
160
520
145
A95UH0702E12 / 95G2UH070E12 Performance (Less Filter)
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
Medium-High
Medium
Medium-Low
Low
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
cfm
Watts
0.00
1380
315
1305
250
1190
200
965
105
920
100
0.10
1360
325
1270
255
1180
205
915
115
865
100
0.20
1310
335
1250
265
1130
215
880
120
815
110
0.30
1275
340
1205
275
1100
225
835
125
775
115
0.40
1250
355
1175
280
1065
230
795
135
730
125
0.50
1215
370
1145
295
1045
240
745
145
670
130
0.60
1200
380
1100
310
995
245
705
150
640
140
0.70
1145
380
1070
310
960
255
670
160
585
145
0.80
N/A
N/A
1035
320
925
265
610
165
550
155
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace
operating).
3. Check amp–draw on the blower motor.
Motor Nameplate__________Actual__________
Exhaust and Air Intake Pipe
1. Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2. Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check
termination for blockages.
3. Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
Blower Performance