CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E
Page 108
Analogical
@ (hexa) @ (deci)
DS50
01H
1
R/W 1 = 1 s
[ BMS ] Activation of the control by a computer or an automat - mode
BMS is activated if this value is different from zero, This value is
decreased every second
3934
02H
2
R/W 10 = 1.0°c
[Occupation][Room SP] Required maximum room temperature in °C.
Cooling set point
3322
(BMS)
03H
3
R/W 10 = 1.0°c
[Occupation][Room SP] Required minimum room temperature in °C.
Heating set point
3323
(BMS)
04H
4
R/W 10 = 1.0%
[Room SP] Required room minimum fresh air rate in % Middle of the
dead zone.
3312
(BMS)
05H
5
R/W 10 = 1.0°c
[Unoccupied][Room SP] Required maximum room temperature in °C.
Cooling set point
3322
(Uno)
06H
6
R/W 10 = 1.0°c
[Unoccupied][Room SP] Required minimum room temperature in °C.
Heating set point
3323
(Uno)
07H
7
R/W 10 = 1.0%
[Humidity] Desired Maximum relative humidity in Room (in %).
–
Dehumidification set point.
3341
(BMS)
08H
8
R/W 10 = 1.0%
[Humidity] Desired Minimum relative humidity in Room (in %).
–
Humidification set point.
3342
(BMS)
09H
9
R/W
not used
0AH
10
R/W
not used
0BH
11
R/W
not used
0CH
12
R/W 1 = 1h
[Clock] Hour
3121
0DH
13
R/W 1 = 1m
[Clock] Minute
3122
0EH
14
R/W 1 = 1
[Clock] Day of the month
3123
0FH
15
R/W 1 = 1
[Clock] Month
3124
10H
16
R/W 1 = 2001
[Clock] Year
3125
11H
17
R/W 10 = 1.0°c
[BMS] Room temperature coming from the BMS
2824
12H
18
R/W 10 = 1.0%
[BMS] Room humidity coming from the BMS
2828
13H
19
R/W 10 = 1.0°c
[BMS] Outdoor temperature coming from the BMS
2814
14H
20
R/W 10 = 1.0%
[BMS] Outdoor humidity coming from the BMS
2818
15H
21
R/W 1 = 1 ppm
[BMS] Air quality coming from the BMS
16H
22
R/W
not used
17H
23
R/W
not used
18H
24
R/W
not used
19H
25
R/W
not used
1AH
26
R/W
not used
1BH
27
R/W
not used
1CH
28
R/W
not used
1DH
29
R/W
not used
1EH
30
R/W
not used
1FH
31
R/W
not used
20H
32
R/W
not used
21H
33
R
1 = 1
[Alarm] Code Error
1000
22H
34
R
10 = 1.0°c
[Temperature] Room
2112
23H
35
R
10 = 1.0°c
[Temperature] Outdoor
2111
Summary of Contents for BAC020SNM
Page 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Page 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Page 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Page 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Page 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Page 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Page 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Page 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Page 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Page 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Page 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Page 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Page 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Page 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Page 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Page 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Page 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...