ELECTRIC HEAT DATA — CB19/CBH19-21,-26
Blower Coil Unit
Model Number
Electric Heat Model Number
& Shipping Weight
Number of
Steps & Phase
Volts
Input
kW
Input
**Btuh
Input
D
Blower
Amps
*Minimum
Circuit Ampacity
Model Number
& Shipping Weight
Steps & Phase
Input
Input
Input
Amps
Circuit 1
Circuit 2
ECB19 2 5
208
1.9
6,400
1.0
12.3
- - - -
ECB19-2.5
(68G86)
1 step
h
220
2.1
7,200
1.0
12.8
- - - -
(68G86)
4 lbs. (2 kg)
1 phase
230
2.3
7,800
1.0
13.4
- - - -
(
g)
240
2.5
8,500
1.0
13.9
- - - -
ECB19 5
208
3.8
12,800
1.0
23.5
- - - -
ECB19-5
(69G87)
1 step
h
220
4.2
14,300
1.0
24.8
- - - -
(69G87)
4 lbs. (2 kg)
1 phase
230
4.6
15,700
1.0
25.9
- - - -
g
240
5.0
17,100
1.0
26.9
- - - -
ECB19 6
208
4.5
15,400
1.0
28.0
- - - -
ECB19-6
(69G88)
2 steps
h
220
5.0
17,100
1.0
29.3
- - - -
(69G88)
5 lbs. (2 kg)
1 phase
230
5.5
18,800
1.0
30.9
- - - -
CB19-21
g
240
6.0
20,500
1.0
32.2
- - - -
CBH19-21
ECB19 7
208
5.3
17,900
1.0
32.5
- - - -
ECB19-7
(69G89)
2 steps
h
220
5.9
20,100
1.0
34.4
- - - -
(69G89)
5 lbs. (2 kg)
1 phase
230
6.4
21,900
1.0
35.8
- - - -
g
240
7.0
23,900
1.0
37.4
- - - -
ECB19 8
208
6.0
20,500
1.0
37.0
- - - -
ECB19-8
(69G90)
2 steps
h
220
6.7
22,900
1.0
39.0
- - - -
(69G90)
5 lbs. (2 kg)
1 phase
230
7.3
25,100
1.0
40.8
- - - -
g
240
8.0
27,300
1.0
42.6
- - - -
ECB19 10
208
7.5
25,600
1.0
45.9
- - - -
ECB19-10
(69G91)
2 steps
h
220
8.4
28,700
1.0
48.6
- - - -
(69G91)
5 lbs. (2 kg)
1 phase
230
9.2
31,400
1.0
50.8
- - - -
g
240
10.0
34,100
1.0
53.0
- - - -
ECB19 2 5
208
1.9
6,400
2.0
13.2
- - - -
ECB19-2.5
(69G86)
1 step
h
220
2.1
7,200
2.0
13.7
- - - -
(69G86)
4 lbs. (2 kg)
1 phase
230
2.3
7,800
2.0
14.3
- - - -
g
240
2.5
8,500
2.0
14.8
- - - -
ECB19 5
208
3.8
12,800
2.0
24.4
- - - -
ECB19-5
(69G87)
1 step
h
220
4.2
14,300
2.0
25.7
- - - -
(69G87)
4 lbs. (2 kg)
1 phase
230
4.6
15,700
2.0
26.8
- - - -
g
240
5.0
17,100
2.0
27.8
- - - -
ECB19 6
208
4.5
15,400
2.0
28.9
- - - -
ECB19-6
(69G88)
2 steps
h
220
5.0
17,200
2.0
30.2
- - - -
(69G88)
5 lbs. (2 kg)
1 phase
230
5.5
18,800
2.0
31.8
- - - -
g
240
6.0
20,500
2.0
33.7
- - - -
ECB19 7
208
5.3
17,900
2.0
33.4
- - - -
ECB19-7
(69G89)
2 steps
h
220
5.9
20,100
2.0
35.3
- - - -
(69G89)
5 lbs. (2 kg)
1 phase
230
6.4
21,900
2.0
36.7
- - - -
CB19-26
g
240
7.0
23,900
2.0
38.3
- - - -
CBH19-26
ECB19 8
208
6.0
20,500
2.0
37.9
- - - -
ECB19-8
(69G90)
2 steps
h
220
6.7
22,900
2.0
39.9
- - - -
(69G90)
5 lbs. (2 kg)
1 phase
230
7.3
25,100
2.0
41.7
- - - -
g
240
8.0
27,300
2.0
43.4
- - - -
ECB19 10
208
7.5
25,600
2.0
46.8
- - - -
ECB19-10
(69G91)
2 steps
h
220
8.4
28,700
2.0
49.5
- - - -
(69G91)
5 lbs. (2 kg)
1 phase
230
9.2
31,400
2.0
51.7
- - - -
g
240
10.0
34,100
2.0
53.9
- - - -
ECB19 12 5
208
9.4
32,000
2.0
39.4
18.9
ECB19-12.5
(69G92)
3 steps
h
220
10.5
35,800
2.0
41.2
19.9
(69G92)
10 lbs. (5 kg)
1 phase
230
11.5
39,200
2.0
43.4
20.8
g
240
12.5
42,600
2.0
45.2
21.8
ECB19 15
208
11.3
38,400
2.0
46.9
22.7
ECB19-15
(69G93)
3 steps
h
220
12.6
43,000
2.0
49.1
23.9
(69G93)
10 lbs. (5 kg)
1 phase
230
13.5
47,000
2.0
51.7
25.0
(
g)
240
15.0
51,200
2.0
53.9
26.0
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167
°
F (75
_
C).
**Electric heater capacity only — does not include additional blower motor heat capacity.
D
Minimum circuit ampacity for blower motor only.
— 6 —