ELECTRIC HEAT DATA — CB19/CBH19-31,-41
Blower Coil Unit
Model Number
Electric Heat Model Number
& Shipping Weight
Number of
Steps & Phase
Volts
Input
kW
Input
**Btuh
Input
D
Blower
Amps
*Minimum
Circuit Ampacity
Model Number
& Shipping Weight
Steps & Phase
Input
Input
Input
Amps
Circuit 1
Circuit 2
208
3.8
12,800
3.0
25.0
- - - -
ECB19-5
(69G87)
1 step
h
220
4.2
14,300
3.0
26.3
- - - -
(69G87)
4 lbs. (2 kg)
1 phase
230
4.6
15,700
3.0
27.4
- - - -
240
5.0
17,100
3.0
28.4
- - - -
208
4.5
15,400
3.0
29.5
- - - -
ECB19-6
(69G88)
2 steps
220
5.0
17,100
3.0
30.8
- - - -
(69G88)
5 lbs. (2 kg)
p
1 phase
230
5.5
18,800
3.0
32.4
- - - -
240
6.0
20,500
3.0
33.7
- - - -
208
5.3
17,900
3.0
34.0
- - - -
ECB19-7
(69G89)
2 steps
220
5.9
20,100
3.0
35.9
- - - -
(69G89)
5 lbs. (2 kg)
p
1 phase
230
6.4
21,900
3.0
37.3
- - - -
240
7.0
23,900
3.0
38.9
- - - -
CB19-31
208
6.0
20,500
3.0
38.5
- - - -
CBH19-31
and
ECB19-8
(69G90)
2 steps
220
6.7
22,900
3.0
40.5
- - - -
and
CB19-41
CBH19 41
(69G90)
5 lbs. (2 kg)
p
1 phase
230
7.3
25,100
3.0
43.3
- - - -
CBH19-41
240
8.0
27,300
3.0
44.0
- - - -
208
7.5
25,600
3.0
47.4
- - - -
ECB19-10
(69G91)
2 steps
220
8.4
28,700
3.0
50.1
- - - -
(69G91)
5 lbs. (2 kg)
p
1 phase
230
9.2
31,400
3.0
52.3
- - - -
240
10.0
34,100
3.0
54.5
- - - -
208
9.4
32,000
3.0
40.0
18.9
ECB19-12.5
(68G92)
3 steps
220
10.5
35,800
3.0
42.2
19.9
(68G92)
10 lbs. (5 kg)
p
1 phase
230
11.5
39,200
3.0
44.0
20.8
240
12.5
42,600
3.0
45.8
21.8
208
11.3
38,400
3.0
47.5
22.7
ECB19-15
(69G93)
3 steps
220
12.6
43,000
3.0
50.1
23.9
(69G93)
10 lbs. (5 kg)
p
1 phase
230
13.5
47,000
3.0
52.3
25.0
240
15.0
51,200
3.0
54.5
26.0
208
3.8
12,800
3.0
15.4
- - - -
ECB19-5
(69G97)
3 steps
220
4.2
14,300
3.0
16.2
- - - -
(69G97)
6 lbs. (3 kg)
p
3 phase
230
4.6
15,700
3.0
16.8
- - - -
240
5.0
17,100
3.0
17.4
- - - -
208
5.6
19,200
3.0
21.9
- - - -
ECB19-7.5
(69G98)
3 steps
220
6.3
21,500
3.0
23.0
- - - -
(69G98)
6 lbs. (3 kg)
p
3 phase
230
6.9
23,500
3.0
24.0
- - - -
240
7.5
25,600
3.0
24.9
- - - -
208
7.5
25,600
3.0
28.4
- - - -
CB19-41
ECB19-10
(69G99)
3 steps
220
8.4
28,700
3.0
29.9
- - - -
CBH19-41
(69G99)
6 lbs. (3 kg)
p
3 phase
230
9.2
31,400
3.0
31.3
- - - -
240
10.0
34,100
3.0
32.5
- - - -
208
11.3
38,400
3.0
41.5
- - - -
ECB19-15
(70G00)
3 steps
220
12.6
43,000
3.0
43.7
- - - -
(70G00)
9 lbs. (4 kg)
p
3 phase
230
13.5
47,000
3.0
45.7
- - - -
240
15.0
51,200
3.0
47.5
- - - -
208
15.0
51,200
3.0
47.4
45.0
ECB19-20
(69G94)
3 steps
220
16.8
57,300
3.0
50.1
47.8
(69G94)
14 lbs. (6 kg)
p
1 phase
230
18.4
62,700
3.0
52.3
49.9
240
20.0
68,200
3.0
54.5
52.2
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167
°
F (75
_
C).
**Electric heater capacity only — does not include additional blower motor heat capacity.
D
Minimum circuit ampacity for blower motor only.
— 7 —