background image

ELECTRIC HEAT DATA — CB19/CBH19-65

Blower Coil

Unit

Electric Heat

Model Number

Number of

Volts

kW

**Btuh

D

Blower

*Minimum Circuit Ampacity

Unit

Model Number

Model Number

& Shipping Weight

Steps & Phase

Input

Input

Input

Amps

Circuit 1

Circuit 2

Circuit 3

ECB19 8

208

6.0

20,500

6.0

41.7

- - - -

- - - -

ECB19-8

(69G90)

2 steps

h

220

6.7

22,900

6.0

43.6

- - - -

- - - -

(69G90)

5 lbs. (2 kg)

1 phase

230

7.3

25,100

6.0

45.4

- - - -

- - - -

(

g)

240

8.0

27,300

6.0

47.2

- - - -

- - - -

ECB19 10

208

7.5

25,600

6.0

50.5

- - - -

- - - -

ECB19-10

(69G91)

2 steps

h

220

8.4

28,700

6.0

53.3

- - - -

- - - -

(69G91)

5 lbs. (2 kg)

1 phase

230

9.2

31,400

6.0

55.4

- - - -

- - - -

g

240

10.0

34,100

6.0

57.7

- - - -

- - - -

ECB19 10

208

7.5

25,600

6.0

31.5

- - - -

- - - -

ECB19-10

(69G99)

3 steps

3 h

220

8.4

28,700

6.0

33.1

- - - -

- - - -

(69G99)

12 lbs. (5 kg)

3 phase

230

9.2

31,400

6.0

34.4

- - - -

- - - -

g

240

10.0

34,100

6.0

35.7

- - - -

- - - -

ECB19-10

3 steps

440

8.4

28,700

3.0

16.2

- - - -

- - - -

(70G04)

6 lbs (3 kg)

3 steps

3 phase

460

9.2

31,400

3.0

16.8

- - - -

- - - -

6 lbs. (3 kg)

3 phase

480

10.0

34,100

3.0

17.4

- - - -

- - - -

ECB19 12 5

208

9.4

32,000

6.0

43.2

18.9

- - - -

ECB19-12.5

(69G92)

3 steps

h

220

10.5

35,800

6.0

45.3

19.9

- - - -

(69G92)

10 lbs. (5 kg)

1 phase

230

11.5

39,200

6.0

47.2

20.8

- - - -

g

240

12.5

42,600

6.0

48.9

21.8

- - - -

ECB19 15

208

11.3

38,400

6.0

50.7

22.7

- - - -

ECB19-15

(69G93)

3 steps

h

220

12.6

43,000

6.0

53.3

23.9

- - - -

(69G93)

10 lbs. (5 kg)

1 phase

230

13.5

47,000

6.0

55.4

25.0

- - - -

g

240

15.0

51,200

6.0

57.7

26.0

- - - -

ECB19 15

208

11.3

38,400

6.0

44.7

- - - -

- - - -

ECB19-15

(70G00)

3 steps

h

220

12.6

43,000

6.0

46.8

- - - -

- - - -

(70G00)

9 lbs. (4 kg)

3 phase

230

13.5

47,000

6.0

48.8

- - - -

- - - -

g

240

15.0

51,200

6.0

50.7

- - - -

- - - -

CB19-65

ECB19-15

3 steps

440

12.6

43,000

3.0

23.0

- - - -

- - - -

CBH19-65

(70G05)

12 lbs (5 kg)

3 steps

3 phase

460

13.8

47,000

3.0

24.0

- - - -

- - - -

12 lbs. (5 kg)

3 phase

480

15.0

51,200

3.0

24.9

- - - -

- - - -

ECB19 20

208

15.0

51,200

6.0

50.5

45.0

- - - -

ECB19-20

(69G94)

4 steps

h

220

16.8

57,300

6.0

53.3

47.8

- - - -

(69G94)

14 lbs. (6 kg)

1 phase

230

18.4

62,700

6.0

55.4

49.9

- - - -

g

240

20.0

68,200

6.0

57.7

52.2

- - - -

ECB19 20

208

15.0

51,200

6.0

31.5

26.0

- - - -

ECB19-20

(70G01)

6 steps

h

220

16.8

57,300

6.0

33.1

27.6

- - - -

(70G01)

19 lbs. (9 kg)

3 phase

230

18.4

62,700

6.0

34.4

28.9

- - - -

g

240

20.0

68,200

6.0

35.7

30.2

- - - -

ECB19-20

6 steps

440

16.8

57,300

3.0

29.9

- - - -

- - - -

(70G06)

18 lbs (8 kg)

6 steps

3 phase

460

18.4

62,700

3.0

31.2

- - - -

- - - -

18 lbs. (8 kg)

3 phase

480

20.0

68,200

3.0

32.4

- - - -

- - - -

ECB19 25

208

18.8

64,100

6.0

50.5

45.0

22.7

ECB19-25

(69G95)

5 steps

h

220

21.0

71,700

6.0

53.3

47.8

23.9

(69G95)

18 lbs. (8 kg)

1 phase

230

23.0

78,300

6.0

55.4

49.9

25.0

(

g)

240

25.0

85,300

6.0

57.7

52.2

26.0

ECB19 25

208

18.8

64,100

6.0

38.2

32.7

- - - -

ECB19-25

(70G02)

6 steps

3 h

220

21.0

71,700

6.0

39.9

34.4

- - - -

(70G02)

19 lbs. (9 kg)

3 phase

230

23.0

78,300

6.0

41.5

36.0

- - - -

(

g)

240

25.0

85,300

6.0

43.2

37.7

- - - -

ECB19-25

6 steps

440

21.0

71,700

3.0

36.8

- - - -

- - - -

(70G07)

18 lbs (8 kg)

6 steps

3 phase

460

23.0

78,300

3.0

38.4

- - - -

- - - -

18 lbs. (8 kg)

3 phase

480

25.0

85,300

3.0

39.9

- - - -

- - - -

ECB19 30

208

22.5

76,900

6.0

50.5

45.0

45.0

ECB19-30

(69G96)

6 steps

h

220

25.2

86,000

6.0

53.3

47.8

47.8

(69G96)

19 lbs. (9 kg)

1 phase

230

27.5

94,000

6.0

55.4

49.9

49.9

(

g)

240

30.0

102,400

6.0

57.7

52.2

52.2

*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167

°

F (75

_

C).

**Electric heater capacity only — does not include additional blower motor heat capacity.

D

Minimum circuit ampacity for blower motor only.

— 9 —

Summary of Contents for CB19-21

Page 1: ...ts are shipped for up flow ap plications and may easily be field converted to the down flow position by turning the unit upside down and repositioning the coil drip shields and cabinet access panel Fi...

Page 2: ...asy replacement Ther mal sequencer relay brings the heating elements on and off line in sequence and equal increments with a time delay between each element Sequencer also initiates and terminates blo...

Page 3: ...x 1 Filter Adaptor Up Flow Only of filters mm 1 406 x 508 x 25 1 508 x 508 x 25 2 406 x 635 x 25 Shipping weight lbs kg 4 2 5 2 24 11 Down Flow Catalog number 85G52 85G53 85G54 Combustible Base Ship...

Page 4: ...t Btuh kW 9 000 2 6 9 500 2 8 ECB19 2 5 A F U E 99 8 99 8 ECB19 5 Output Btuh kW 18 000 5 3 18 000 5 3 18 000 5 3 18 000 5 3 19 000 5 6 ECB19 5 A F U E 99 7 99 7 99 9 100 100 ECB19 6 Output Btuh kW 21...

Page 5: ...5 815 1540 725 60 150 1665 785 1585 750 1405 665 NOTE All air data is measured external to unit Electric heaters have no appreciable air resistance For optional up flow air filter resistance see separ...

Page 6: ...86 4 lbs 2 kg 1 phase 230 2 3 7 800 2 0 14 3 g 240 2 5 8 500 2 0 14 8 ECB19 5 208 3 8 12 800 2 0 24 4 ECB19 5 69G87 1 step h 220 4 2 14 300 2 0 25 7 69G87 4 lbs 2 kg 1 phase 230 4 6 15 700 2 0 26 8 g...

Page 7: ...0 42 2 19 9 68G92 10 lbs 5 kg p 1 phase 230 11 5 39 200 3 0 44 0 20 8 240 12 5 42 600 3 0 45 8 21 8 208 11 3 38 400 3 0 47 5 22 7 ECB19 15 69G93 3 steps 220 12 6 43 000 3 0 50 1 23 9 69G93 10 lbs 5 kg...

Page 8: ...lb 5 k 3 steps 3 phase 460 9 2 31 400 2 0 16 1 12 lbs 5 kg 3 phase 480 10 0 34 100 2 0 16 7 ECB19 12 5 208 9 4 32 000 3 0 40 7 18 9 ECB19 12 5 68G92 3 steps 220 10 5 35 800 3 0 42 8 19 9 68G92 10 lbs...

Page 9: ...H19 65 70G05 12 lbs 5 kg 3 steps 3 phase 460 13 8 47 000 3 0 24 0 12 lbs 5 kg 3 phase 480 15 0 51 200 3 0 24 9 ECB19 20 208 15 0 51 200 6 0 50 5 45 0 ECB19 20 69G94 4 steps h 220 16 8 57 300 6 0 53 3...

Page 10: ...inches 60mm larger side to side and 2 1 2 inches 64mm larger front to rear than unit supply air opening DIMENSIONS inches mm CB19 UP FLOW POSITION Model N CB19 21 26 CB19 31 41 CB19 51 65 No inch mm...

Page 11: ...BOTH SIDES AIR FILTERS Furnished AIR FLOW SIDE VIEW FRONT VIEW 20 508 A B 18 457 1 25 1 25 OPENING SAME BOTH SIDES NOTE Air flow may be either direction SIDE VIEW 1 25 1 25 2 1 2 64 AIR FLOW AIR FILTE...

Page 12: ...EW INLET VIEW 21 5 8 549 1 1 2 38 5 8 16 33 838 9 229 BLOWER ELECTRICAL INLETS Both Sides OPTIONAL ELECTRIC HEAT Field Installed 12 305 B19 51 and B19 65 BLOWER SECTION CH19 51 and CH19 65 COIL SECTIO...

Reviews: