10
PROGRAMMING THE PARAMETERS
Proceed as follow, reach to the operating parameters of the unit:
To continue modifying other operating parameters follow steps 2-3-4.
To exit programming mode and accept the modifications to the parameters, press the
hold
button.
To exit programming mode, and NOT accept the modifications to the parameters, press the resume button, or wait for
1 minute of inactivity (the final 15 seconds are signalled by the flashing of the characters on the display).
All modifications on the operating unit parameters must be carried out by qualified personnel.
Incorrect programming of the parameters may cause damage to the unit, and consequently the loss
of guarantee of the unit.
COD: The code which appears on the display
The field variation for the parameters,
MIN: Minimum value for the parameter.
MAX: Maximum value for the parameter.
UNIT: The units of measure used.
C=Centigrade, s= seconds, min=minutes, h=hours, Khrs=hoursx1000
VAR.: Minimum variation allowed.
DEF: The default value, factory set.
The table below gives the following information for each parameter.
The parameters
are scrolled using
the front buttons.
The modifications
are accepted by
pressing
set
again.
clock
set
mode
fan
hold
resume
clock
set
mode
fan
hold
resume
clock
set
mode
fan
hold
resume
R3
2,0
20
C
0,5
2
Temperature differential cool/heat.
R4
0
10
C
0,5
0,5
Temperature dead zone.
R8
0
C
0,5
4
Auxiliary element set-point offset.
50
R9
1
C
0,5
2
Auxiliary element differential.
22
MIN MAX UNIT VAR. DEF
VALUES
DESCRIPTION
COD
S4
-12
12
C
0,5
0
Regulation probe calibration.
Value to be added to/subtracted from the value measured by the temperature
probe used for the regulation.
S6
1
15
---
1
1
Input digital filter, filter for analogue inputs, S6=1 the fastest.
S8
0
1
---
1
0
Indicates the presence of an external or internal temperature probe.
Step 1
Step 2
Step 3
Step 4
Step 5
Pressing simultaneously both
set
and
hold
buttons,
the display shows the first of the unit
operating parameters.
Parameters can be
changed while they
are flashing.
Press
set
to accept
modifications.