ALARM CODES
NO ALARM DISPLAYED MESSAGES
HOLD
R SP
FIRM
IS NOT AN ALARM INDICATION IT MEANS TEMPERATURE SET POINT OVERRIDE
On units with built in clock, if switches from time-band to manual operation, (pressing [HOLD] button) in such
situation the word HOLD appears and the comfort set point can be modified
IS NOT AN ALARM INDICATION IT MEANS THE EFFECTIVE START-UP TEMPERATURE
(press and buttons simultaneously). For example, in cooling operation with set = 24ºC and a compensation
(R4) of 1ºC, the effective start-up point of the compressor is 25ºC.
The displayed message will disappear after a few seconds.
IS NOT AN ALARM INDICATION IT MEANS THE FIRMWARE VERSION
(press and buttons simultaneously and hold for 5 seconds).
The displayed message will disappear after a few seconds.
*
Only included on terminal for units with free cooling, pressing [RESUME] button silences the buzzer.
NTC sensor temperature (°C) resistance (Kohm) relationship
°C
-50
-45
-40
-35
-30
-25
-20
-15
Kohm
329.20
247.50
188.40
144.00
111.30
86.39
67.74
53.39
°C
30
35
40
45
50
55
60
65
Kohm
8.31
6.94
5.82
4.91
4.16
3.53
3.02
2.58
ºC
-10
-5
0
5
10
15
20
25
Kohm
42.25
33.89
27.28
22.05
17.96
14.68
12.09
10.00
ºC
70
75
80
85
90
95
100
105
Kohm
2.22
1.92
1.66
1.45
1.26
1.10
0.97
0.85
SUMMARY OF ALARM EFFECTS
CODE
HR 1
HR 2
HR F
HI T
LO T
E ID
th F
E SR
E ST
E1
E2
E3
EE
MEANING
Maintenance alarm
High/ low ambient temperature
Compressor protection (ID3)
Outdoor fan protection
High pressure switch
Low pressure switch
Indoor fan protection (ID1)
Communication error
Error on ambient sensor (B1)
Error on free cooling sensor (B2)
Error on outdoor coil sensor (B3)
EEPROM alarm
RESET
Reset the
hour-counter
MANUAL
AUTOMATIC
MANUAL
AUTOMATIC
AUTOMATIC
AUTOMATIC
AUTOMATIC
SWITCH
OFF/ON
COMP
NO
ACTION
NO
ACTION
NO
ACTION
OFF
OFF
OFF
OFF
OFF
SUPPLY
FAN
NO
ACTION
NO
ACTION
NO
ACTION
OFF
OFF
ON
ON
OFF
CONDEN
FAN
NO
ACTION
NO
ACTION
NO
ACTION
OFF
OFF
OFF
OFF
OFF
HEATER
NO
ACTION
NO
ACTION
NO
ACTION
OFF
OFF
OFF
OFF
OFF
BUZZER
*
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
NOTES
Action delayed 10 min
Action delayed 0 sec
NO
ACTION
NO
ACTION
NO
ACTION
NO
ACTION
REVERSE
VALVE
NO
ACTION