background image

2

LNX15-574.2

EXTENDED VENT KIT INSTALLATION - KIT IDENTIFICATION

EXTENDED

VENT COLLAR

GASKET

EXTENDED

VENT COLLAR

(B-VENT)

SUPPORT

BRACKETS

(2 PARTS)

TEE CAP

(B-VENT)

TEE

(B-VENT)

VENT PIPE CLAMP

SUPPORT BRACKET

VENT PIPE

(B-VENT)

LOCKING WIND

VENT CAP

(B-VENT)

ELBOW

(B-VENT)

78" VENT KITS INCLUDE AN 

ADDITIONAL 90° ELBOW

Figure 2.1 – Non-Condensing Furnace Extended Vent 

Kit Components 

 For C-Cabinet, there are two vent assemblies and for D-Cabinet, 

there are two or four vent assemblies.  Refer to Table 2.2.

Table 2.2 - Extended Vent Kit Pipe Quanity by Length

Cabinet 

Size 

(Digit 6)

Heat Capacity and

Furnace Type 

(Digit 18)

Vent Pipe Qty by 

Length in Kit

36” 48” 60” 78”

B

F, G, H, J, K 

(Non-Condensing)

-

1

-

-

R, S, T 

(Condensing)

2

-

-

-

C

J, K, L, M 

(Non-Condensing)

-

1

1

-

U, V 

(Condensing)

4

-

-

-

D

K, L, M, Q 

(Non-Condensing)

-

-

-

2

1, 2, 3, 4, 5 

(Non-Condensing)

-

-

2

2

V, P, 6, 7, 8, 9 

(Condensing and/or Hybrid)

Contact Factory

Table 2.1 - Extended Vent Kit Pipe Quanity by Length

Before You Begin

Before installing the extended vent kit, verify the kit(s) to be 

installed is correct for the gas heat option on the unit. To 

verify, follow these steps, based on the Model DLV model 

nomenclature shown on the unit serial plate:
1.  Identify the Cabinet Size (Digit 6).
2.  Confirm the unit has a Gas Heat Option (Digit 17=2, 3, 5, 

or 6.

3.  Identify the Heat Capacity (Digit 18).
4.  Review Table 2.1 to determine which kit is required for the 

unit to which it will be installed.  The kits are marked with 

Item Codes.
Example: Digit 2=C, Digit 17=2, Digit 18=M.  From Table 

1.1, the kit should be 40336. 

5.  Inspect the contents of the kit(s) to become familiarized 

with the parts included.  Non-condensing kit components 

can be seen in Figure 2.1 and condensing kit components 

can be seen in Figure 2.2.  Note that kits include vent pipe 

that are 36", 48", 60" or 78" in total length. Review Table 

2.2 to determine how many lengths of pipe are included of 

various lengths.
Example: Digit 2=C, Digit 17=2, Digit 18=M.  From Table 

2.2, the kits include (1) 48" pipe and (1) 60" pipe. 

HOSE CLAMP

BIRD SCREEN

TERMINATION TEE

BIRD GUARD

VENT PIPES

VENT PIPE CLAMP AND

SUPPORT BRACKETS

COUPLER

EDGE SEAL

VENT ELBOW

LOCKING RING

Figure 2.2 – Condensing Furnace Extended Vent Kit 

Components 

Cabinet Size 

(Digit 6)

Heat Capacity and Furnace Type 

(Digit 18)

Item 

Code

B

F, G, H, J, K 

(Non-Condensing)

40335

R, S, T 

(Condensing)

40339

C

J, K, L, M 

(Non-Condensing)

40336

U, V 

(Condensing)

40340

D

K, L, M, Q 

(Non-Condensing)

40337

1, 2, 3, 4, 5 

(Non-Condensing)

40338

V, P, 6, 7, 8, 9 

(Condensing and/or Hybrid)

Contact 

Factory

Reviews: