TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
9/13
99H 16732
Digit_Output_LSB
Digital Output
L
9AH 16879
Alarm_Auto_1
Alarm_Auto_1
L
9BH 16880
Alarm_Auto_2
Alarm_Auto_2
L
9CH 16881
Alarm_Auto_3
Alarm_Auto_3
L
9DH 16882
Alarm_Auto_4
Alarm_Auto_4
L
9EH 16883
Alarm_Manu_1
Alarm_Manu_1
L
9FH 16884
Alarm_Manu_2
Alarm_Manu_2
L
A0H 16885
Alarm_Manu_3
Alarm_Manu_3
L
A1H 16886
Alarm_Manu_4
Alarm_Manu_4
L
A2H 18433
I/Ver
VERSION
L
5.d Detailed explanation of the CLIMATIC 400 parameters
5.d.1 /Logical parameters
In the zone of logical parameters , we can read the different status of the controller digital outlets and inlets . Correspondence
between these inlets , depending the model of unit are the following :
EAR 0472 to 0812
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch 1
Low pressure
switch 1
Fan +
compressor
protection 1
Defrosting
switch 1
Flow switch
High
pressure
switch 2
Low pressure
switch 2
Fan+
compressor
protection 2
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
switch 2
Remote
on/off
Remote
cooling /
heating
Not used
Not used
Not used
Not used
Not used
90H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1
4 way valve 1
Compressor
2
4 way valve 2
Water pump
Electrical
heater
Electrical
heater
Alarm
98H
99H
Not
used
Not
used
EAC 1003 to 1303
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch
Low pressure
switch 1
Fan
protection 1
Defrosting
pressostat 1
Flow switch
High
pressure
switch 2
Low pressure
switch 2
Fan
protection 2
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
pressostat 2
Remote
ON/OFF
Remote
cooling
/heating
Compressor
protection 1
Compressor
protection 2
Compressor
protection 3
Compressor
protection 4
Not used
0H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1
Fan 1
Compressor
2
Fan 2
Water pump
Electrical
heater
Electrical
heater
Alarm
98H
99H
Compressor
3
Compressor
4
EAR 1003 to 1303
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch 1
Low pressure
switch 1
Fan+
compressor
protection 1
Defrosting
pressostat 1
Flow switch
High
pressure
switch
Low pressure
switch 2
Fan
+compressor
protection
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
switch 2
Remote
ON/OFF
Remote
cooling/
heating
Compressor
protection 1
Compressor
protection 2
Compressor
protection 3
Compressor
protection 4
Not used
90H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1
4 way valve 1
Compressor
2
4 way valve 2
Water pump
Electrical
heater
Electrical
heater
Alarm
98H
99H
Compressor
3
Compressor
4