TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
10/13
5.d.2 /Analogical parameters/
00H, 01H (readable and writable)
This parameter defines the setpoint which the unit will function with in cooling ( 00H parameter) or in heating ( 01H parameter)
¡Important: Value of the required temperature has to be multiplied by 10!
Values included in this parameter must be within the range from the minimum setpoint ( 82H parameter for cooling / 80H for
heating) and the maximum setpoint ( Parameter 83H for cooling / 81 H for heating) .
¡Important: if the unit Works out of this range of temperatures, the unit may work with critical damages!
If the unit is a cooling only unit , there is not sense in using 01H parameter. We can limit this possibility with the 84 H parameter
which with the value 1 shows that the unit is heating pump version .
Example: H00=110 and H01=430 shows cooling setpoint 11.0ºC and heating setpoint 43.0ºC
02H parameter (readable and writable)
This parameter defines the function of the unit as following :
Parameter 02H=00H
∧
Stopped unit
Parameter 02H=80H
∧
Stand-By mode
Parameter 02H=81H
∧
Cooling only mode
Parameter 02H=82H
∧
Heat pump mode
¡Important: If different values are used , the result obtained maybe wrong!
To know if the unit can work in heat pump mode , read the value of the 84 H parameter.
¡Important: If in a cooling only unit , heat pump mode is demanded , the unit may work with critical damages!
80H, 81H, 82H, 83H parameters(only readable)
Cooling and heating setpoint limits, in detail :
80H
∧
Maximum heating setpoint
81H
∧
Minimum heating setpoint
82H
∧
Maximum cooling setpoint
83H
∧
Minimum cooling setpoint
Use these values to establish the limit values of the parameters 00 H and 01 H.
84H (only readable)
Shows with a value 0 if the unit is cooling only or with a value 1 if the unit is heat pump mode.
Using this value can establish if it is possible to modify the heating setpoint (H01 parameter) and more important also if we can
change to heat pump mode (H02 parameter)