TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
11/13
85H, 86H, 87H, 88H, 89H parameters ( only readable)
In these parameters we can read the values measured by the temperature sensors in the unit. The values shown are ºC x 10.
85H
∧
Outlet water temperature
86H
∧
Outlet water temperature
87H
∧
Refrigerant piping temperature 1
88H
∧
Outdoor temperature
89H
∧
Outdoor temperature circuit 2
Note:
Outdoor temperature will only show correct values if the unit is fitted with the outdoor temperature sensor (dynamic
setpoint kit)
Example: in 85H we will read the value 428, so the inlet water sensor is showing the value 42.8ºC.
8AH, 8BH, 8CH, 8DH, 8EH, 8FH, 90H, 91H, 92H, 93H parameters (only readable)
In these parameters we can read the hours of functioning of different components, in detail:
8AH
∧
Hours of functioning of compressor 1 (MSB)
8BH
∧
Hours of functioning of compressor 1 (LSB)
8CH
∧
Hours of functioning of compressor 2 (MSB)
8DH
∧
Hours of functioning of compressor 2 (LSB)
8EH
∧
Hours of functioning of compressor 3 (MSB)
8FH
∧
Hours of functioning of compressor 3 (LSB)
90H
∧
Hours of functioning of compressor 4 (MSB)
91H
∧
Hours of functioning of compressor 4 (LSB)
92H
∧
Hours of functioning of water pump (MSB)
93H
∧
Hours of functioning of water pump (LSB)
To calculate the value, the following formula has to be taken into account:
HR= MSB·256 + LSB
Example: in 8AH we can read the value 2 and in 8 BH a value of 48. This means 2 * 256 + 48=560. This shows that
compressor 1 has worked 560 hours.
94H, 95H, 95H, 96H, 97H, 98H, 99H parameters (only readable)
In these parameters we can read the status of the different devices of the unit:
94H, 95H
∧
Analogical outputs (% fan speed)
96H, 97H
∧
Digital inputs (pressostats, protections, remote on/ off, remote cooling/ heating)
98H, 99H
∧
Digital outputs (compressor, water pump, 4 way valve, antifreeze heater, alarm relay)
Correspondence with the different devices is the following:
94H and 95H parameters
show the speed (in %) of fans 1 and 2 :
0
: fan stopped
100
: maximum fan speed
Intermediate values:
fan in regulation
This value is valid for:
-
EAR 0472 to 0812 standard and FP1.
-
EAR 1003 to 1303 but only taking 0 and 100 values.