TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
12/13
96H y 97H
parameters
show the different digital inlets, according the models as following (1 means closed contact and 0 open
contact)
EAR 0472 to 0812
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
96H
Not used
Not used
High
pressure
switch 1
Low pressure
switch 1
Fan + comp
protection 1
Not used
Not used
Remote
cooling /
heating
97H
Defrosting
switch 2
Fan +
compressor 2
protection
Remote
ON/OFF
Not used
Low pressure
switch 2
Flow switch
Defrosting
switch
High
pressure
switch 2
EAC 1003 to 1303
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
96H
Compressor
protection 4
Compressor
protection 3
High
pressure
switch 1
Low pressure
switch 1
Fan
protection 1
Not used
Compressor
protection 2
Not used
97H
Not used
Fan
protection 2
Remote
on/off
Compressor
protection 1
Low pressure
switch 2
Flow switch
Not used
High
pressure
switch 2
EAR 1003 to 1303
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
96H
Compressor
protection 4
Compressor
protection 3
High
pressure
switch 1
Low pressure
switch 1
Fan
protection 1
Not used
Compressor
protection 1
Not used
97H
Defrosting
pressostat 2
Fan
protection 2
Remote
ON/OFF
Compressor
protection 2
Low pressure
switch 2
Flow switch
Defrost swicth
1
High
pressure
switch 2
Example : in a unit EAC 1103 the value of 96H is 208 (1111 1010 in binary) shows that the protections of the compressors 4,3
and 2 , the protection of the fan 1 , the high pressure switch 1 and the low pressure switch 1 are closed.
98H y 99H
will show the functioning of the following devices, according the models (1 means functioning, 0 means stop)
EAR 0472 to 0812
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
98H
Electrical
heater
Electrical
heater
Water pump
4 way valve 2
Compressor
2
4 way valve 1
Compressor
1
Alarm
99H
Fan 1 ( only
FP2 version)
Fan 2 ( only
FP2 version)
Not used
Not used
Not used
Not used
Not used
Not used
EAC 1003 to 1303
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
98H
Electrical
heater
Electrical
heater
Water pump
Fan 2
Compresso 2
Fan 1
Compressor
1
Alarm
99H
Compressor
3
Compressor
4
Not used
Not used
Not used
Not used
Not used
Not used
EAR 1003 to 1303
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
98H
Electrical
heater
Electrical
heater
Water pump
4 way valve 2
Compressor
2
4 way valve 1
Compressor
1
Alarm
99H
Compresor
3
Compresor
4
N/U N/U N/U N/U N/U N/U
Example : in one unit EAC 0472 the value of 34 (0010 0010 in binary) show that there are only functioning compressor 1 and
water pump .