TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
13/13
9AH, 9BH, 9CH, 9DH, 9EH, 9FH, A0H, A1H parameters (only readable)
In these parameters it is shown the presence of an alarm , and if it is neccessary the restarting. 90H, 91H and 92H parameters
shown the status of the alarm and 93H, 94H and 95H the necessity of restarting .
Alarm 9AH restart 9EH
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E07 E06 E05 E04 E03 E02 E01 E00
Alarm 9BH restart 9FH
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E23 E22 E21 E19 E13 E12 E11 E09
Alarm 9CH restart A0H
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E33 E32 E31 E29 E27 E26 E25 E24
Alarm 9DH restart A1H
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E46 E45 E44 E43 E42 E41 E40 E39
The meaning of the alarms is the following:
•
E00
∧
remote ON/ OFF
•
E01
∧
High pressure circuit 1
•
E02
∧
Low pressure circuit 1
•
E03
∧
Compresso overload relay 1
•
E04
∧
Fan overload relay 1
•
E05
∧
Antifreeze circuit 1
•
E06
∧
Error water outlet sensor
•
E07
∧
Error refrigerant piping sensor circuit 1
•
E09
∧
High pressure compressor 1
•
E11
∧
High pressure piping circuit 1
•
E12
∧
Low pressure piping circuit 1
•
E13
∧
Overload protection compressor 2
•
E19
∧
High pressure compressor 2
•
E21
∧
High pressure circuit 2
•
E22
∧
Low pressure circuit 2
•
E23
∧
Overload protection compressor3
•
E24
∧
Fan overload protection 2
•
E25
∧
Antifreeze protection 2
•
E26
∧
Error sensor ST5
•
E27
∧
Error refrigerant piping sensor 2
•
E29
∧
High pressure compressor 3
•
E31
∧
High piping temperature circuit 2
•
E32
∧
Low piping temperature circuit 2
•
E33
∧
Overload protection compressor 4
•
E39
∧
High pressure compressor 4
•
E40
∧
Error water inlet sensor
•
E41
∧
Error flow switch sensor
•
E42
∧
Error outdoor temperature sensor
•
E43
∧
External antifreeze
•
E44
∧
Unit without charge
•
E45
∧
Error in configuration
•
E46
∧
High inlet water temperature
Some of these units may be not available in the unit, or have slightly different meanings. See the manual of the unit to know the
detailed meaning of each alarm
Example : if appear one alarm by high pressure , the parameters 9AH and 9EH will take value 2 2 (0000 0010 in binary),
when the cause of the alarm is settled ( pressostat restarted) , parameter 9AH will show the value 0 (0000 0000 in binary) but
in the parameter 9EH nothing will change until we do not reset the alarm in the controller ( pressing the reset button) .
A2H parameter (only readable)
This parameter shows the current version of the software control.