TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
1/13
1.- ¿How is the net configured?
(How many units can be connected, which are the combination, what is needed by the
interface?)
The purpose of this net is connecting one or more units Ecolean to a BMS system. To get this we use the interface KP06. Up to 8
units can be connected (depending sizes and characteristics), to an interface KP06. We can connect up to 15 KP06 to the net.
In each Ecolean unit, is necessary to install a BUS adapter to convert the control (TTL) system in a signal RS-485.
We can connect in the net different controllers (as Climatic, Ecolean), but in a KP06 we can connect only controllers of the same
type.
2. - ¿What can be controlled by this net?
With this system, we can manage the following options in each of Ecolean units:
-
Select between OFF/STAND-BY/COOL/HEAT.
-
Modify the cooling / heating setpoint
-
Read the limitations in the unit, as the functioning of the heat pump, the maximum setpoint, and minimum setpoint. .
-
Read all the alarm status.
-
Read inlet water temperature , outlet water temperature, condensing temperature and outdoor temperature ( this last one only
if the unit is fitted with the dynamic setpoint option)
-
Read inlet signals status (pressostats, water flow switch, thermal relays motor protections).
-
Read the outlet signal status (compressor, fan, water pump ...).
3. - Fitting instructions.
It is necessary to include in every installation:
One Bus Adapter by each of the units
One KP06 at least by every 8 units
Bus Adapter will be delivered installed inside the Ecolean unit (electrical board), with the power supply taken from the general
power supply of the unit, and the control connection made. KP06 is delivered loose, for later installation in the most adequate
place.
KP06 nº1
KP06 nº2
KP06 nº3
KP06 nº15
( . . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )