TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
5/13
02H parameter (readable and writable)
This parameter defines the functioning of the unit according the following :
Parameter 02H=00H
∧
Stopped unit
Parameter 02H=04H
∧
Stand- By mode
Parameter 02H=05H
∧
Cooling only mode
Parameter 02H=06H
∧
Heating pump mode
¡Important. If values different from 0 are used, they may appear wrong values!
To know if the unit can work as a heat pump , parameter 84 H has to be read.
¡Important : if in a cooling only unit , heat pump mode is demanded , unit can work suffering critical damages!
80H, 81H, 82H, 83H parameters (only readable)
Limits of cooling setpoint and heating setpoint:
80H
∧
Maximum heating setpoint
81H
∧
Minimum heating setpoint
82H
∧
Maximum cooling setpoint
83H
∧
Minimum cooling setpoint
Use these values to establish the limits values for the parameters 00H y 01H.
84H (only readable)
Shows a 0 value if the unit is cooling only , and a 1 value if the unit is heat pump .
Use these value to establish if it is posible to modif. The heating setpoint ( H01 parameter ) and it is more important to know if it
can be switched in heat pump mode ( H02 parameter)
85H, 86H, 87H, 88H, 89H, 8AH, 8BH, 8CH parameters (only readable)
In this parameters we can read the values measured by different temperature sensors of the unit.
85H
∧
Water inlet temperature (MSB)
86H
∧
Water inlet temperature (LSB)
87H
∧
Water outlet temperature (MSB)
88H
∧
Water outlet temperature (LSB)
89H
∧
Refrigerant piping temperature (MSB)
8AH
∧
Refrigerant piping temperature (LSB)
8BH
∧
Outdoor temperature (MSB)
8CH
∧
Outdoor temperature (LSB)
Nota:
The outdoor temperature will only show the correct values if the outdoor temperature sensor is included. (dynamic
setpoint kit )
To calculate the value , we have to take into account the following value:
ºC·10= MSB·256 + LSB
Example : in 85H we can read value 1 and in 86H value 172. This means 1 * 256 + 172=428. The water indoor temperature
sensor is showing a value of 42.8ºC.