TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
7/13
90H, 91H, 92H, 93H, 94H, 95H parameters (only readable)
In these parameters the presence of an alarm is shown, and if it necessary , it can be restarted. 90H, 91H and 92H parameters,
show the alarm status ,and 93H, 94H and 95H show the necessity of restarting .
Alarm 90H restart 93H
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E11 E43 E05 E04 E41 E02 E01 E00
Alarm 91H restart 94H
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
E46 E42 E07 E06 E40 E45 E44 E12
Alarm 92H restart 95H
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Not used
Not used
Not used
Not used
Not used
Not used
E13
E03
The meaning of these different alarm codes is the following :
•
E00
∧
remote ON/OFF
•
E01
∧
High pressure
•
E02
∧
Low pressure
•
E03
∧
Compressor overload relay
•
E04
∧
Fan overload relay
•
E05
∧
Antifreeze
•
E06
∧
Error in outlet water sensor
•
E07
∧
Error in refrigerant piping sensor
•
E11
∧
Piping high temperature
•
E12
∧
Piping low temperature
•
E40
∧
Error in inlet water sensor
•
E41
∧
Error in flow switch sensor
•
E42
∧
Error in outdoor temperature sensor
•
E43
∧
External antifreeze
•
E44
∧
Unit without charge
•
E45
∧
Configuration error
•
E46
∧
High inlet water temperature
Some of these alarms may be not activated in your unit, or have slightly different meanings. In the unit manual you will see the
meaning of every of these alarms.
Example : if a high pressure alarm appears , 90H and 93H values will take then value 2 ( 0000 0000 in binary system) , when
the cause of the alarm is eliminated , ( restarting of the pressostat) , in 90H we will have then value 0 ( 0000 0000 in binary
system ) , but in 93H the value won´t change until we restart the alarm in the controller ( pressing reset button) .
96H parameter (readable only )
This parameter shows the current version of the control software.