Horizontal Application

Unit Installed on Platform

clearances.

GAS

ENTRY

VENT

PIPE

See the unit nameplate for

Line contact is permissible

SERVICE PLATFORM

FIGURE 13 

 WARNING

Improper installation of the furnace can result in personal 

injury  or  death.  Combustion  and  flue  products  must 

never be allowed to enter the return air system or the 

living space. Use screws and joint tape to seal the return 

air system to the furnace.
In platform installations with bottom return air, the furnace 

should be sealed airtight to the return air plenum. A 

door must never be used as a portion of the return air 

duct system. The base must provide a stable support 

and an airtight seal to the furnace. Allow absolutely no 

sagging, cracks, gaps, etc. The return and supply air 

duct systems must never be connected to or from other 

heating devices such as a fireplace or stove, etc. Fire, 

explosion, carbon monoxide poisoning, personal injury 

and/or property damage could result.

 WARNING

The blower access panel must be securely in place when 

the blower and burners are operating. Gas fumes, which 

could contain carbon monoxide, can be drawn into living 

space resulting in personal injury or death.

Filters

This unit is not equipped with a filter or rack. A field-pro

-

vided high-velocity filter is required for the unit to operate 

properly. Table 1 lists recommended filter sizes.
A filter must be in place any time the unit is operating.

 IMPORTANT

If a highefficiency filter is being installed as part of this 

system to ensure better indoor air quality, the filter must 

be  properly  sized.  Highefficiency  filters  have  a  higher 

static pressure drop than standardefficiency glass/foam 

filters. If the pressure drop is too great, system capacity 

and performance may be reduced. The pressure drop 

may also cause the limit to trip more frequently during 

the winter and the indoor coil to freeze in the summer, 

resulting in an increase in the number of service calls.

Before  using  any  filter  with  this  system,  check  the 

specifications provided by the filter manufacturer against 

the data given in the appropriate Lennox Product 

Specifications bulletin. Additional information is provided 

in Service and Application Note ACC002 (August 2000).

TABLE 1

 

Furnace Cabinet 

Width

Filter Size

Side Return

Bottom Return

14-1/2”

16 X 25 X 1 (1)

14 X 25 X 1 (1)

17-1/2”

16 X 25 X 1 (1)

16 X 25 X 1 (1)

21”

16 X 25 X 1 (1)

20 X 25 X 1 (1)

24-1/2”

16 X 25 X 1 (2)

24 X 25 X 1 (1)

Summary of Contents for EL280UH070P24A

Page 1: ...ife Installation and service must be performed by a licensed professional HVAC installer or equivalent service agency or the gas supplier 2017 Lennox Industries Inc Dallas Texas USA ELITE SERIES GAS F...

Page 2: ...y 3 Optional External Side Return Air Filter Kit is not for use with the optional Return Air Base 1 NOTE 60C and 60D size units that require second stage air volumes over 1800 cfm 850 L s must have on...

Page 3: ...installation of gas furnaces must conform with local building codes In the absence of local codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel...

Page 4: ...uction heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL280UH units may be us...

Page 5: ...renced subject which is represented only by the standard in its entirety CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the...

Page 6: ...d equipment in the confined space Each opening must be at least 100 square inches 64516 mm2 One opening shall be within 12 inches 305 mm of the top of the enclosure and one opening within 12 inches 30...

Page 7: ...penings shall each have a free area of at least one square inch 645 mm2 per 4 000 ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of attic INLET AIR Ends...

Page 8: ...hipping leg equipped with a shipping bolt and flat white plastic washer The bolt and washer must be re moved before the furnace is placed into operation Af ter the bolt and washer have been removed th...

Page 9: ...de Return Air with transition and filter FIGURE 8 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with Opt...

Page 10: ...ic or a crawl space Either suspend the furnace from roof rafters or floor joists as shown in figure 12 or install the furnace on a platform as shown in figure 13 Typical Horizontal Application Unit Su...

Page 11: ...can be drawn into living space resulting in personal injury or death Filters This unit is not equipped with a filter or rack A field pro vided high velocity filter is required for the unit to operate...

Page 12: ...duct system Return Air Plenum NOTE Return air must not be drawn from a roomwhere this furnace or any other gas fueled appliance i e water heater or carbon monoxide producing device i e wood fireplace...

Page 13: ...rifice plate See figure 14 Lift and rotate the assembly 90 degrees clockwise or counter clockwise to either the 3 o clock position or to 9 o clock position and re secure with four screws Gasket should...

Page 14: ...e other side of orifice plate and re connect pressure switch hose Re secure pressure switch wires by either pulling excess wires through the blower compartment and securing with supplied wire tie or c...

Page 15: ...irst vent connector elbow at a minimum of six inches 152 mm from the furnace vent outlet See figure 22 Venting Using a Masonry Chimney The following additional requirements apply when a lined masonry...

Page 16: ...gnized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable for venting EL280UH series units The chimney passageway must be checked periodically to ensure...

Page 17: ...the common venting tables should be reduced by 20 the equivalent of two 90 elbows 0 80 x maximum common vent capacity The horizontal length of the offset shall not exceed1 1 2 feet 46 m for each inch...

Page 18: ...l L feet Vent and Connector Diameter D inches 3 inch 4 inch 5 inch 6 inch Appliance Input Rating in Thousands of Btu Per Hour Min Max Min Max Min Max Min Max 6 0 0 78 0 152 0 251 0 375 2 13 51 18 97 2...

Page 19: ...33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 2...

Page 20: ...r other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting syst...

Page 21: ...figure 31 6 In some localities codes may require the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type...

Page 22: ...ged Tap Shown NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 25 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JO...

Page 23: ...must be properly grounded in accordance with national and local codes WARNING Fire Hazard Use of aluminum wire with this product may result in a fire causing property damage severe injury or death Use...

Page 24: ...er rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con nected to one of the provided neutral terminals If a hu midifier rated at greater than one amp is...

Page 25: ...DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 1 Heat 1 Cool NOTE Use DIP ond stage heat ON delay OFF10 minutes ON 15 minutes ON Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 C...

Page 26: ...tch Settings and On Board Links See figure 30 Wiring Connections DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 2 Heat 2 Cool OFF Cut Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 1 Coo...

Page 27: ...Page 27 EL280UH Schematic Wiring Diagram FIGURE 29...

Page 28: ...switch is factory positioned for use with a twostage thermostat If a single stage thermostat is to be used the DIP switch must be repositioned a Select OFF for two stage heating operation controlled b...

Page 29: ...control system parts and electrical parts that have been wet or to replace the furnace if deemed necessary WARNING If overheating occurs or if gas supply fails to shut off shut off the manual gas val...

Page 30: ...volution 1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Furnace should operate at least 5 minutes before...

Page 31: ...atuarl 1 7 3 5 1 5 3 2 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 110 Natural 1 7 3 5 1 5 2 8 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 135 Natural 1 7...

Page 32: ...ired setting FIGURE 32 Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower...

Page 33: ...witch set at SINGLE 1 SureLight control energizes combustion air inducer B6 on low heat speed Combustion air inducer runs until S128 low heat prove switch contacts close switch must close within 2 1 2...

Page 34: ...installed must be properly sized open and unobstructed to provide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or bl...

Page 35: ...e four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit 4 To clean burners run a vacuum cleaner with a soft brush attachment over the face of b...

Page 36: ...lent service agency or gas supplier Cabinet Parts Main access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wh...

Page 37: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Page 38: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Reviews: