background image

Page 29

TABLE 8

 

Heating Blower-Off Delay Switch Settings

Blower Off Delay 

(Seconds)

Switch 3

Switch 4

60

Off

On

90 

factory setting

Off

Off

120

On

Off

180

On

On

Switch 5 -- Cooling Blower-Off Delay -- T

he cooling 

blower-off delay (time that the blower operates after the 

cooling demand has been satisfied) can be adjusted by 

moving switch 5 on the integrated control. The switch is 

factory- set in the OFF position, which provides a cooling 

blower- off delay of 45 seconds. If the switch is toggled to 

the ON position, it will provide a 2-second cooling blow-

er-off delay

On-Board Link W951 Heat Pump (R to O)

On-board link W951 is a clippable connection between 

terminals R and O on the integrated control. W951 must 

be cut when the furnace is installed in applications which 

include a heat pump unit and a thermostat which features 

dual fuel use. If the link is left intact, terminal “O” will re-

main energized eliminating the HEAT MODE in the heat 

pump.

On-Board Link W915 2 Stage Compr (Y1 to Y2)

On-board link W915 is a clippable connection between 

terminals Y1 and Y2 on the integrated control. W915 must 

be cut if two-stage cooling will be used. If the link is not cut 

the outdoor unit will operate in second-stage cooling only 

and the indoor blower will operate on high cool speed only.

Unit Start-Up

FOR YOUR SAFETY READ BEFORE LIGHTING

 WARNING

Do not use this furnace if any part has been underwater. 

A  flood-damaged  furnace  is  extremely  dangerous. 

Attempts to use the furnace can result in fire or explosion. 

Immediately call a qualified service technician to inspect 

the furnace and to replace all gas controls, control 

system parts, and electrical parts that have been wet or 

to replace the furnace, if deemed necessary.

 WARNING

If overheating occurs or if gas supply fails to shut off, 

shut off the manual gas valve to the appliance before 

shutting off electrical supply.

 CAUTION

Before attempting to perform any service or maintenance, 

turn the electrical power to unit OFF at disconnect switch.

BEFORE LIGHTING 

smell all around the appliance area 

for gas. Be sure to smell next to the floor because some 

gas is heavier than air and will settle on the floor.

The gas valve on the EL280UH unit will be equipped with 

a gas control switch. Use only your hand to move the 

switch. Never use tools. If the switch will not turn or if the 

control switch will not move by hand, do not try to repair it.

Placing the furnace into operation:

EL280UH units are equipped with an automatic ignition 

system. Do not attempt to manually light burners on these 

furnaces. Each time the thermostat calls for heat, the 

burners will automatically light. The ignitor does not get 

hot when there is

 WARNING

If you do not follow these instructions exactly, a fire or 

explosion may result causing property damage, personal 

injury or death.

Gas Valve Operation (Figure 31)

1 - 

 STOP! 

Read the safety information at the beginning 

of this section.

2 -  Set the thermostat to the lowest setting.
3 -  Turn off all electrical power to the unit.
4 -   This furnace is equipped with an ignition device 

which automatically lights the burners. Do not try to 

light the burners by hand.

5 -  Remove the upper access panel.
6 -   Move switch on gas valve to OFF. Do not force. See 

figure 31.

7 - 

 Wait five minutes to clear out any gas. If you then 

smell gas, STOP! Immediately call your gas supplier 

from a neighbor’s phone. Follow the gas supplier’s 

instructions. If you do not smell gas go to next step

Summary of Contents for EL280UH070P24A

Page 1: ...ife Installation and service must be performed by a licensed professional HVAC installer or equivalent service agency or the gas supplier 2017 Lennox Industries Inc Dallas Texas USA ELITE SERIES GAS F...

Page 2: ...y 3 Optional External Side Return Air Filter Kit is not for use with the optional Return Air Base 1 NOTE 60C and 60D size units that require second stage air volumes over 1800 cfm 850 L s must have on...

Page 3: ...installation of gas furnaces must conform with local building codes In the absence of local codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel...

Page 4: ...uction heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL280UH units may be us...

Page 5: ...renced subject which is represented only by the standard in its entirety CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the...

Page 6: ...d equipment in the confined space Each opening must be at least 100 square inches 64516 mm2 One opening shall be within 12 inches 305 mm of the top of the enclosure and one opening within 12 inches 30...

Page 7: ...penings shall each have a free area of at least one square inch 645 mm2 per 4 000 ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of attic INLET AIR Ends...

Page 8: ...hipping leg equipped with a shipping bolt and flat white plastic washer The bolt and washer must be re moved before the furnace is placed into operation Af ter the bolt and washer have been removed th...

Page 9: ...de Return Air with transition and filter FIGURE 8 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with Opt...

Page 10: ...ic or a crawl space Either suspend the furnace from roof rafters or floor joists as shown in figure 12 or install the furnace on a platform as shown in figure 13 Typical Horizontal Application Unit Su...

Page 11: ...can be drawn into living space resulting in personal injury or death Filters This unit is not equipped with a filter or rack A field pro vided high velocity filter is required for the unit to operate...

Page 12: ...duct system Return Air Plenum NOTE Return air must not be drawn from a roomwhere this furnace or any other gas fueled appliance i e water heater or carbon monoxide producing device i e wood fireplace...

Page 13: ...rifice plate See figure 14 Lift and rotate the assembly 90 degrees clockwise or counter clockwise to either the 3 o clock position or to 9 o clock position and re secure with four screws Gasket should...

Page 14: ...e other side of orifice plate and re connect pressure switch hose Re secure pressure switch wires by either pulling excess wires through the blower compartment and securing with supplied wire tie or c...

Page 15: ...irst vent connector elbow at a minimum of six inches 152 mm from the furnace vent outlet See figure 22 Venting Using a Masonry Chimney The following additional requirements apply when a lined masonry...

Page 16: ...gnized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable for venting EL280UH series units The chimney passageway must be checked periodically to ensure...

Page 17: ...the common venting tables should be reduced by 20 the equivalent of two 90 elbows 0 80 x maximum common vent capacity The horizontal length of the offset shall not exceed1 1 2 feet 46 m for each inch...

Page 18: ...l L feet Vent and Connector Diameter D inches 3 inch 4 inch 5 inch 6 inch Appliance Input Rating in Thousands of Btu Per Hour Min Max Min Max Min Max Min Max 6 0 0 78 0 152 0 251 0 375 2 13 51 18 97 2...

Page 19: ...33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 2...

Page 20: ...r other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting syst...

Page 21: ...figure 31 6 In some localities codes may require the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type...

Page 22: ...ged Tap Shown NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 25 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JO...

Page 23: ...must be properly grounded in accordance with national and local codes WARNING Fire Hazard Use of aluminum wire with this product may result in a fire causing property damage severe injury or death Use...

Page 24: ...er rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con nected to one of the provided neutral terminals If a hu midifier rated at greater than one amp is...

Page 25: ...DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 1 Heat 1 Cool NOTE Use DIP ond stage heat ON delay OFF10 minutes ON 15 minutes ON Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 C...

Page 26: ...tch Settings and On Board Links See figure 30 Wiring Connections DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 2 Heat 2 Cool OFF Cut Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 1 Coo...

Page 27: ...Page 27 EL280UH Schematic Wiring Diagram FIGURE 29...

Page 28: ...switch is factory positioned for use with a twostage thermostat If a single stage thermostat is to be used the DIP switch must be repositioned a Select OFF for two stage heating operation controlled b...

Page 29: ...control system parts and electrical parts that have been wet or to replace the furnace if deemed necessary WARNING If overheating occurs or if gas supply fails to shut off shut off the manual gas val...

Page 30: ...volution 1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Furnace should operate at least 5 minutes before...

Page 31: ...atuarl 1 7 3 5 1 5 3 2 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 110 Natural 1 7 3 5 1 5 2 8 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 135 Natural 1 7...

Page 32: ...ired setting FIGURE 32 Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower...

Page 33: ...witch set at SINGLE 1 SureLight control energizes combustion air inducer B6 on low heat speed Combustion air inducer runs until S128 low heat prove switch contacts close switch must close within 2 1 2...

Page 34: ...installed must be properly sized open and unobstructed to provide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or bl...

Page 35: ...e four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit 4 To clean burners run a vacuum cleaner with a soft brush attachment over the face of b...

Page 36: ...lent service agency or gas supplier Cabinet Parts Main access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wh...

Page 37: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Page 38: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Reviews: