background image

Page 30

GAS VALVE SHOWN IN ON POSITION

INLET PRESSURE POST

HIGH FIRE ADJUSTMENT

SCREW

(under cap)

MANIFOLD

PRESSURE TAP

WHITE RODGERS GAS VALVE

FIGURE 31 

8 -   Move switch on gas valve to ON. Do not force. See 

figure 31.

9 -  Replace the upper access panel.
10 -  Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.

NOTE - 

When unit is initially started, steps 1 through 11 

may need to be repeated to purge air from gas line.

12 -  

If the appliance will not operate, follow the 

instructions “Turning Off Gas to Unit” and call your 

service technician or gas supplier.

Turning Off Gas to Unit

1 -  Set the thermostat to the lowest setting.
2 -   Turn off all electrical power to the unit if service is to 

be performed.

3 -  Remove the upper access panel.
4 -  Move switch on gas valve to OFF. Do not force.
5 -  Replace the upper access panel.

Failure To Operate

If the unit fails to operate, check the following:

1 -  Is the thermostat calling for heat?
2 -  Are access panels securely in place?
3 -  Is the main disconnect switch closed?
4 -  Is there a blown fuse or tripped circuit breaker?
5 - 

 Is the filter dirty or plugged? Dirty or plugged filters 

will cause the limit control to shut the unit off.

6 -  Is gas turned on at the meter?
7 -  Is the manual main shut-off valve open?
8 -  Is the gas valve ON/OFF switch in the ON position?
9 -   Is the unit ignition system in lock out? If the unit locks 

out again, call the service technician to inspect the 

unit for blockages.

10 - 

 Is  pressure  switch  closed?  Obstructed  flue  will 

cause unit to shut off at pressure switch. Check flue 

and outlet for blockages.

11 - 

 Are flame rollout switches tripped? If flame rollout 

switches are tripped, call the service technician for 

inspection.

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 9 

GAS METERING CLOCKING CHART

EL280 

Unit

Natural 1000 btu/cu ft

LP 2500 btu cu/cu ft

Seconds For One Revolution

1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial

-045

80

160

200

400

-070

55

110

136

272

-090

41

82

102

204

-110

33

66

82

164

-135

27

54

68

136

Furnace should operate at least 5 minutes before check-

ing gas flow. Determine time in seconds for two revolu

-

tions of gas through the meter. (Two revolutions assures 

a more accurate time.) Divide by two and compare to time  

in table 9 below. If manifold pressure matches table 11 

and rate is incorrect, check gas orifices for proper size and 

restriction. Remove temporary gas meter if installed.

NOTE - 

To obtain accurate reading, shut off all other gas 

appliances connected to meter.

Supply Pressure Measurement

An inlet post located on the gas valve provides access 

to the supply pressure. See figure 31. Back out the 3/32” 

hex screw one turn, connect a piece of 5/16” tubing and 

connect to a manometer to measure supply pressure. See 

table 11 for supply line pressure.

Manifold Pressure

A manifold pressure post located on the gas valve pro-

vides  access  to  the  manifold  pressure.  See  figure  3

1. 

Back out the 3/32 hex screw one turn, connect a piece 

of 5/16” tubing and connect to a manometer to measure 

manifold pressure.

NOTE - 

Pressure test adapter kit (10L34) is available from 

Lennox to facilitate manifold pressure measurement.

1 -   

Connect test gauge to manifold pressure post 

(figure 31) gas valve.

2 - 

 Ignite unit on high fire and let run for 5 minutes to 

allow for steady state conditions.

3 - 

 After  allowing  unit  to  stabilize  for  5  minutes,  record 

manifold pressure and compare to value given in table 

11.

4 -   If necessary, make adjustments. Figure 31 shows 

location of high fire adjustment screw.

5 - 

 If  an  adjustment  is  made  on  high  fire,  re-check 

manifold pressure on low fire. Do not adjust low fire 

manifold  pressure.  If  low  fire  manifold  pressure  is 

more  than  1/2”  above  or  below  value  specified  in 

table 11, replace valve.

6 -   soon as an accurate reading has been obtained. 

Turn the supply and manifold 3/32” hex screw one 

revolution back into the gas valve.

7 -   Start unit and perform leak check. Seal leaks if 

found.

Summary of Contents for EL280UH070P24A

Page 1: ...ife Installation and service must be performed by a licensed professional HVAC installer or equivalent service agency or the gas supplier 2017 Lennox Industries Inc Dallas Texas USA ELITE SERIES GAS F...

Page 2: ...y 3 Optional External Side Return Air Filter Kit is not for use with the optional Return Air Base 1 NOTE 60C and 60D size units that require second stage air volumes over 1800 cfm 850 L s must have on...

Page 3: ...installation of gas furnaces must conform with local building codes In the absence of local codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel...

Page 4: ...uction heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL280UH units may be us...

Page 5: ...renced subject which is represented only by the standard in its entirety CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the...

Page 6: ...d equipment in the confined space Each opening must be at least 100 square inches 64516 mm2 One opening shall be within 12 inches 305 mm of the top of the enclosure and one opening within 12 inches 30...

Page 7: ...penings shall each have a free area of at least one square inch 645 mm2 per 4 000 ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of attic INLET AIR Ends...

Page 8: ...hipping leg equipped with a shipping bolt and flat white plastic washer The bolt and washer must be re moved before the furnace is placed into operation Af ter the bolt and washer have been removed th...

Page 9: ...de Return Air with transition and filter FIGURE 8 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with Opt...

Page 10: ...ic or a crawl space Either suspend the furnace from roof rafters or floor joists as shown in figure 12 or install the furnace on a platform as shown in figure 13 Typical Horizontal Application Unit Su...

Page 11: ...can be drawn into living space resulting in personal injury or death Filters This unit is not equipped with a filter or rack A field pro vided high velocity filter is required for the unit to operate...

Page 12: ...duct system Return Air Plenum NOTE Return air must not be drawn from a roomwhere this furnace or any other gas fueled appliance i e water heater or carbon monoxide producing device i e wood fireplace...

Page 13: ...rifice plate See figure 14 Lift and rotate the assembly 90 degrees clockwise or counter clockwise to either the 3 o clock position or to 9 o clock position and re secure with four screws Gasket should...

Page 14: ...e other side of orifice plate and re connect pressure switch hose Re secure pressure switch wires by either pulling excess wires through the blower compartment and securing with supplied wire tie or c...

Page 15: ...irst vent connector elbow at a minimum of six inches 152 mm from the furnace vent outlet See figure 22 Venting Using a Masonry Chimney The following additional requirements apply when a lined masonry...

Page 16: ...gnized standards lined or relined with suitable materials or replaced with a gas vent or chimney suitable for venting EL280UH series units The chimney passageway must be checked periodically to ensure...

Page 17: ...the common venting tables should be reduced by 20 the equivalent of two 90 elbows 0 80 x maximum common vent capacity The horizontal length of the offset shall not exceed1 1 2 feet 46 m for each inch...

Page 18: ...l L feet Vent and Connector Diameter D inches 3 inch 4 inch 5 inch 6 inch Appliance Input Rating in Thousands of Btu Per Hour Min Max Min Max Min Max Min Max 6 0 0 78 0 152 0 251 0 375 2 13 51 18 97 2...

Page 19: ...33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 2...

Page 20: ...r other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting syst...

Page 21: ...figure 31 6 In some localities codes may require the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type...

Page 22: ...ged Tap Shown NOTE BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 25 GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JO...

Page 23: ...must be properly grounded in accordance with national and local codes WARNING Fire Hazard Use of aluminum wire with this product may result in a fire causing property damage severe injury or death Use...

Page 24: ...er rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con nected to one of the provided neutral terminals If a hu midifier rated at greater than one amp is...

Page 25: ...DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 1 Heat 1 Cool NOTE Use DIP ond stage heat ON delay OFF10 minutes ON 15 minutes ON Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 C...

Page 26: ...tch Settings and On Board Links See figure 30 Wiring Connections DIP Switch 1 W915 Two Stage Cooling W951 Heat Pumps 2 Heat 2 Cool OFF Cut Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 1 Coo...

Page 27: ...Page 27 EL280UH Schematic Wiring Diagram FIGURE 29...

Page 28: ...switch is factory positioned for use with a twostage thermostat If a single stage thermostat is to be used the DIP switch must be repositioned a Select OFF for two stage heating operation controlled b...

Page 29: ...control system parts and electrical parts that have been wet or to replace the furnace if deemed necessary WARNING If overheating occurs or if gas supply fails to shut off shut off the manual gas val...

Page 30: ...volution 1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Furnace should operate at least 5 minutes before...

Page 31: ...atuarl 1 7 3 5 1 5 3 2 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 110 Natural 1 7 3 5 1 5 2 8 1 7 3 5 4 5 13 0 LP propane 3 4 9 10 0 4 9 10 0 4 9 10 0 11 0 13 0 135 Natural 1 7...

Page 32: ...ired setting FIGURE 32 Electrical 1 Check all wiring for loose connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower...

Page 33: ...witch set at SINGLE 1 SureLight control energizes combustion air inducer B6 on low heat speed Combustion air inducer runs until S128 low heat prove switch contacts close switch must close within 2 1 2...

Page 34: ...installed must be properly sized open and unobstructed to provide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or bl...

Page 35: ...e four screws securing the burner manifold assembly to the vestibule panel and remove the assembly from the unit 4 To clean burners run a vacuum cleaner with a soft brush attachment over the face of b...

Page 36: ...lent service agency or gas supplier Cabinet Parts Main access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wh...

Page 37: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Page 38: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Reviews: