Page 5
• Do not install the furnace where drafts might blow
directly into it. This could cause improper combus-
tion and unsafe operation.
• Do not block the furnace combustion air openings
with clothing, boxes, doors, etc. Air is needed for
proper combustion and safe unit operation.
• When the furnace is installed in an attic or other
insulated space, keep insulation away from the fur-
nace.
• Please consult the manufacturer of your evaporator
coil for their recommendations on distance required
between the heat exchanger and their drain pan.
Adequate space must be provided between the
drain pan and the furnace heat exchanger.
NOTE - The Commonwealth of Massachusetts stipu-
lates these additional requirements:
•
Gas furnaces shall be installed by a licensed
plumber or fitter only.
•
The gas cock must be “T handle” type.
•
When a furnace is installed in an attic, the pas-
sageway to and service area surrounding the
equipment shall be floored.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and fireplaces force additional air
that could be used for combustion out of the house. Un-
less outside air is brought into the house for combustion,
negative pressure (outside pressure is greater than inside
pressure) will build to the point that a downdraft can oc-
cur in the furnace vent pipe or chimney. As a result, com-
bustion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combus-
tion and ventilation, use the guidelines and procedures in
this section to install EL280UH furnaces to ensure effi
-
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
piping. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (AN-
SI-Z223.1). This reprinted material is not the complete
and official position of the ANSI on the referenced subject,
which is represented only by the standard in its entirety.
CAUTION
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All gas-fired appliances require air for the combustion
process. If sufficient combustion air is not available, the
furnace or other appliances will operate inefficiently and
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as ex-
haust fans which force air out of the house. When fire
-
places, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is necessary
to ensure proper combustion and to prevent a downdraft.
Insufficient air causes incomplete combustion which can
result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace com-
ponents.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is in-
stalled in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com-
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
un confined, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.