background image

Page 13

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

OUTLET AIR

INLET AIR

WATER

HEATER

CHIMNEY

OR OIL

VENT

FIGURE 14

NOTE-Each air duct opening shall have a free area of at least one

square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour

of the total input rating of all equipment in the enclosure. If the equip

ment room is located against an outside wall and the air openings

communicate directly with the outdoors, each opening shall have a

free area of at least one square inch (6.4 square centimeters) per

4,000 Btu (1172 W) per hour of the total input rating of all other equip

ment in the enclosure.

OIL

FURNACE

When ducts are used, they shall be of the same cross-sec
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area, the
blocking effect of louvers, grilles, or screens must be consid
ered. If the design and free area of protective covering is not
known for calculating the size opening required, it may be
assumed that wood louvers will have 20 to 25 percent
free area and metal louvers and grilles will have 60 to 75
percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment operation.

CAUTION

Combustion air openings in the front of the furnace

must be kept free of obstructions. Any obstruction

will cause improper burner operation and may result

in a fire hazard or injury.

CAUTION

The barometric shall be in the same atmospheric

pressure zone as the combustion air inlet to the

furnace. Deviation from this practice will cause im

proper burner operation and may result in a fire

hazard or injury.

Direct Connection of Outdoor Air for Combustion

The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90

 elbow equals

6feet (1.8 m).

To convert the AFII burner from confined space to out
side combustion air, simply remove the three screws at
taching the inlet air scoop to the burner and insert 4" (102
mm) direct air intake piping.
The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space
air to be used as combustion air in the event that the
opening to the outdoor air becomes blocked. Using a
barometric relief in the intake will reduce the chance of
sooting.

CAUTION

DO NOT USE a barometric draft relief in exhaust

vent pipe if outdoor combustion air is connected

directly to the burner. The only exception are baro

metric draft reliefs as required by FIELD or TJERN

LUND power vents.

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a venting
system commonly run with separate appliances, the venting
system is likely to be too large to properly vent the remaining
attached appliances. The following test should be conducted
while each appliance is in operation and the other ap
pliances not in operation remain connected to the com
mon venting system. If venting system has been installed
improperly, the system must be corrected as outlined in the
previous section.
1 - Seal any unused openings in the common venting sys

tem.

 2 - Visually inspect venting system for proper size and hori

zontal pitch and determine there is no blockage or restric
tion, leakage, corrosion or other deficiencies which could
cause an unsafe condition.

 3 - Insofar as is practical, close all building doors and

windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliances
not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and bath
room exhausts, so they will operate at maximum
speed. Do not operate a summer exhaust fan. Close
fireplace dampers.

 4 - Following the lighting instruction on the unit, place the

appliance being inspected in operation. Adjust thermo
stat so appliance will operate continuously.

 5 - Test for spillage using a draft gauge.

Summary of Contents for Elite 80 Series

Page 1: ...furnaces use Beckett oil burners with heating capacities of 105 000 to 154 000 Btuh 30 8 kW to 45 1 kW OF24 units are suitable for residential or commercial application The drum type heat exchanger co...

Page 2: ...203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 40 1016 41 1041 cfm L s at 20 in wg 50 Pa external static pressure 820 390 1170 550 1550 730 Number and size of filters in mm...

Page 3: ...in mm 10 x 8 254 x 203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 41 1041 42 1067 cfm L s at 20 in wg 50 Pa external static pressure 1300 615 105 input 1220 575 120 input...

Page 4: ...URNER INDOOR BLOWER BLOWER MOTOR OBSERVATION PORT CLEAN OUT PORT FLUE OPENING HEAT EXCHANGER COMBUSTION AIR INTAKE FIGURE 2 OF24 GENERAL PARTS ORIENTA TION CLEAN OUT PORT FAN LIMIT SWITCH BECKETT AFII...

Page 5: ...identifies the burners used in Lennox units Figure 3 shows the typical layout of the burner assembly 1 Combustion Air Blower Pump Motor B6 The burner is activated by the primary control A com bustion...

Page 6: ...OZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET DOOR GASKET REAR ACCESS COUPLING OIL PUMP PLATE ESCUTCHEON NUT SPLINED DOOR ASSY REAR ACCESS ASSY HOUSING MAIN HOLE PLUG SCREWS AIR TUBE FLANGE ASSY EL...

Page 7: ...in the O24 OF24 The firing rate dictates which head is used See table 1 The greater the FB number the larger the slots on the head When combustion takes place the flame will be cylindrical compact sha...

Page 8: ...an air free fuel to the burner An oil filter is required for all models Use an oil filter of gener ous capacity for all installations Install filter inside the building between the tank shut off valve...

Page 9: ...g g Single Stage Two Stage Single Stage Two Stage 0 0 0 m 84 25 6 m 93 28 3 m 100 30 5 m 100 30 5 m 2 0 6 m 73 22 3 m 85 25 9 m 100 30 5 m 100 30 5 m 4 1 2m 63 19 2 m 77 23 5 m 100 30 5 m 100 30 5 m 6...

Page 10: ...not pass through a floor or ceiling Clear ances to single wall vent pipe should be no less than 6 152 mm more if local codes require it 8 The vent may pass through a wall where provisions have been m...

Page 11: ...rements for exhaust vents and oil piping Combustion Air Requirements CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the hea...

Page 12: ...tilation the confined space shall be provided with two permanent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must...

Page 13: ...from confined space to out side combustion air simply remove the three screws at taching the inlet air scoop to the burner and insert 4 102 mm direct air intake piping The use of a barometric relief p...

Page 14: ...be located within 18 457 mm of the furnace vent outlet See figure 15 for barometric draft con trol location III START UP A Preliminary and Seasonal Checks 1 Inspect electrical wiring both field and f...

Page 15: ...inimum FIGURE 16 AFII ELECTRODE TIP GAP To position the electrode tips beyond the face of the nozzle and above the center line position the gauge as shown in figure 17 Align the center mark with the n...

Page 16: ...retention head burners Oil furnace installations also require careful inspection to make sure the chimney is in good condition and can ac commodate the products of combustion The temperature in uncon...

Page 17: ...mbly will come out of the furnace There is adequate wire to remove the burner without disconnecting wires Once removed just turn the burner around in the vest panel area NOTE Before disassembling any...

Page 18: ...rom the primary control If the motor and blower wheel only need to be removed to check and clean there is adequate wire in the motor wiring harness without disconnecting 3 Loosen two bolts securing mo...

Page 19: ...atmosphere 3 With only the blower motor running and the evapora tor coil dry observe the manometer reading Adjust blower motor speed to deliver the air desired accord ing to the job requirements 4 Pr...

Page 20: ...as described in section IV D Supply Air Blower 1 Disconnect power to unit 2 Check and clean blower wheel 3 Motors are prelubricated for extended life no further lu brication is required E Vent Pipe Th...

Page 21: ...close energizing combustion air blower pump B6 3 When 1K2 closes the electronic ignitor is energized When 1K1 closes the solid state switch and cad cell are energized When the cad cell senses light t...

Page 22: ...NCE 1 When 1K2 closes 120VAC is routed through the relay timer electronic ignitor A73 and the limit switch 2 The relay timer energizes the venter motor 3 After the venter motor establishes a draft the...

Page 23: ...RATION SEQUENCE 1 When 1K2 closes 120VAC is routed through the relay 2 The relay energizes the venter motor 3 After the venter motor establishes a draft the N O fan proving switch closes completing th...

Page 24: ...lution Close all leaks with cement Problem Failure to extend the length of the flue partition down to the floor Detected by inspection or smoke test Solution Extend partition to floor level Problem Sm...

Page 25: ...r leak around cover Be sure strainer cover screws are tightened securely Check for damaged cover gasket To determine the cause of improper cutoff insert a pressure gauge in the nozzle port of the fuel...

Page 26: ...r auxiliary control switch open Open circuit between disconnect switch and limit control Low line voltage or power failure Defective internal control circuit Jumper terminals if burner starts switch i...

Page 27: ...ll power company Properly ground transformer case Check voltage at power source Correct cause of voltage drop or call power company Motor does not come up to speed and trips out on overload Turn off p...

Page 28: ...hermostat in warm air draft Dirty furnace air filters Blower running too slow Blower motor seized or burned out Blower wheel in backwards Wrong motor rotation Restrictions in return or supply air syst...

Reviews: