background image

Page 5

TABLE 1

FURNACE / BURNER SPECIFICATIONS

Unit

Lennox Burner

Part Number

Burner

Model

*Initial Air

Dial

Setting

Output

Nozzle Size

(Delevan)

Pump

Pressure

Head

70

35K74

AFII 85

3.0

57,000 BTU

(16.7 kW)

0.50 X 80

A

100 psig

(689.5 kPa)

FB0

105

35K75

AFII 85

4.0

84,000 BTU

(24.6 kW)

0.65 X 80

B

140 psig

965.3 kPa)

FB3

120

35K75

AFII 85

4.5

105,000 BTU

(30.8 kW)

0.75 X 80

B

140 psig

965.3 kPa)

FB3

140

35K76

AFII 150

6.0

112,000 BTU

(32.8 kW)

0.85 X 80

B

140 psig

965.3 kPa)

FB6

154

35K76

AFII 150

6.5

125,000 BTU

(36.6 kW)

1.00 X 80

B

140 psig

965.3 kPa)

FB6

*NOTE: The initial air dial setting is provided to get unit started. The air dial setting

 MUST

 be adjusted after startup to

achieve proper combustion.

CAUTION

Electrostatic discharge can affect electronic

components. Take precautions during furnace

installation and service to protect the furnace's

electronic controls. Precautions will help to avoid

control exposure to electrostatic discharge by

putting the furnace, the control and the techni

cian at the same electrostatic potential. Neutral

ize electrostatic charge by touching hand and all

tools on an unpainted unit surface, such as the

gas valve or blower deck, before performing any

service procedure.

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

I-UNIT COMPONENTS

General parts orientation for the O24 and OF24 are shown in

figures 1 and 2 respectively. The O24 and OF24 burner, limit

switch and cleanout ports may be accessed by removing the

front access panel. The blower can be accessed in the O24

and OF24 by removing the blower access panel.

A-Burner (Figure 3)

The O24 and OF24 oil furnaces use the Beckett AFII burner.

The oil burner provides an atomized oil vapor mixed with the

correct proportion of air when it is ignited in the combustion

chamber. Oil burner minimum and maximum ratings are listed

on the unit nameplate. Proper air adjustment for these ratings

is achieved through the air adjustment dial. Set air dial to the

initial air dial setting (see table 1). After start up adjust air dial to

achieve proper combustion. Remember to tighten set screw on

air dial.

The AFII burner is available in five sizes with either a single

or two stage pump. Table 1 identifies the burners used in

Lennox units. Figure 3 shows the typical layout of the burner

assembly.

1-Combustion Air Blower / Pump Motor (B6)

The burner is activated by the primary control. A com

bustion air blower is mounted on the motor shaft. The

motor shaft also connects to the direct drive oil pump

through a coupler. The burner motor turns both the com

bustion air blower and the oil pump. The motor operates

at 3500 RPM.

Burner motors are overload protected. In the event of ex

cess motor temperature or current, the overload opens

to de-energize the motor. The overload automatically re

sets after temperature has returned to normal. Keep mo

tor clean to prevent starting switch from sticking. All AFII

motors are permanently lubricated. No further oiling is required.

2-Combustion Air Blower / Pump Fuse (F22)

(-140 and -154 CSA units only)

In the -140 and -154 Canadian units an in line fuse (F22) is

used between the line voltage from the blower control and

the blower / pump motor. The fuse is rated at 300 volts and

15 amps.

3- Pump

The O24 and OF24 oil furnaces use a single stage, 3450

RPM pump. A two stage pump is available as an option

(catalog # 65A44). The oil burner is shipped from factory

for use in a single line system. To convert the pump to a

two line system, install the bypass plug provided in the at

tached bag according to the accompanying instructions.

4-Burner Control (A3) & Transformer (T1)

The burner control, along with the matching cad cell, proves

flame and controls the burner. After the cad cell closes a circuit

to the burner control, the burner control de-energizes the safety

switch heater to allow the unit to operate normally. The burner

control allows 45 seconds for the cad cell to close. If the cad cell

remains open after the 45 second time frame, the burner con

trol locks out. The burner control must be manually reset by de

pressing the red reset button on top of the burner control.

Transformer (T1) is part of the burner control. T1 provides

24VAC to the low voltage components in the unit and to the

thermostat.

5-Cad Cell (R26)

Together the cad cell and the burner control prove flame.

The cad cell senses the presence of burner light (less re

sistance) to close a circuit to the burner control.

IMPORTANT-Burner should not be installed so it is ex

posed to direct sunlight or electric bulb light. If the cell

is exposed to light on start up, the burner will not oper

ate.

Summary of Contents for Elite 80 Series

Page 1: ...furnaces use Beckett oil burners with heating capacities of 105 000 to 154 000 Btuh 30 8 kW to 45 1 kW OF24 units are suitable for residential or commercial application The drum type heat exchanger co...

Page 2: ...203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 40 1016 41 1041 cfm L s at 20 in wg 50 Pa external static pressure 820 390 1170 550 1550 730 Number and size of filters in mm...

Page 3: ...in mm 10 x 8 254 x 203 12 x 9 305 x 229 Blower Data Blower pulley in mm 7 178 Belt size in mm 41 1041 42 1067 cfm L s at 20 in wg 50 Pa external static pressure 1300 615 105 input 1220 575 120 input...

Page 4: ...URNER INDOOR BLOWER BLOWER MOTOR OBSERVATION PORT CLEAN OUT PORT FLUE OPENING HEAT EXCHANGER COMBUSTION AIR INTAKE FIGURE 2 OF24 GENERAL PARTS ORIENTA TION CLEAN OUT PORT FAN LIMIT SWITCH BECKETT AFII...

Page 5: ...identifies the burners used in Lennox units Figure 3 shows the typical layout of the burner assembly 1 Combustion Air Blower Pump Motor B6 The burner is activated by the primary control A com bustion...

Page 6: ...OZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET DOOR GASKET REAR ACCESS COUPLING OIL PUMP PLATE ESCUTCHEON NUT SPLINED DOOR ASSY REAR ACCESS ASSY HOUSING MAIN HOLE PLUG SCREWS AIR TUBE FLANGE ASSY EL...

Page 7: ...in the O24 OF24 The firing rate dictates which head is used See table 1 The greater the FB number the larger the slots on the head When combustion takes place the flame will be cylindrical compact sha...

Page 8: ...an air free fuel to the burner An oil filter is required for all models Use an oil filter of gener ous capacity for all installations Install filter inside the building between the tank shut off valve...

Page 9: ...g g Single Stage Two Stage Single Stage Two Stage 0 0 0 m 84 25 6 m 93 28 3 m 100 30 5 m 100 30 5 m 2 0 6 m 73 22 3 m 85 25 9 m 100 30 5 m 100 30 5 m 4 1 2m 63 19 2 m 77 23 5 m 100 30 5 m 100 30 5 m 6...

Page 10: ...not pass through a floor or ceiling Clear ances to single wall vent pipe should be no less than 6 152 mm more if local codes require it 8 The vent may pass through a wall where provisions have been m...

Page 11: ...rements for exhaust vents and oil piping Combustion Air Requirements CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the hea...

Page 12: ...tilation the confined space shall be provided with two permanent openings One opening shall be within 12 305 mm of the top of the enclosure and one within 12 305 mm of the bottom These openings must...

Page 13: ...from confined space to out side combustion air simply remove the three screws at taching the inlet air scoop to the burner and insert 4 102 mm direct air intake piping The use of a barometric relief p...

Page 14: ...be located within 18 457 mm of the furnace vent outlet See figure 15 for barometric draft con trol location III START UP A Preliminary and Seasonal Checks 1 Inspect electrical wiring both field and f...

Page 15: ...inimum FIGURE 16 AFII ELECTRODE TIP GAP To position the electrode tips beyond the face of the nozzle and above the center line position the gauge as shown in figure 17 Align the center mark with the n...

Page 16: ...retention head burners Oil furnace installations also require careful inspection to make sure the chimney is in good condition and can ac commodate the products of combustion The temperature in uncon...

Page 17: ...mbly will come out of the furnace There is adequate wire to remove the burner without disconnecting wires Once removed just turn the burner around in the vest panel area NOTE Before disassembling any...

Page 18: ...rom the primary control If the motor and blower wheel only need to be removed to check and clean there is adequate wire in the motor wiring harness without disconnecting 3 Loosen two bolts securing mo...

Page 19: ...atmosphere 3 With only the blower motor running and the evapora tor coil dry observe the manometer reading Adjust blower motor speed to deliver the air desired accord ing to the job requirements 4 Pr...

Page 20: ...as described in section IV D Supply Air Blower 1 Disconnect power to unit 2 Check and clean blower wheel 3 Motors are prelubricated for extended life no further lu brication is required E Vent Pipe Th...

Page 21: ...close energizing combustion air blower pump B6 3 When 1K2 closes the electronic ignitor is energized When 1K1 closes the solid state switch and cad cell are energized When the cad cell senses light t...

Page 22: ...NCE 1 When 1K2 closes 120VAC is routed through the relay timer electronic ignitor A73 and the limit switch 2 The relay timer energizes the venter motor 3 After the venter motor establishes a draft the...

Page 23: ...RATION SEQUENCE 1 When 1K2 closes 120VAC is routed through the relay 2 The relay energizes the venter motor 3 After the venter motor establishes a draft the N O fan proving switch closes completing th...

Page 24: ...lution Close all leaks with cement Problem Failure to extend the length of the flue partition down to the floor Detected by inspection or smoke test Solution Extend partition to floor level Problem Sm...

Page 25: ...r leak around cover Be sure strainer cover screws are tightened securely Check for damaged cover gasket To determine the cause of improper cutoff insert a pressure gauge in the nozzle port of the fuel...

Page 26: ...r auxiliary control switch open Open circuit between disconnect switch and limit control Low line voltage or power failure Defective internal control circuit Jumper terminals if burner starts switch i...

Page 27: ...ll power company Properly ground transformer case Check voltage at power source Correct cause of voltage drop or call power company Motor does not come up to speed and trips out on overload Turn off p...

Page 28: ...hermostat in warm air draft Dirty furnace air filters Blower running too slow Blower motor seized or burned out Blower wheel in backwards Wrong motor rotation Restrictions in return or supply air syst...

Reviews: