background image

Page 13

Table 6

Fuel Pump Usage

Pump

Piping Application

Maximum Lift (vacuum)

Single-Stage Pump

One-Pipe System

8 ft. (6” Hg vacuum)

Two-Pipe System

10 ft. (12” Hg vacuum)

Two-Stage Pump

Two-Pipe System

10 ft. or greater

(12” to 17” Hg vacuum)

Oil Supply Line & Filter Connections

One-Pipe Systems

CAUTION

Do not install the bypass plug into the pump on one-
pipe systems.

The burner is shipped with fuel pump set for one-pipe op­
eration. For one-pipe systems, the oil supply pipe is con­
nected to the inlet tap on the pump. A one-pipe system
should only be used where there is gravity oil flow to the
pump and the pipe is not run at any point above the oil level
in the tank.

 1 - Connect the inlet pipe to the pump inlet. Start the

burner.

 2 - Set the primary burner control for continuous opera­

tion during purging.

 3 - Turn the bleed valve one turn counterclockwise to

open.

 4 - Bleed the unit until all air bubbles disappear.

NOTE - Hurried bleeding will prevent the unit from op­
erating properly.

 5 - Tighten the bleed valve securely.

Two-Pipe Systems

If the installation requires a two-pipe operation, install the
bypass plug included in the bag which is attached to the
pump. To convert the pump, install the bypass plug ac­
cording to the provided pump instructions. Notice in the
two‐pipe system the return pipe must terminate in the tank
3” (76 mm) to 4” (102 mm) above the supply inlet. Ensure
the return pipe terminates at the correct measurement or
air may escape into the system. This could result in loss of
prime.

NOTE- If using an outside tank in cold climates a number
one fuel or an oil treatment is strongly recommended.

 1 - Remove 1/4” plug from return port.

 2 - Insert bypass plug and tighten it. See figure 13.

 3 - Attach the return and inlet pipes. Start the burner. Air

bleeding is automatic.

NOTE - If a faster bleed is necessary, open the bleed
valve.

 4 - The return pipe must terminate 3” to 4” above the sup­

ply pipe inlet. See figure 13.

NOTE - If the return pipe does not terminate where it
should, air may enter the system, and prime may be
lost.

An oil filter is required for all models.

 Install a field sup­

plied oil filter inside the building between the tank shut‐off
valve and the burner. Locate filter close to burner for easy
maintenance. Table 7 lists the filters for the ELO183DH
furnace.

Table 7

Oil Filters

Cat. 

Number

10 micron filter (no mounting bracket)

81P89

10 micron filter (mounting bracket)

53P92

10 micron replacement cartridge for filter, 45 gph

53P93

Filter restriction indicator gauge

53P90

Consult burner manufacturer's instructions packaged with
unit for further details concerning oil supply pipe connec­
tions.

Leak Check

After oil piping is completed, carefully check all piping con­
nections (factory and field) for oil leaks.

Oil Line Heater (Optional)

A heater for the oil line is available for applications that are
located in cold climates. The heater warms the oil pipe to
assist the initial start-up. An oil line heater is available from
Beckett using part number 51621 (Beckett Start Helper).

Electrical Wiring

All wiring must conform to the National Electric Code
(NEC), or Canadian Electric Code (CEC) and any local
codes.

 1 - Refer to the appliance rating plate for proper fuse size.

 2 - Install the room thermostat and make wire connec­

tions to the control. Avoid installing thermostat on an
outside wall or where it can be affected by radiant heat.
Set the adjustable heat anticipator on thermostat ac­
cording to the wiring diagram sticker provided on unit.

 3 - Install a separate fused disconnect switch near unit so

power can be shut off for servicing.

Summary of Contents for Elite ELO183DH Series

Page 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Page 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Page 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Page 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Page 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Page 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Page 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Page 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Page 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Page 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Page 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Page 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Page 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Page 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Page 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Page 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Page 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Page 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Page 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Page 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Page 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Reviews: