background image

Page 16

Fan Delay

Fan on time is 1 to 30 seconds and non adjustable. Fan off
time is 60 to 120 seconds and non adjustabe.

Limit Control

Limit Control — Do not adjust from factory setting.

Burner Adjustment

The following instructions are essential to the proper op­
eration of ELO183DH series oil furnaces. To prevent soot­
ing and prevent premature failure of the heat exchanger,,
these instructions must be followed in sequence:

1.

Draft

—This test should be taken at the breach be­

tween the outlet of the vent connector and the baro­
metric draft control. Generally a 1/4” hole will need to
be drilled for the draft gauge to be inserted into the vent
connector.
A minimum of 0.03 draft must be established without
the burner in operation. With the burner in operation,
the draft should be 0.04 to 0.05. This is VERY critical to
the flame retention head burners.
Oil furnace installations also require careful inspection
to make sure the chimney is in good shape and can ac­
commodate the products of combustion. The temper­
ature in the unconditioned space will also affect the
draft if long vent connectors are allowed to get too
cold.

2.

Overfire Draft

—This test should be taken with the

burner in operation. Remove the plug from the center
of the inspection port. Insert your draft gauge into the
hole.
A reading of the overfire draft should be 0.02 less than
the reading found in the vent connector. If a positive
reading is seen at this point, the combustion fan is
pumping too much air into the heat exchanger. Make
the necessary adjustments with the air shutter or air
band.

3.

Smoke Test

—The smoke test should be taken at the

hole drilled in step 1.

Air Band

(Secondary)

Air Shutter / Band Adjustment

Loosen this screw
to adjust air band.

Air Shutter

Air Band

Figure 15

Using a smoke test gun, adjust the air so that you will
have just a trace (between 0 and #1) of smoke. If the
burner is producing more than #1 smoke, adjust the air
shutter (primary) and air band (secondary) to reduce
the smoke. See figure 15. To adjust the air shutter,
loosen the top screw on the air shutter (and lower
screw, if necessary). Then, rotate the shutter until the
desired smoke level is achieved. If smoke cannot be
reduced to the desired level by moving the air shutter,
adjust the air band to increase the air. To adjust the air
band, loosen the air band screw and rotate the
band.

This is the 

starting

 point.

 

Do not stop here.

4.

CO

2

 Test

—Again, take this sample at the vent pipe.

With the unit firing at a trace of smoke, take a sample
of the CO

2

. From the results of this test, a “window of

operation” will be determined. This window of opera­
tion establishes some tolerance. The tolerance the in­
staller builds in provides room within the set‐up for
those things which might affect combustion. Those
things which might affect combustion can then do so
without causing the unit to start sooting/smoking.
Things which might affect combustion include a nozzle
going bad, draft that changes during different climatic
conditions, dirty oil, dirt obstructing the air inlet, etc.
To build in a “window of operation,” set up the burner to
be 2% less in CO

2

. For example, if you find a reading of

12% CO

2

, adjust the air shutter (and air band, if neces­

sary) to increase the air and drop the CO

2

 to 10%.

5.

Retest the Smoke

—With a drop in the CO

2

 and in­

crease in the air you should see that the smoke has re­
turned to 0.

6.

Retest the Overfire Draft

—This test serves to con­

firm that you have not increased the air too much.
Again you do not want a positive pressure at the test
port. It should still be 0.02 less than the draft pressure
reading taken at the breach. You may need to increase
the stack draft by adjusting the barometric draft con­
trol.

7.

Stack Temperature

—Take a stack temperature

reading in the vent pipe. Subtract the room air temper­
ature from the stack temperature. This will give you the
net stack temperature. Use the efficiency charts pro­
vided in most CO

2

 analyzers to determine furnace effi­

ciency.

8. When the proper combustion and smoke readings

have been achieved, re-tighten the air shutter
screw(s) and air band screw.

Service 

Servicing Filter

NOTE - Under no circumstances should the access panels
to the blower compartment be left off or left partially open.

1. Throw‐Away Type Filters — Filters should be checked

monthly and replaced when necessary to assure prop­
er furnace operation. Replace filters with like kind and
size filters.

Summary of Contents for Elite ELO183DH Series

Page 1: ...ist 1 Unit Dimensions 2 ELO183DH Unit Parts Arrangement 3 Oil Burner Parts Arrangement 3 Requirements 4 Combustion Ventilation Air 5 Installation 7 Adjustments 8 Venting 9 Flue Connections 10 Supply R...

Page 2: ...IEW SIDE VIEW FRONT VIEW FLUE OUTLET 8 203 SUPPLY AIR OPENING HORIZONTAL POSITION DOWNFLOW POSITION OPTIONAL DOWNFLOW COMBUSTIBLE FLOOR BASE OPTIONAL DOWNFLOW ADDITIVE BASE Additive Base Raises Furnac...

Page 3: ...XCHANGER CLEAN OUT PORT ELO183DH Oil Burner Parts Arrangement Figure 2 ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button OIL DELAY VALVE AIR TUBE WITH ELECTRODE ASSEMBLY AND N...

Page 4: ...the type and construction outlined in section 160 of NFPA No 31 Air for combustion and ventilation must conform to stan dards outlined in section 140 of NFPA No 31 or in Cana da CSA Standard B139 When...

Page 5: ...side for combustion Also exhaust fans ap pliance vents chimneys and fireplaces force additional air that could be used for combustion out of the house Unless outside air is brought into the home for c...

Page 6: ...per 1 000 Btu 293 W per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches 614 5 square centimeters Oil Furnace Air from Outside If air from outside i...

Page 7: ...ELO183DH furnace is shipped from the factory in the horizontal left hand air discharge application Air flow may be reversed to right side discharge or unit may be used as downflow 1 Reversing Airflow...

Page 8: ...odes The burner assembly is attached to the vestibule panel by three nuts Slots are provided in the mounting flange for re moving the burner assembly from the vestibule Loosen the nuts and turn the wh...

Page 9: ...t be smaller than the out let diameter of the vent outlet of the furnace 4 Pipe should be at least 24 gauge galvanized 5 Single wall vent pipe should not run outside or through any unconditioned space...

Page 10: ...and win dows and all doors between the space in which the ap pliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appli...

Page 11: ...is no complete return air duct sys tem a return air connection should be run the same size as the return air opening to a location outside the room containing the furnace 5 Install supply and return a...

Page 12: ...itions require that you use of a two pipe system which consists of a return line that purges the fuel pump of air by returning it to the tank To determine the run and lift for piping refer to table 5...

Page 13: ...it See figure 13 3 Attach the return and inlet pipes Start the burner Air bleeding is automatic NOTE If a faster bleed is necessary open the bleed valve 4 The return pipe must terminate 3 to 4 above t...

Page 14: ...wire WARNING Run 24V Class II wiring only through specified low voltage opening Run line voltage wiring only through specified high voltage opening Do not combine voltage in one opening CAUTION Use c...

Page 15: ...re fuel pump pressure with unit off Attach pressure gauge to pump outlet Turn unit on and check pressure and compare to table 9 Adjust if necessary Temperature Rise Adjustment To measure temperature r...

Page 16: ...rotate the shutter until the desired smoke level is achieved If smoke cannot be reduced to the desired level by moving the air shutter adjust the air band to increase the air To adjust the air band lo...

Page 17: ...f the heat exchanger Then using the hose at tachment vacuum out loose debris 4 Remove the locking screw and cap from the observa tion tube and with the spiral wire brush reach upward toward the rear o...

Page 18: ...ontinue to flow as long as cad cell senses flame D Heat fan on timing 1 to 30 seconds begins When timing is complete the indoor blower is at heat speed and warm air is delivered to the controlled spac...

Page 19: ...ls Burner motor is de energized and oil primary control goes into recycle mode If heat fan off delay is longer than the recycle delay timing the heat fan continues to run through the next trial for ig...

Page 20: ...nect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off fals...

Page 21: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 22: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 23: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 24: ...nger Clean heat exchanger Dirty burner blower wheel Clean burner blower wheel Dirty furnace air filters Clean or replace filter Restricted or closed registers or dampers Readjust registers or damp ers...

Reviews: