Page 38
TABLE 14
ACCESSORY AIR RESISTANCE
Model
C17−090/120 Coil
Pleated Filter −
1 in. (25 mm)
*Disposable Filter −
1 in. (25 mm)
EMD17M−95
EMD17M−135
cfm
L/s
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
Pa
2400
1135
0.14
35
0.17
42
0.05
12
.04
10
−−−−
−−−−
2600
1225
0.16
40
0.18
45
0.06
15
.05
12
−−−−
−−−−
2800
1320
0.19
47
0.20
50
0.07
17
.06
15
−−−−
−−−−
3000
1415
0.22
55
0.22
55
0.08
20
.07
17
.03
7
3200
1510
0.24
60
0.23
57
0.09
22
.08
20
.04
10
3400
1605
0.27
67
0.25
62
0.10
25
.09
22
.05
12
3600
1700
0.30
75
0.27
67
0.10
25
.10
25
.06
15
3800
1795
0.33
82
0.29
72
0.11
27
.11
27
.07
17
4000
1890
0.36
90
0.31
77
0.12
30
.12
30
.07
17
4200
1980
0.38
95
0.34
85
0.13
32
−−−−
−−−−
.08
20
4400
2075
0.42
104
0.36
90
0.14
35
−−−−
−−−−
.09
22
4600
2170
0.45
112
0.39
97
0.16
40
−−−−
−−−−
.10
25
4800
2265
0.48
119
0.42
104
0.17
42
−−−−
−−−−
.11
27
5000
2360
0.51
127
0.44
109
0.18
45
−−−−
−−−−
.11
27
* Furnished with filter box.
TABLE 15
DRIVE KIT SPECIFICATIONS
Additive
Cooling
Tons
Drive Kit
Model No
Voltage
& Phase
Motor Output
hp (kW)
Minimum
Circuit
Motor Pulley
(in ) & Groove
Blower Pulley
(in ) & Groove
RPM
Range
Belt
Shipping
Weight
Tons
(kW)
Model No.
& Phase
min.
max.
Circuit
Ampacity
(in.) & Groove
(in.) & Groove
Range
Belt
Weight
lbs. (kg)
DKG24−200−1
115v−1ph
25
42 (19)
7 5
10
DKG24−200−2
230v−1ph
14
42 (19)
7.5 or 10
(26.4 or
35 2)
DKG24S−200−3
208/230v−3ph 1.5 (1.1) 1.7 (1.3)
9
7/8 x 4−3/4 − A
1 x 10 − A
535 − 772
A − 52
48 (22)
35.2)
DKG24S−200−4
460v−3ph
4
48 (22)
DKG24S−200−5
575v−3ph
3
48 (22)
DKG24−200−6
208/230v−3ph
9
57 (26)
10
(35.2)
DKG24−200−7
460v−3ph
2 (1.5) 2.3 (1.7)
4
7/8 x 6 − A
1 x 10 − A
802 − 977
A − 52
57 (26)
(35.2)
DKG24−200−8
575v−3ph
3
57 (26)
Maximum usable output of motors furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used,
keep within the service factor limitations specified on motor nameplate.
At rated voltages shown.
NOTE − All drive kits include matching 24 volt control transformer. All kits (except 208/230v) include matching auto−transformer for combustion air blower operation.