Page 8
This furnace design has not been CSA international certi-
fied for installation in mobile homes, recreational vehicles,
or outdoors.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju-
ry or death.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements indicated previously, the fol-
lowing general recommendations should be considered
when installing the Lennox G24−200 furnace.
The furnace should be placed as close to the center of the
air distribution system as possible. The furnace should also
be located close to the chimney or vent termination point.
Do not install the furnace where drafts might blow directly
into it. This could cause improper combustion and unsafe
operation.
Do not block furnace combustion air openings with cloth-
ing, boxes, doors, etc. Combustion air is needed for proper
combustion and safe unit operation.
When the furnace is installed in an attic or other insulated
space, keep insulation away from the furnace.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of Cal-
ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900 USA
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, ap-
pliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house. Un-
less outside air is brought into the house for combustion,
negative pressure (outside pressure is greater than inside
pressure) will build to the point that a downdraft can occur
in the furnace vent pipe or chimney. As a result, combus-
tion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combus-
tion and ventilation, use the guidelines and procedures in
this section to install G24−200 furnaces to ensure efficient
and safe operation. You must consider combustion air
needs and requirements for exhaust vents and gas piping.
A portion of this information has been reprinted with per-
mission from the National Fuel Gas Code
(ANSI-Z223.1/NFPA54). This reprinted material is not the
complete and official position of the ANSI on the refer-
enced subject, which is represented only by the standard
in its entirety.
In Canada, refer to the standard CSA B149.1 installation
code.
CAUTION
Do not install furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
Combustion Air Requirements