Page 26
TABLE 13
G32V3-75 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Setting
Low Speed
High Speed
Setting
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
Norm
880
415
930
440
980
465
1040
490
1060
500
1105
520
1260
595
1330
630
ć
775
365
810
380
850
400
910
430
930
440
970
460
1070
505
1130
535
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Setting
Low Speed
High Speed
Setting
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
Norm
945
446
1025
484
1125
531
1270
599
1080
510
1172
533
1286
607
1452
685
ć
803
379
871
411
956
451
1080
510
918
433
996
470
1093
516
1234
582
15% lower motor speed than NORM switch setting.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown.
NOTE - Continuous Fan only speed is approximately 800 cfm (380 L/s) - non adjustable.
NOTE - Lennox Harmony II
t
zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 850
cfm (400 L/s) for all positions.
TABLE 14
G32V5-100/125 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Setting
Low Speed
High Speed
Setting
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
Norm
1140
540
1250
590
1440
680
1550
730
1620
765
1820
860
2000
945
2100
990
ć
970
455
1060
500
1280
605
1320
595
1380
650
1550
730
1700
800
1780
840
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Setting
Low Speed
High Speed
Setting
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
Norm
1140
540
1250
590
1440
680
1550
730
1560
735
1720
810
2030
960
2150 1015
ć
970
455
1060
500
1280
605
1320
595
1330
660
1460
690
1730
815
1830
865
15% lower motor speed than NORM switch setting.
G32V5-125 Models Only - Do not set switches for position #1 (at NORM or ć" setting) or position #2 (at -" setting) for HEAT speed.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown.
NOTE - Continuous Fan only speed is approximately 1150 cfm (545 L/s) - non adjustable.
NOTE - Lennox Harmony II
t
zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 1140
cfm (540 L/s) for all positions.