background image

Page 9

FIGURE 7

G32V-100 OR -125 WITH 2 IN. VENTING

G32V-100 OR -125 WITH 3 IN. VENTING

3 IN.

IN

2 IN.

OUT

3 IN. FIELD

PROVIDED

NIPPLE

3 IN. X 2 IN.

REDUCER

2 IN. VENT PIPE

3 IN.

IN

2 IN.

OUT

3 IN. VENT PIPE

3 IN. X 2 IN. REDUCER

2 IN. FIELD

PROVIDED

NIPPLE

Joint Cementing Procedure

All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.

WARNING

DANGER OF EXPLOSION! Fumes from PVC glue

may ignite during system check. Disconnect wire

from pressure switch terminal before 115 volt powĆ

er is applied to unit. Reconnect wire after two minĆ

utes of combustion air blower operation.

 1 - Measure and cut vent pipe to desired length.
 2 - Debur and chamfer end of pipe, removing any ridges

or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in

a leaking joint.

 3 - Clean and dry surfaces to be joined.
 4 - Test fit joint and mark depth of fitting on outside of

pipe.

 5 - Uniformly apply liberal coat of PVC primer for PVC or

ABS cleaner for ABS to inside socket surface of fitĆ
ting and male end of pipe to depth of fitting socket.

 6 - Promptly apply solvent cement to end of pipe and inĆ

side socket surface of fitting. Cement should be apĆ

plied lightly but uniformly to inside of socket. Take
care  to  keep  excess  cement  out  of  socket.  Apply

second coat to end of pipe.

NOTE - Time is critical at this stage. Do not allow

primer to dry before applying cement.

 7 - Immediately  after  applying  last  coat  of  cement  to

pipe, and while both inside socket surface and end of
pipe are wet with cement, forcefully insert end of pipe

into socket until it bottoms out. Turn pipe 1/4 turn durĆ

ing assembly (but not after pipe is fully inserted) to
distribute cement evenly.

NOTE - Assembly should be completed within 20 seĆ

conds  after  last  application  of  cement.  Hammer
blows should not be used when inserting pipe.

 8 - After  assembly,  wipe  excess  cement  from  pipe  at

end of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indiĆ

cate  a  defective  assembly  due  to  insufficient  sol-
vent.

 9 - Handle joints carefully until completely set.

Venting Practices

WARNING

Insufficient  combustion  air  can  cause  headaches,

nausea,  dizziness  or  asphyxiation.  It  will  also

cause excess water in the heat exchanger resulting

in  rusting  and  premature  heat  exchanger  failure.

Excessive  exposure  to  contaminated  combustion

air  will  result  in  safety  and  performance  related

problems.  Avoid  exposure  to  the  following  subĆ

stances in the combustion air supply:

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine base swimming pool chemicals

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Cements and glues

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

The thickness of construction through which vent/air inĆ
take pipes may be installed is a minimum of 3 inches (76

mm) and a maximum of 24 inches (610 mm). If a G32V
furnace replaces a furnace which was commonly vented

with another gas appliance, the size of the existing vent
pipe for that gas appliance must be checked. Without the

heat of the original furnace flue products, the existing vent
pipe is probably oversized for the single water heater or

other appliance. The vent should be checked for proper
draw with the remaining appliance.

Intake Piping

 1 - Cement intake piping in slip connector located at top

of unit.

 2 - Route piping to outside of structure. Continue with

installation  following  instructions  given  in  exhaust
and intake piping termination section.

Summary of Contents for G32V3-75

Page 1: ...mation 32 Other Unit Adjustments 32 Service 32 Repair Parts List 35 Integrated Control Board Diagnostic Codes 35 Troubleshooting 36 Start Up Performance Check List 42 WHAT TO DO IF YOU SMELL GAS Do no...

Page 2: ...DRAIN Both Sides EXHAUST AIR OUTLET COMBUSTION AIR INTAKE 21 3 4 552 7 3 8 187 23 3 4 603 25 635 5 8 16 H G 5 8 16 EXTERNAL SIDE RETURN AIR FILTER KIT Either Side Optional 23 584 D Return Air Knockout...

Page 3: ...EAT EXCHANGER ASSEMBLY CONTROL VOLTAGE CIRCUIT BREAKER WARM HEADER COLLECTOR BOX COLD HEADER COLLECTOR BOX TWO SPEED COMBUSTION AIR INDUCER COMBUSTION AIR ORIFICE BLOWER ACCESS DOOR BURNER ACCESS PANE...

Page 4: ...AN CGA B149 1 and B149 2 standards When the furnace is used with cooling units it shall be installed in parallel with or on the upstream side of cool ing units to avoid condensation in the heating com...

Page 5: ...ncy or the gas supplier CAUTION As with any mechanical equipment personal inju ry can result from contact with sharp sheet metal edges Be careful when you handle this equipment Installation Setting Eq...

Page 6: ...SIZE REQUIREMENTS UNIT MODEL NUMBER FILTER PART NUMBER FILTER SIZE G32V 75 31J81 14 inches x 25 inches 356 x 635 mm G32V 100 G32V 125 P 8 7831 20 inches x 25 inches 508 x 635 mm Bottom Return Air Appl...

Page 7: ...errack usingscrews When using screws take care to avoid interference with the fil ter which may cause improper filtration The return air must not be drawn from a room where another gas appliance ie a...

Page 8: ...umber of elbows the larger diameter pipe must be used for both runs TABLE 5 VENT PIPE SIZING TABLE FOR G32V FURNACES MINIMUM DIAMETER OF INTAKE EXHAUST PIPE Vent Pipe Equivalent Length Max Feet Meters...

Page 9: ...mpleted within 20 se conds after last application of cement Hammer blows should not be used when inserting pipe 8 After assembly wipe excess cement from pipe at end of fitting socket A properly made j...

Page 10: ...lo cated and other spaces of the building Turn on clothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so th...

Page 11: ...erioration NOTE During extremely cold temperatures below approximately 20 F 6 67 C units with long runs of vent pipe through unconditioned space even when in sulated may form ice in the exhaust termin...

Page 12: ...L Inches mm SIDE VIEW WALL RING TERMINATION 15F74 LB 49107CB for 2 in 51 Venting INTAKE PIPE EXHAUST PIPE 9 Position termination ends so they are free from any obstructions and above the level of snow...

Page 13: ...trapping or a large wire tie 11 In areas where piping penetrates joists or interior walls hole must be large enough to allow clearance on all sides of pipe as it passes through the center of the hole...

Page 14: ...h 1 2 inch 13 mm foam insulation If intake and ex haust pipes are reversed slit and remove foam insulation and reapply to other vent Exhaust vent must be insulated Front View Side View OUTSIDE WALL In...

Page 15: ...r and must be water tight Teflon tape is recommended to seal the joint Right Hand Side Condensate Exit Install the nipple adapter assembly from the out side of the cabinet and insert the adapter into...

Page 16: ...ace The piping must be supported at proper inter vals every 8 to 10 feet 2 44 to 3 01 m using suit able hangers or straps A drip leg should be installed in vertical pipe runs to the unit 5 In some loc...

Page 17: ...ted control ELECTROSTATIC DISCHARGE ESD Precautions and Procedures CAUTION Electrostatic discharge can affect electronic com ponents Take precautions during furnace installa tion and service to protec...

Page 18: ...leg of the circuit being connected to the neutral HUM terminal See figure 29 for control board con figuration This terminal is energized in the heating mode whenever the combustion air inducer is ope...

Page 19: ...Page 19 TYPICAL G32V SCHEMATIC WIRING DIAGRAM FIGURE 27...

Page 20: ...ring Connections 1 Heat 1 Cool NOTE Use dip switch 3 to set second stage heat ON delay ON 10 minutes OFF 15 min utes SINGLE Yes Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 1 Cool wi...

Page 21: ...s OFF 15 min utes SINGLE No Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool with CCB1 NOTE Use dip switch 3 to set second stage heat ON delay ON 10 minutes OFF 15 min utes SINGLE...

Page 22: ...outdoor unit and thermostat made at FM21 control board per FM21 instructions NOTE Remove Y1 Y2 jumper for two stage cooling Harmony Application 2 Heat 1 Cool TWO Yes Cut Intact TEMP MOD SWITCH CONTRO...

Page 23: ...l break and remake thermostat demand to the furnace and auto matically reset the control to relight the furnace Thermostat Selection Jumper E20 This unit may be used with either a single stage or two...

Page 24: ...to better suit the application The table below provides blower speed adjustments that will result from different switch settings Refer to tables 13 and14 for corresponding cfm values TABLE 10 Blower...

Page 25: ...two speed outdoor unit On Board Jumper W951 On board jumper W951 which connects terminals R and O on the integrated control board must be cut when the furnace is installed in applications which inclu...

Page 26: ...y 850 cfm 400 L s for all positions TABLE 14 G32V5 100 125 BLOWER MOTOR PERFORMANCE 0 0 to 0 8 w g 0 through 200 Pa External Static Pressure Range Blower Speed Adjustment Settings Switches 5 and 6 Coo...

Page 27: ...atically lights the burner Do not try to light the burner by hand 5 Remove unit access panel 6 Turn gas valve knob to OFF position See figure 30 7 Wait five 5 minutes to clear out any gas If you then...

Page 28: ...Thermostat Selection Jumper E20 in Single Stage Position NOTE In these applications two stage heat will be initi ated by the integrated control if heating demand has not been satisfied after the field...

Page 29: ...ow er speed immediately increases to the COOL CFM to hasten the end of the cycle Call for cooling after call for humidity None Humidity level above set point Demand initiated Off Dehumidification mode...

Page 30: ...evel rises slightly 1 above setpoint Demand initiated High 77 74 of HIGH COOL Blower immediately changes speed in response to thermostat demand demand Y2 No demand Acceptable High HIGH COOL Call for 1...

Page 31: ...stment NOTE Pressure test adaptor kit 10L34 is available from Lennox to facilitate manifold pressure measure ment 1 Connect test gauge to outlet tap on gas valve 2 Disconnect pressure sensing hose fro...

Page 32: ...me by observation Flame should be predominantly blue and strong in appearance Check burner flame periodically to ensure proper opera tion Service WARNING Disconnect power before servicing unit CAUTION...

Page 33: ...tibule panel and heat exchanger assembly to cabinet Remove heat exchanger 21 Back wash heat exchanger with soapy water solu tion or steam If steam is used it must be below 275 F 135 C 22 Thoroughly ri...

Page 34: ...ckage caused by foreign matter Remove any blockage 14 Reinstall ignitor and sensor bracket assemblies on burners NOTE Install the ignitor on the opposite side of the burner from the metal button protr...

Page 35: ...limit or rollout limit switch open Limits must close within 3 minutes or unit goes into 1 hour Watchguard OFF SLOW FLASH Low fire pressure switch open OR Blocked inlet exhaust vent OR Low fire pressu...

Page 36: ...H DS 2 SIMULTANEOUS FAST FLASH YES PRIMARY LIMIT SWITCH CLOSED YES NO COMBUSTION AIR INDUCER OFF INDOOR BLOWER ON HAS PRIMARY LIMIT RESET WITHIN 3 MINUTES DS1 SLOW FLASH DS2 ON ON OFF LED ON HEAT LED...

Page 37: ...R IS REPLACED OR RECONNECTED DS1 AND DS2 ALTERNATING FAST FLASH YES AT END OF IGNITOR 20 SECOND WARM UP PERIOD 4 SECOND TRIAL FOR IGNITION GAS VALVE OPENS IGNITOR ENERGIZED DURING 4 SECOND TRIAL UNTIL...

Page 38: ...INDOOR BLOWER OFF AFTER DELAY DS1 OFF DS 2 SLOW FLASH ON OFF LED OFF HEAT LED ON NO YES C FIRST STAGE HEAT DEMAND SATISFIED DS1 AND DS2 SIMULTANEOUS SLOW FLASH GAS VALVE OFF COMBUSTION AIR INDUCER OF...

Page 39: ...D IS SATISFIED A FIVE 5 MINUTE WAIT PERIOD IS INITIATED BEFORE RETRY WERE 5 ATTEMPTS MADE FOR SECOND STAGE HEAT YES NO SEE BOX C FIRST STAGE HEAT DEMAND SATISFIED HEAT DEMAND SATISFIED DS1 AND DS2 SIM...

Page 40: ...OLTS LOW VOLTAGE SIGNAL AT DS HOLDS UNTIL VOLTAGE RISES ABOVE 75 VOLTS NO YES NO SIGNAL IMPROPER GROUND AT DS SIGNAL HOLDS UNTIL UNIT IS PROPERLY GROUNDED INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL S...

Page 41: ...TCHES TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAGE HE...

Page 42: ...Heating Section Thermostat Heat Anticipator Setting Thermostat Level Fuel Type Natural Gas Blower Motor Amps Blower Motor H P Gas Piping Connections Tight Leak Tested Proper Draft State Blower OFF De...

Reviews: