Page 4

BLOWER PERFORMANCE

G41UF−24B−045 PERFORMANCE

External Static

Air Volume / Watts at Different Blower Speeds

External Static

Pressure

High

Medium

Low

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

0.00

0

1225

580

485

1000

470

365

820

385

290

0.10

25

1190

560

455

990

470

355

815

385

275

0.20

50

1160

545

435

970

460

340

805

380

265

0.30

75

1120

530

415

945

445

325

780

365

260

0.40

100

1070

505

395

910

430

305

755

355

245

0.50

125

1015

480

375

865

405

295

740

350

240

0.60

150

955

450

355

835

395

285

695

325

225

0.70

175

885

415

335

750

355

260

640

300

210

0.80

200

825

390

320

695

330

245

545

255

185

0.90

225

715

335

3000

600

285

220

435

205

170

NOTES −  All air data is measured external to unit without filter (not furnished − field provided).

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

G41UF−36B−045 PERFORMANCE

External Static

Air Volume / Watts at Different Blower Speeds

External Static

Pressure

High

Medium−High

Medium−Low

Low

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

0.00

25

1555

735

630

1410

665

585

1190

560

520

1030

485

435

0.10

25

1515

715

605

1385

655

555

1190

560

485

1020

480

415

0.20

50

1470

695

580

1345

635

520

1170

550

455

1010

475

400

0.30

75

1410

665

555

1310

620

495

1155

545

440

1000

470

385

0.40

100

1350

640

535

1250

590

465

1120

530

410

980

465

360

0.50

125

1290

610

505

1205

570

450

1080

510

390

950

450

345

0.60

150

1220

575

485

1145

540

420

1020

480

365

905

430

320

0.70

175

1145

540

460

1080

510

400

975

460

345

860

405

300

0.80

200

1050

495

425

985

465

365

870

410

320

785

370

285

0.90

225

945

445

410

900

425

345

825

390

305

730

345

270

NOTES −  All air data is measured external to unit without filter (not furnished − field provided).

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

G41UF−36B−070 PERFORMANCE

External Static

Air Volume / Watts at Different Blower Speeds

External Static

Pressure

High

Medium−High

Medium−Low

Low

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

0.00

0

1640

775

660

1415

665

575

1160

545

485

1005

475

410

0.10

25

1600

755

635

1395

660

550

1160

545

460

1000

470

385

0.20

50

1540

725

605

1370

650

525

1160

545

445

995

470

375

0.30

75

1495

705

580

1345

635

505

1145

540

425

990

465

365

0.40

100

1420

670

545

1275

605

480

1125

530

395

965

455

345

0.50

125

1360

640

525

1245

590

450

1080

510

375

945

445

325

0.60

150

1275

600

490

1165

550

410

1025

485

350

900

425

305

0.70

175

1170

555

465

1085

515

385

965

430

335

860

405

295

0.80

200

1080

510

440

1010

475

360

865

410

310

775

365

270

0.90

225

945

445

400

840

395

320

765

360

275

710

 335

245

NOTES −  All air data is measured external to unit without filter (not furnished − field provided).

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

G41UF−36C−090 PERFORMANCE

External Static

Air Volume / Watts at Different Blower Speeds

External Static

Pressure

High

Medium−High

Medium−Low

Low

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

0.00

0

1705

805

730

1395

660

605

1195

555

495

1010

475

410

0.10

25

1680

795

700

1390

650

585

1185

560

480

1005

475

395

0.20

50

1645

775

675

1380

650

560

1175

555

465

1000

470

390

0.30

75

1600

755

635

1365

645

535

1165

550

445

995

470

375

0.40

100

1560

735

615

1345

635

515

1155

545

425

990

465

360

0.50

125

1495

705

580

1305

615

500

1125

530

400

970

460

345

0.60

150

1415

665

540

1270

600

475

1080

510

375

940

445

320

0.70

175

1330

630

505

1205

570

435

1035

490

360

890

420

300

0.80

200

1255

590

485

1120

530

400

955

450

330

840

395

280

0.90

225

1135

535

450

1020

480

365

830

390

300

760

360

260

NOTES −  All air data is measured external to unit without filter (not furnished − field provided).

Air volume based on bottom air return air. Actual air volume may vary on side return air applications.

Summary of Contents for G41UF?24B?045

Page 1: ...d in this manual is intended for use by qualified service technicians only All specifications are sub ject to change Procedures outlined in this manual are pre sented as a recommendation only and do n...

Page 2: ...x 17 5 8 x 28 5 8 102 x 448 x 727 4 x 21 5 8 x 28 5 8 102 x 549 x 727 Number and size of field provided filter in mm 16 x 25 x 1 406 x 635 x 25 20 x 25 x 1 508 x 635 x 25 Condensate Drain Heat 6 ft 1...

Page 3: ...x 24 x 1 in 610 x 610 x 25 mm Condensate Drain Heat 6 ft 1 8 m long 26K68 26K68 26K68 26K68 Drain Heat Cable 24 ft 7 3 m long 26K69 26K69 26K69 26K69 50 ft 15 2 m long 26K70 26K70 26K70 26K70 Heat Ca...

Page 4: ...ide return air applications G41UF 36B 070 PERFORMANCE External Static Air Volume Watts at Different Blower Speeds External Static Pressure High Medium High Medium Low Low in w g Pa cfm L s Watts cfm L...

Page 5: ...815 885 1640 775 720 1555 735 625 1340 630 510 NOTES All air data is measured external to unit without filter not furnished field provided G41UF 60C 090 PERFORMANCE Bottom Return Air Side Return Air w...

Page 6: ...660 1430 675 580 NOTES All air data is measured external to unit without filter not furnished field provided G41UF 60D 135 PERFORMANCE Single Side Return Air Air volumes in bold require field fabrica...

Page 7: ...AND MANIFOLD SIGHT GLASS DuralokPlusTM HEAT EXCHANGER ASSEMBLY CONDENSER COIL CONTROL BOX DOOR INTERLOCK SWITCH COLD HEADER COLLECTOR BOX COMBUSTION AIR INDUCER BLOWER ACCESS DOOR BURNER ACCESS PANEL...

Page 8: ...azard Disconnect power before servicing Control is not field repairable If control is inoperable sim ply replace entire control Can cause injury or death Unsafe operation will result if repair is atte...

Page 9: ...oes into Watchguard Flame Failure mode After a 60 min ute reset period the control will begin the ignition sequence again The SureLight control board has an added feature that pro longs the life of th...

Page 10: ...feature of the board voltage cannot be measured so ignitor must be ohmed Ohm value should be 10 9 to 19 7 FIGURE 6 13 32 5 8 SureLight Ignitor Location BURNERS FRONT VIEW MEASUREMENT IS TO I D OF RETE...

Page 11: ...ners failed to ignite SLOW FLASH OFF Flame sensed without gas valve energized ON SLOW FLASH Rollout switch open OR 12 pin connector improperly attached ON ON ON OFF Circuit board failure or control wi...

Page 12: ...CLAMSHELL Each Segment CONDENSER COIL WARM END HEADER BOX COLD END HEADER BOX COMBUSTION AIR INDUCER PROVE SWITCH TUBING PROVE SWITCH BURNER BOX ASSEMBLY LIMIT CONTROL SURELIGHT IGNITOR GAS VALVE ROL...

Page 13: ...up secondary limit control S113 is a N C auto reset switch located on the combustion air inducer See figure 9 for approximate location S113 acts as a backup to primary limit S10 in the event of an ind...

Page 14: ...G41UF units is factory preset to open at 280_F 12_F 138_C 6 7_C on a temperature rise All flame rollout switches are manually reset FIGURE 11 BURNER BOX ASSEMBLY FLAME ROLLOUT SWITCH S47 MANIFOLD GAS...

Page 15: ...l will not initiate ignition at start up FIGURE 13 COMBUSTION AIR PROVE SWITCH S18 PROVE SWITCH S18 PROVE SWITCH HOSE COLD END HEADER BOX ON OFF PROVE SWITCH BRACKET TAP TERMINALS TABLE 7 G41UF Unit S...

Page 16: ...not be used when inserting pipe 8 After assembly wipe excess cement from pipe at end of fitting socket A properly made joint will show a bead around its entire perimeter Any gaps may indi cate a defe...

Page 17: ...NG AND CONDENSATE TRAP INSTALLATION Right Hand Exit Shown CONDENSATE TRAP Must be installed on same side as exhaust piping VENT PLUG Must be glued in place PLUG FIGURE 18 PLUG TYPICAL G41UF 60D 135 VE...

Page 18: ...s and Propane appliances venting sizing tables in the cur rent standard of the CSA B149 1 Natural Gas and Propane Installation Code in Canada 9 After determining that each appliance remaining connecte...

Page 19: ...nimum for vent installations in Canada see current edition of CSA B149 Code E Clearance to non mechanical air supply inlet for vent installations in USA 12 in 305mm for vent installations in Canada 12...

Page 20: ...igure 16 Refer to figure 22 for proper piping method When exhaust piping must be run up an outside wall any reduction in exhaust pipe size must be done after the final elbow FIGURE 22 12 305 ABOVE AVE...

Page 21: ...t may be used on the condensate trap and line Heating cable kit is available from Lennox in various lengths 6 ft 1 8m kit no 18K48 24 ft 7 3m kit no 18K49 and 50 ft 15 2m kit no 18K50 CAUTION Do not u...

Page 22: ...s line 12 If the appliance will not operate follow the instructions Turning Off Gas to Unit and call your service techni cian or gas supplier Turning Off Gas to Unit 1 Set the thermostat to the lowest...

Page 23: ...TABLE 9 Conversion Kit and Prove Switch Requirements at Varying Altitudes Altitude Model Input Si Gas 0 4500 ft 0 1372 m 4 501 7500 ft 1373 2286 m 7501 10 000 ft 2286 3048 m p Size Required Prove Swi...

Page 24: ...c operation or underfire High pressure can result in permanent damage to gas valve or overfire For natural gas units operating pressure at unit gas connection must be between 4 5 W C and 13 0 W C For...

Page 25: ...9 48C 090 6 8 7 8 8 0 9 0 8 1 9 1 8 9 9 9 60C 090 6 8 7 8 7 6 8 6 7 9 8 9 8 5 9 5 48C 110 6 9 7 9 7 5 8 5 7 7 8 7 8 4 9 4 60C 110 6 8 7 8 7 2 8 2 8 0 9 0 8 8 9 8 60D 135 7 4 8 4 7 8 8 8 8 1 9 1 8 7 9...

Page 26: ...sted on the unit rating plate If the temperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable in crease blower speed t...

Page 27: ...umes which could contain carbon monoxide can be drawn into living space resulting in personal injury or death B Filters All G41UF filters are installed external to the unit Filters should be inspected...

Page 28: ...exchanger with soapy water solution or steam If steam is used it must be below 275 F 135 C 21 Thoroughly rinse and drain the heat exchanger Soap solutions can be corrosive Take care to rinse entire a...

Page 29: ...f the burners and crossovers for any block age caused by foreign matter Remove any blockage 7 Reconnect the sensor wire and reconnect the 2 pin plug to the ignitor wiring harness 8 Reinstall the burne...

Page 30: ...trol goes into 5 minute Watchguard Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control A92 energizes ignitor A 20 sec ond warm up period begins 5 Gas valve opens fo...

Page 31: ...VE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence hol...

Page 32: ...LAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LEDs SIGNAL WATCHGUARD FAILURE CODE IS 60 MINUTE RESET...

Page 33: ...D SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY COOLING SPEED EAC H TERM ENERGIZED COMPRESSO...

Page 34: ...ERMINAL IS ENERGIZED THERMOSTAT CALLS FOR HEAT W THERMOSTAT CALLS FOR COOLING THERMOSTAT OPENS SYSTEM FAN SWITCHED TO COOL H SPEED EAC H TERM REMAINS ON THERMOSTAT OPENS CONTROL G ENERGIZES SYSTEM FAN...

Page 35: ...h by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace code LED 1 O 1 2 2 Roll out switch failure ACTION 1 Check continuity across roll out s...

Page 36: ...BLOWER DOES NOT ENERGIZE Condition Possible Cause Corrective Action Comments 2 1 Unit operates with a cooling or contin uous fan demand Combustion air inducer will not start with a Heating demand Diag...

Page 37: ...switch lines with a heating demand Diagnostic lights flash the pressure switch failure code 2 5 minutes after heating demand 3 1 2 Prove switch does not close due to obstructions in the pressure line...

Page 38: ...nt termination kit installed See Placement and Installation section Diagnostic lights flash the pressure switch code LED 1 Off 5 1 3 Condensate drain line is not draining properly ACTION 1 Check conde...

Page 39: ...sembly Condition will cause high CO2 with high CO ACTION 2 Seal leakage if possible replace heat exchanger if necessary tag and return heat exchanger to proper Lennox personnel 5 3 4 Insufficient flow...

Page 40: ...tion Comments 7 0 Indoor blower fails to operate in continuous fan cooling or heating mode 7 1 1 Miswiring of furnace or improper con nections at control or indoor blower motor ACTION 1 Correct wiring...

Reviews: