Page 36
SureLight
®
Control Troubleshooting: Continuous Fan Sequence of Operation
SURELIGHT
®
CONTROL
CONTINUOUS FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES INDOOR BLOWER AT
FAN SPEED. EAC TERM. IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS. COMBUSTION AIR INDUCER
AND HUM TERMINAL ARE DE−ENERGIZED.
INDOOR BLOWER SWITCHES TO COOL SPEED.
THERMOSTAT OPENS.
INDOOR BLOWER SWITCHES TO FAN
SPEED. EAC TERM. REMAINS ENERGIZED.
NO
YES
YES
NO
HUM TERM. ENERGIZES
WITH COMB. AIR INDUCER.
INDOOR BLOWER SWITCHES TO HEAT SPEED
AFTER NORMAL DELAY.
INDOOR BLOWER SELECTED TIME OFF DELAY BEGINS.
AFTER DELAY HEAT SPEED DE−ENERGIZED.
(blower remains energized during continuous fan mode).
G50DF(X) Start−Up & Performance Check List
Filter Clean & Secure?
Electrical Connections Tight?
Job Name
Job Location
Installer
Unit Model No.
Furnace Btu Input
Line Pressure
Job No.
City
City
Serial No.
Date
State
Technician
Flue Connections Tight?
Heating Section
Thermostat
Calibrated?
Heat Anticipator Properly Set?
Level?
Fuel Type: Natural Gas?
Blower Motor H.P.
Gas Piping Connections Tight & Leak−Tested?
Proper Draft?
Vent Clear?
State
Temperature Rise
Fan Control Off Setting
Fan Control Setting (45 Seconds Fixed On)
Regulator Pressure
w.c. − Nat.:
LP/Propane Gas?
Combustion Gas Tested?
CO
2
CO
Supply Voltage
Blower Motor Amps
w.c. − LP/Propane