background image

Page 12 

Figure 10 illustrates the relationship between liquid line siz
ing, pressure drop per 100 feet, velocity range, and ton
nage. Remember, when using liquid line solenoid valves,
velocities should not exceed 300 fpm (1.5 m/s). Find the
cooling capacity on the left side of the chart in figure 10,
then proceed right to the smallest tube size that will not ex
ceed 300 fpm (1.5 m/s) velocity.

Table 3

Equivalent Length in Feet of Straight Pipe for

Valves and Fittings

Line
Size
O.D.

in.

Solenoid/

Globe

Valve

Angle

Valve

90°

Long*

Radius

Elbow

45°

Long*

Radius

Elbow

Tee

Line

Tee

Branch

3/8

7

4

0.8

0.3

0.5

1.5

1/2

9

5

0.9

0.4

0.6

2.0

5/8

12

6

1.0

0.5

0.8

2.5

3/4

14

7

1.3

0.6

0.9

3.0

7/8

15

8

1.5

0.7

1.0

3.5

11/8

22

12

1.8

0.9

1.5

4.5

13/8

28

15

2.4

1.2

1.8

6.0

15/8

35

17

2.8

1.4

2.0

7.0

21/8

45

22

3.9

1.8

3.0

10

25/8

51

26

4.6

2.2

3.5

12

NOTE − Long radius elbow. Multiply factor by 1.5 for short radius el
bow equivalent length.

Equipment that is above five tons in capacity typically oper
ates at a saturated condensing temperature of 125°F
(52°C) which corresponds to an operating pressure of 280
psig (1930 kPa). This equipment is designed to hold a
charge allowing 10°F (6°C) subcooling at 95°F (53°C) am
bient. Use the condensing temperature and the subcooling
to calculate the maximum allowable pressure drop as de
tailed below.

NOTE − 95

°

F (53

°

C) ambient is an arbitrary temperature

chosen to represent typical summer operating conditions
and the maximum allowable pressure drop. This tempera
ture (and the corresponding subcooling) will vary with re
gional climate.

Example − Calculating maximum allowable pressure
drop:

 Find the maximum allowable liquid line pressure

drop of a unit operating at 10°F (6°C) subcooling, 125°F
(52°C) condensing temperature and operating pressure of
280 psig (1931 kPa). Subtract 10°F (6°C) subcooling tem
perature from 125°F (52°C) condensing temperature to
equal 115°F (46°C) subcooled liquid temperature. This
corresponds with operating pressure of 245 psig (1689
kPa), which is the point at which flash gas will begin to form.
Subtract 245 psig (1689 kPa) subcooled pressure from 280
psig (1931 kPa) condensing pressure to find a maximum
allowable pressure drop of 35 psig (241 kPa).

To calculate the actual pressure drop in the liquid line, cal
culate the pressure drop due to 

friction

 and the pressure

drop due to 

vertical lift, 

then

 

add the two:

Pressure drop due to friction

 +

Pressure drop due to vertical lift

=

Pressure drop in

the liquid line

You must consider the pressure drop due to friction in the
pipe, fittings, and fieldinstalled accessories such as driers,
solenoid valves, or other devices. Pressure drop ratings for
different pipe sizes are listed in figure 10. Pressure drop
ratings of fieldinstalled devices are typically supplied by
the manufacturer.

Pressure drop due to vertical lift (1/2 pound per foot) is
typically high and can be a limiting factor in the design of
the system.

The liquid refrigerant pressure must be sufficient to pro
duce the required flow through the expansion device. Liq
uid refrigerant (free of flash gas) should be delivered to the
expansion valve at a minimum of 175 psig (1207 kPa) to
ensure that the 100 psig (690 kPa) necessary to produce
full refrigerant flow is at the rated capacity.

Example − Liquid Line Pipe Sizing

Given:

 10ton condensing unit on ground level with a

10ton evaporator on the third level above ground and a to
tal of 96 linear feet of piping. The unit is charged with 10°F
(6°C) subcooling at 125°F (52°C) condensing temperature
and an operating pressure of 280 psig (1930 kPa). Refer to
figure 11.

Find:

 Select tube size from figure 10.

given; 10 ton evaporator

10 ton condensing unit

with 10°f subcooling at 125°F

length of line − 96 ft.

find: liquid line size

10 ton

condensing unit

10 ton

evaporator

53 FT.

3 ft.

40 ft.

Liquid Line Sizing Example

Figure 11

filter/drier

4.25 psig

100 ft.

x 98 ft. = 4.17psig

Answer:  5/8 in. o.d. copper tubing can be used. Pressure loss does not exceed maximum
allowable pressure drop (6

_

F to 7

_

F subcooling will be available at the expansion valve)

and velocity is acceptable.

select a proposed tubing

size: 5/8 in. copper

solution: 

pressure drop

cannot exceed

35 psig.

total pressure drop=

total friction lift filter/drier

total equivalent length = 

linear equivalent length of fittings

two 90° long radius elbows @ 5/8 in. o.d. = 1ft. equiv. ft. ea.

total equivalent length = 98 ft.

total friction losses =

lift losses = 40 ft. x 1/ 2 psig per foot = 20 psig

total pressure drop = 20 psig + 4.17 psig + 1 psig = 25.17 psig

filter drop = 1 psig (by manufacturer)

Solution:

 For a 10−ton system, select a 5/8 inch O.D. line

with 4.25 psig (29 kPa) per 100 feet drop (per figure 10).
Now, calculate pressure drop due to friction and liquid lift to
determine if this is a good selection.

Summary of Contents for HS29-072

Page 1: ...ting 7 Electrical 7 Plumbing 10 Service Valves 17 Leak Testing 18 Evacuation Dehydration 18 Start Up 19 Charging 20 System Operation 21 Maintenance 21 Start Up Performance Check List 22 Shipping Packi...

Page 2: ...et Air Inlet Air AA BB CC DD Center Of Gravity EE FF AA BB CC DD Center Of Gravity EE FF Compressor A 3 1 4 83 34 864 B Control Box Access Side View Lifting Holes For Rigging Forklift Slots Both Sides...

Page 3: ...l Outdoor Fans And Guards 2 Control Box Lifting Holes For Rigging Forklift SlotS Both Sides Discharge Air Inlet Air Electrical Inlets Either Side Liquid Line Either Side 1 7 16 37 6 5 8 168 4 3 8 111...

Page 4: ...lve low pressure switch S87 low ambient switch S11 fan guard compressor B1 liquid line service valve HS29 120 Unit Parts Arrangement Figure 2 condenser fan motor B4 B5 control box low ambient switch S...

Page 5: ...C1 minimum run timer DL33 outdoor fan relay K10 latching relay K167 ground lug HS29 120 Control Box Arrangement Figure 4 contactor K1 low ambient thermostat S41 capacitor C1 C2 latching relay K167 ou...

Page 6: ...ve grade to allow water to drain adequately Locate the top of the slab so that run off water from higher ground will not collect around the unit Roof Mounting Install the unit at a minimum of 4 inches...

Page 7: ...y and maximum overcurrent protection size WARNING Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death Line Voltage Knockouts are provided...

Page 8: ...Page 8 Typical Unit Wiring Diagram HS29 072 090 Figure 8...

Page 9: ...Page 9 Typical Unit Wiring Diagram HS29 120 Figure 9...

Page 10: ...elihood of slugging is greatly increased if the lines are over 50 feet 15 m An incremental increase in liquid line size results in a 40 to 50 percent increase in liquid refriger ant to fill the line T...

Page 11: ...2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Liquid Line Pressure Drop lbs 100 Feet NOTE Shaded area represents unacceptable velocity range Figure 10 12 5 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 5 8 IN O D...

Page 12: ...e drop due to friction and the pressure drop due to vertical lift then add the two Pressure drop due to friction Pressure drop due to vertical lift Pressure drop in the liquid line You must consider t...

Page 13: ...00 fpm velocity for oil entrainment In order to ensure oil entrainment suction risers require a mini mum velocity of 1200 fpm 1500 fpm is preferred re gardless of the length of the riser Figure 14 ill...

Page 14: ...0 9 8 7 6 5 4 3 2 1 5 1 0 9 8 7 6 5 4 3 2 HCFC 22 Suction Line Pressure Drop lbs 100 Feet NOTE Shaded area denotes unacceptable velocity range Figure 14 40 30 20 15 40 30 20 15 EXAMPLE 10 TON UNIT 1 3...

Page 15: ...ss of 1 8 psig Use figure 14 to calculate the pressure drop in 25 feet of 1 3 8 inch line Multiply 2 100 by 25 feet to calculate friction loss of 0 5 psig This loss has already been included in the ca...

Page 16: ...ells Find Select tube sizes for horizontal runs and risers fig ure 14 Determine if double suction risers are necessary Size the double suction riser for proper system perfor mance Solution Size each s...

Page 17: ...psig The total pressure drop for the riser is equal to the average of the pressure drop in both risers 1 4 B riser drop 1 26 A riser drop 2 66 2 66 2 1 33 average pressure drop through A and B risers...

Page 18: ...Schrader valve core is present in this valve A cap is also provided to seal off the service port The valve is not re buildable so it must always be replaced if failure has oc curred Opening the Suctio...

Page 19: ...the manifold gauge set to the service valve ports as follows D low pressure gauge to suction line service valve D high pressure gauge to liquid line service valve 3 Purge the system of dry air helium...

Page 20: ...isted on the unit nameplate If it is not do not start the equipment until you have consulted the power company and the volt age condition has been corrected 5 To start the unit set the thermostat for...

Page 21: ...1 105_F 40_C 298 71 308 82 314 77 290 73 115_F 46_C 333 72 342 83 352 79 328 74 HS29 072 tested with CB30U 65 Pressure shown is with typical 5 ton indoor coil match up HS29 072 and HS29 090 tested wit...

Page 22: ...time control This control prevents the compressor from short cycling and ensures that the oil returns to the compressor properly When a cooling cycle begins the run time control keeps the compressor o...

Page 23: ...al ____________ Start Up Performance Check List HS29 072 090 120 Job Name Job Location Installer Unit Model No Nameplate Voltage Minimum Circuit Ampacity Maximum Overcurrent Protection Size Refrigeran...

Reviews: